PRO-2200
Single Reader Enclosure
Installation Guide
Part Number: PRO22ENC4
WARNINGS AND CAUTIONS
WARNING
Before installation, turn off the external circuit breaker which supplies power to the system.
Before connecting the device to the power supply, verify that the output voltage is within specifications of the power supply.
Do not apply power to the system until after the installation has been completed. Personal injury or death could occur, and the equipment
could be damaged beyond repair if these WARNINGS are not observed!
Fire Safety and Liability Notice
Never connect card readers to any critical entry, exit door, barrier, elevator or gate without providing an alternative exit in accordance with
all fire and life safety codes pertinent to the installation. These fire and safety codes vary from city to city and you must get approval from
local fire officials whenever using an electronic product to control a door or other barrier. Use of egress buttons, for example, may be illegal
in some cities. In most applications, single action exit without prior knowledge of what to do is a life safety requirement. Always make cer-
tain that any required approvals are obtained in writing. DO NOT ACCEPT VERBAL APPROVALS, THEY ARE NOT VALID.
Engineered Systems never recommends using the PRO-2200 Series or related products for use as a primary warning or monitoring system.
Primary warning or monitoring systems should always meet local fire and safety code requirements. The installer must also test the system
on a regular basis and instruct the end user in appropriate daily testing procedures. Failure to test a system regularly could make installer
liable to the end user for damages if a problem occurs.
WARNING
EARTH ground all enclosures, for proper installation.
WARNING
Use suppressors on all door strikes. Use S-4 suppressors for installation. Engineered Systems recommends only DC strikes.
CAUTION
IF ANY DAMAGE TO THE SHIPMENT IS NOTICED, A CLAIM MUST BE FILED WITH THE COMMERCIAL CARRIER RESPONSIBLE.
CAUTION
Electro-static discharge can damage CMOS integrated circuits and modules.
To prevent damage always follow these procedures:
Use static shield packaging and containers to transport all electronic components, including completed reader assemblies.
Handle all ESD sensitive components at an approved static controlled workstation. These workstations consist of a desk mat, floor mat and
an ESD wrist strap. Workstations are available from various vendors.
NOTICE
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules when
wired using metal conduit for the cabling external to the enclosure. These limits are designed to provide reasonable protection against harmful
interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency
energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications.
Operation of this equipment in a residential area is likely to cause harmful interference that will require correcting at the users expense.
NOTICE
This document and the data in it shall not be duplicated, used or disclosed to others for procurement or manufacture, except as authorized
by and with the written permission of, Engineered Systems. The information contained in this document or in the product itself is considered
the exclusive property and trade secrets of Engineered Systems. Copyright laws of the United States protect all information in this docu-
ment or in the software product itself.
The information is this document is subject to change without notice.
TD1148rev0601
A division of Northern Computers, Inc.
CABLE SPECIFICATIONS
Application
NCI Part No.
AWG
Description
Max. Dist.
Imp.
Cap.
N-485 connections
NC2442-TN
N/A
Belden 9842
4000' (1200 m)
120W
12.8pf/ft
N/A
or equivalent
Readers/Keypads with
NC1861-BL
18
6 conductor shielded 500' (152 m)
Wiegand style INTERFACE
Alarm input points
NC 2221-BR
22
2000' (610 m)
Relay outputs
NC 1821-OR
18
twisted pair, shielded 2000' (610 m)
Note: For plenum rated cable just add a “P” to Engineered Systems' NC part number prefix; for example NC1861-BL becomes NCP1861-BL.
NCI CABLE PART NUMBERS
Part Number
Description
Application
Length
NC1841-GY
18 AWG/4 conductor
reader cable
1,000' (304.8m)
NC1861-BL-500
18 AWG/6 conductor
reader cable
500' (152m)
NC1861-BL
18 AWG/6 conductor
reader cable
1,000' (304.8m)
NC18121-YL-500
18 AWG/12 conductor
keypad cable
500' (152m)
NC18121-YL
18 AWG/12 conductor
keypad cable
1,000' (304.8m)
NCNET-1
50
Ω
network cable
1,000' (304.8m)
NC2221-BR
22 AWG/2 conductor
alarm cable
1,000' (304.8m)
NC1821-OR
18 AWG/2 conductor
power/door cable
1,000' (304.8m)
NCC59206-BK
RG-59 video
cable
1,000'
(304.8m)
NCP1841-GY
18 AWG/4 conductor Plenum
reader cable
1,000' (304.8m)
NCP1861-BL-500
18 AWG/6 conductor Plenum
reader cable
500' (152m)
NCP1861-BL
18AWG/6 conductor Plenum
reader cable
1,000' (304.8m)
NCP18121-YL
18 AWG/12 conductor Plenum
keypad cable
1,000' (304.8m)
NCP18121-YL-500
18 AWG/12 conductor Plenum
keypad cable
500' (152m)
NCPNET-1
50
Ω
Plenum network
cable
1,000'
(304.8m)
NCP2221-BR
22 AWG/2 conductor Plenum
alarm point cable
1,000' (304.8m)
NCP1821-OR
8 AWG/2 conductor Plenum
power/door cable
1,000' (304.8m)
NC2442-TN
24 AWG/120
Ω
12.8pf RS485 wire
communication cable
1,000' (304.8m)
NCP2442-TN
24 AWG/120
Ω
12.8pf Plenum
communication cable
1,000' (304.8m)
Small PRO-2200 Enclosure - PRO22ENC4
Installation Guide
4
SHAPING SECURITY THROUGH CREATIVE SOLUTIONS
5007 South Howell Ave • Milwaukee, WI 53207 USA • Tel: (414)769-5980 or (800)323-4576
A division of Northern Computers, Inc.