![NetApp 42U 1280 mm System Cabinet Скачать руководство пользователя страница 6](http://html.mh-extra.com/html/netapp/42u-1280-mm-system-cabinet/42u-1280-mm-system-cabinet_manual_1669923006.webp)
Required tools and equipment
Before unpacking and installing on your system cabinet, you should gather the necessary tools and
equipment to move the system cabinet into place and install it or to perform maintenance on it.
•
The appropriate hardware guide for your disk shelves
•
The appropriate installation and setup instructions for your system
NetApp All Flash FAS Resources
NetApp FAS Storage Systems Resources
NetApp E-Series Systems Documentation Center
•
#1 and #2 Phillips screwdrivers
•
Torx driver for system cabinet screws
•
Leveling tool for leveling the system cabinet
Space requirements and system cabinet dimensions
When unpacking your system cabinet, you must make sure that you have enough room to remove the
system cabinet from the packing material. Also make sure that the intended location for the system
cabinet is large enough for you to move the cabinet into place.
Required space for unpacking the system cabinet
The following table defines the requires space needed to unpack and install your system cabinet:
Dimensions
U.S.
Metric
Shipping ramp length
80 in.
203.2 cm
Clearance beyond the ramp for
cabinet mobility
72 in.
182.9 cm
Shipping pallet depth
59 in.
149.9 cm
Shipping pallet width
42 in.
106.6 cm
Shipping pallet and packaging
height
86 in.
218.4 cm
Total rack space, 42U
73.5 in.
186.7 cm
Rail load capacity
Supports all current systems
Supports all current systems
Empty weight
~400 lbs (~181 kg) lbs
~ 181 kg
Fully loaded ship weight
Up to 1,800 lbs
Up to 816.5 kg
Fully loaded static weight
Up to 2,700 lbs
Up to 1,224.7 kg
Front service clearance
47.2 in.
120 cm
Rear service clearance
Note:
The rear door is split.
Actual minimum rear
clearance is approximately
1/2 the recommendation.
30 in.
76.3 cm
6 | 42U 1280 mm System Cabinet Guide