The following recommendations apply for all signal connections to the
DAQPad-MIO-16XE-50:
•
Separate DAQPad-MIO-16XE-50 signal lines from high-current or
high-voltage lines. These lines are capable of inducing currents in
or voltages on the DAQPad-MIO-16XE-50 signal lines if they run in
parallel paths at a close distance. To reduce the magnetic coupling
between lines, separate them by a reasonable distance if they run in
parallel, or run the lines at right angles to each other.
•
Do not run signal lines through conduits that also contain power lines.
•
Protect signal lines from magnetic fields caused by electric motors,
welding equipment, breakers, or transformers by running them through
special metal conduits.
For more information, refer to the NI Developer Zone tutorial,
Field Wiring
and Noise Considerations for Analog Signals
, at
ni.com/zone
.