Rack Mount Safety Information
Caution
Due to the device weight, two people should work together to mount the
device in a rack.
Caution
Install the unit as low as possible in the rack to maintain a lower center of
gravity and prevent the rack from tipping when moved.
Follow these safety guidelines when installing the device in a rack:
•
Elevated Operating Ambient
—If installed in a closed or multi-unit rack assembly, the
operating ambient temperature of the rack environment may be greater than room ambient
temperature. Therefore, you should install the equipment in an environment compatible
with the maximum ambient temperature (T
ma
) of 40 °C.
•
Reduced Air Flow
—When installing the equipment in a rack or cabinet, do not
compromise the amount of airflow required for safe operation of the equipment.
•
Mechanical Loading
—When mounting the equipment in the rack or cabinet, avoid uneven
mechanical loading that could create a hazardous condition.
•
Circuit Overloading
—When connecting the equipment to the supply circuit, avoid
overloading the circuits. Refer to equipment nameplate ratings to avoid damaging over
current protection and supply wiring.
•
Reliable Earthing
—Maintain reliable earthing of rack-mounted equipment, especially
when using supply connections other than direct connections to the branch circuit (for
example, power strips).
•
Redundant Power Supplies
—Where redundant power supplies are provided with the
equipment, connect each power supply to a separate circuit to optimize the equipment
redundancy.
•
Servicing
—Prior to servicing the equipment, disconnect all power supplies.
Electromagnetic Compatibility Guidelines
This product was tested and complies with the regulatory requirements and limits for
electromagnetic compatibility (EMC) stated in the product specifications. These requirements
and limits provide reasonable protection against harmful interference when the product is
operated in the intended operational electromagnetic environment.
This product is intended for use in industrial locations. However, harmful interference may
occur in some installations, when the product is connected to a peripheral device or test object,
or if the product is used in residential or commercial are-as. To minimize interference with radio
and television reception and prevent unacceptable performance degradation, install and use this