background image

 

EVC Thermostat

 

Specification & Installation Instructions

 

 

TRL5x-121025-ESA.doc

 

         

1

 

EVC Thermostat

 

 

Technical Data 

TRL54 TRL55 

Electrical connection 

3 wire cable 

RJ45 cable 

Setpoint range 

10ºC to 40ºC [50ºF to 104ºF] 

External sensor range 

-40ºC to 100ºC [-40ºF to 212ºF] 

Control accuracy 

Temperature: ±0.4ºC [0.8ºF] 

Power supply 

22 to 26 Vac 50/60Hz 

Power consumption 

1 VA 

Rated impulse 

330 V 

Proportional band 

0.5ºC to 5ºC [1ºF to 10ºF] adjustable (heat/cool/changeover independent) 

Dead band 

0.3ºC to 5ºC [0.6ºF to 10ºF] adjustable (heat/cool/changeover independent) 

Operating temperature 

0ºC to 50ºC [32ºF to 122ºF] 

Storage & transport temperature 

-30ºC to 50ºC [-22ºF to 122ºF] 

Relative Humidity 

5 to 95% non condensing 

Degree of protection of housing 

IP 30 (EN 60529) 

Weight 

160 g. [0.36 lb] 

Dimensions 

A = 3.00 in (78mm) 
B = 3.00 in (78mm) 

C = 1.00 in (24mm) 
D = 2.36 in (60mm)

 

A

B

C

D

 

 

Interface

 

 

Display Symbols 

 

Cooling ON 
A: Automatic 

Menu set-up lock 

 

Energy saving mode 

 

Heating ON 
A: Automatic 

Programming mode 
(Technician setting) 

C

or 

F

 

ºC: Celsius scale 
ºF: Fahrenheit scale 

 

Alarm status 

Minimum/Maximum 
set points  

  

 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

The TRL5x functions only with the EVC controllers. All inputs/outputs are located 
on the controller except for the temperature sensor built-in the TRL5x. 

Features: 

 

Used to program/configure the EVC VAV controller 

 

Attractive modern look with large LCD and backlight 

 

Icons driven information  

 

3 wire or RJ45 Ethernet cable between thermostat & EVC 

 

Selectable analog and digital output 

 

Precise temperature control with programmable PI function 

 

Selectable Fahrenheit or Celsius scale 

 

Manual night set back or no occupancy override 

 

Multi level lockable access menu 

 Lockable 

setpoint 

 

Selectable internal or external temperature sensor (10 K

 

Change over by contact or external temperature sensor 

 

Pressure sensor air flow program available 

 

Selectable proportional control band and dead band 

 Anti-freeze 

protection 

 BACnet

®

 MS/TP @ 9600, 19200, 38400, 76800bps available 

 

Selectable MAC address by dip switch on the EVCB 

TRL54 
TRL55

 

 
 
 
 
 
 
 
 

 