5. Data Report
The device will immediately send a version packet report along with an uplink packet including vibration
status and battery voltage.
The device sends data in the default configuration before any configuration is done.
Default setting:
MaxTime: Max Interval = 60 min = 3600s
MinTime: Min Interval = 60 min = 3600s
BatteryChange: 0x01 (0.1V)
ActiveThreshold: 0x0003 (Threshold range: 0x0003-0x00FF, 0x03 is the most sensitive)
Deactivetime: 0x05 (Deactive time Range: 0x01-0xFF)
ActiveThreshold:
Active Threshold = Critical value ÷ 9.8 ÷ 0.0625
*The gravitational acceleration at standard atmospheric pressure is 9.8 m/s
2
*The scale factor of the threshold is 62.5 mg
R311FA vibration alarm:
The device detects a sudden movement or vibration, change of the quiescent state, and it will
immediately send a report. After the vibration alarm, the device waits for DeactiveTime to enter the
quiescent state before starting the next detection. If the vibration continues to occur during this process,
the timing restarts until it enters the quiescent state.
R311FX Series DeviceType:
R311FA 0x01; R311FB 0x02; R311FC 0x03
Note:
The device report interval will be programmed based on the default firmware which may vary.
The interval between two reports must be the minimum time.
Please refer Netvox
LoRaWAN Application Command document
and
Netvox Lora Command Resolver
http://www.netvox.com.cn:8888/page/index