PLATINUM Series Controllers User’s Guide
65
Reference Section: Operating Mode (oPER)
8.9
Display Peak Reading (oPER > PEAk)
Select Display Peak Reading (PEAk) to change the process value displayed to the highest
reading since PEAk was last cleared.
Clear the PEAk reading buffer. Return to RUN Mode or to displaying “RUN” depending on the
Operating Safety parameter setting (
6.7.2 Operating Mode Confirmation (INIt > SFty > oPER)
).
Note:
Using the other buttons to navigate away from PEAk does not clear the PEAk reading
buffer.
8.10
Standby Mode (oPER > Stby)
Select Standby Mode (Stby) to disable outputs and Alarm conditions. Stby is displayed until
navigating elsewhere. Navigate to any desired initialization or programming settings to
change them or to adjust the process.
Return to RUN Mode or to displaying “RUN” depending on the Operating Safety parameter
setting (
6.7.2 Operating Mode Confirmation (INIt > SFty > oPER)
).
8.11
Standby Mode (oPER > tARE)
Select Standby Mode (tARE) to allow zeroing the current input value. Available only if enabled
in the INIt menu. The tARE will adjust the input offset to show zero.
Return to RUN Mode or to displaying “RUN” depending on the Operating Safety parameter
setting (
6.7.2 Operating Mode Confirmation (INIt > SFty > oPER)
).