CL
set closed loop update interval
IMM
PGM
MIP
USAGE
♦
♦
♦
SYNTAX
xxCLnn
or xxCL?
PARAMETERS
Description
xx
{ int ]
-
axis number
nn
[ int ]
-
closed loop update interval
Range
xx
-
0
to
MAX AXES
Units
xx
- none
nn
- milliseconds
Defaults
xx
missing:
error 37, AXIS NUMBER MISSING
nn
missing:
error 38, COMMAND PARAMETER MISSING
out
of
range:
error
7, PARAMETER OUT OF RANGE
DESCRIPTION
This command is used to set the closed loop update interval for an axis. This will
be the time duration between position error corrections during closed loop
stepper positioning. Note that this command is effective only for steeper motors.
If "0" is used as an axis number, this command will set the specified interval to
all the axes.
RETURNS
If "?" sign takes the place of
nn
value, this command reports the current setting.
REL. COMMANDS
ZB
-
set feedback configuration
EXAMPLE
3ZB300
|
enable encoder feedback and closed loop positioning of axis #3
3DB1
|
set position deadband value to 1 encoder count
3DB?
|
query deadband value
3CL100
|
set closed loop update interval to 100 milliseconds
3CL?
|
query closed loop update interval
100
|
controller returns a value of 100 milliseconds
nn
-
0
to
60000
out of range:
error 9, AXIS NUMBER OUT OF RANGE
Furthermore, note that encoder feedback and closed loop positioning must be
enabled for this command to be effective. Refer to feedback configuration (
ZB
)
command for enabling these features in the case of stepper motors.
DB
-
set position deadband value
1
|
controller returns a value of 1 encoder count
3-40
Section
3
–
Remote
Mode
Содержание ESP300 Series
Страница 1: ...ESP300 Motion Controller Driver User s Manual...
Страница 4: ...ESP300 1999 EU Declaration of Conformity iv Preface...
Страница 29: ...This page is intentionally left blank Section 2 Modes of Operation 1 15...
Страница 30: ......
Страница 230: ...4 16 Section 4 Advanced Capabilities...
Страница 274: ...This page is intentionally left blank 6 6 Section 6 Servo Tuning...
Страница 290: ...This page is intentionally left blank B 6 Appendix B Trouble Shooting and Maintenance...