Neptronic TRO5404 Скачать руководство пользователя страница 1

Room controller Thermostat

 

Specification & Installation instructions

 

 

TRO5404-121108-ESA.docx

 

         

1

 

 

Technical Data 

TRO5404 

Outputs 

2 Analog Cooling outputs (0-10VDC) 
2 Analog Heating outputs (0-10VDC) 

0 or 22 VDC, TPM, (Time proportional modulation) 250 mA max. 

Power supply 

22 to 26 VAC 50/60Hz  

Power consumption 

2 VA 

Set point range 

10ºC to +35ºC [50ºF to 95ºF] 

Control accuracy 

Temperature: +/-0.2ºC [0.4ºF] 

Proportional band 

0.5 ºC to 4ºC [1 ºC to 8ºF] adjustable 

Electrical connection 

0.8 mm

[18 AWG] minimum 

Operating temperature 

0ºC to +50ºC [32ºF to +122ºF] 

Storage temperature 

-30ºC to +50ºC [-22ºF to +122ºF] 

Relative Humidity 

5 to 95 % non condensing 

Degree of protection of housing 

IP 30 to EN 60529 

Weight 

85 g. [0.2 lb] 

 

Presentation

 

 

Symbols on display 

Cooling ON 
A: Automatic 

Menu set-up Lock ON 

Heating ON 
A: Automatic 

 

Programming mode 

 

Energy saving mode ON 

Minimum/Maximum 
set points  

 or 

ºC: Celsius scale 
ºF: Fahrenheit scale 

 

 

  

 

Dimensions 

Dimension

Inches Metric 

(mm)

A

3.00 78 

B

3.00 78 

C

1.00 24 

D

2.36 60 

 

 

A

B

C

D

 

Feature: 

 Selectable 

analog 

output 

 

Selectable Fahrenheit or Celsius scale 

 

Manual Night Set Back override 

 

Multi level lockable access menu 

 

Lockable Set point 

 

Selectable internal or external temperature sensor 

  Selectable external temperature sensor type 

(3.3 K

 or 10 K

 | Type 3 or Type G) 

 Selectable 

proportional 

control 

band 

TRO5404 

 
 
 
 

 
 
 
 
 

Отзывы: