Room controller Thermostat
Specification & Installation instructions
TRO5404-121108-ESA.docx
1
Technical Data
TRO5404
Outputs
2 Analog Cooling outputs (0-10VDC)
2 Analog Heating outputs (0-10VDC)
0 or 22 VDC, TPM, (Time proportional modulation) 250 mA max.
Power supply
22 to 26 VAC 50/60Hz
Power consumption
2 VA
Set point range
10ºC to +35ºC [50ºF to 95ºF]
Control accuracy
Temperature: +/-0.2ºC [0.4ºF]
Proportional band
0.5 ºC to 4ºC [1 ºC to 8ºF] adjustable
Electrical connection
0.8 mm
2
[18 AWG] minimum
Operating temperature
0ºC to +50ºC [32ºF to +122ºF]
Storage temperature
-30ºC to +50ºC [-22ºF to +122ºF]
Relative Humidity
5 to 95 % non condensing
Degree of protection of housing
IP 30 to EN 60529
Weight
85 g. [0.2 lb]
Presentation
Symbols on display
Cooling ON
A: Automatic
Menu set-up Lock ON
Heating ON
A: Automatic
Programming mode
Energy saving mode ON
Minimum/Maximum
set points
or
ºC: Celsius scale
ºF: Fahrenheit scale
Dimensions
Dimension
Inches Metric
(mm)
A
3.00 78
B
3.00 78
C
1.00 24
D
2.36 60
A
B
C
D
Feature:
Selectable
analog
output
Selectable Fahrenheit or Celsius scale
Manual Night Set Back override
Multi level lockable access menu
Lockable Set point
Selectable internal or external temperature sensor
Selectable external temperature sensor type
(3.3 K
Ω
or 10 K
Ω
| Type 3 or Type G)
Selectable
proportional
control
band
TRO5404