Actuator
Specification & Installation Instructions
TM1N-RM1N_211213
1
Technical Data
TM100N
TM120N
TM160N
RM100N
RM120N
RM160N
RM180N
Auxiliary switches
No
Yes (2)
No
No
Yes (2)
No
Yes (2)
Fail safe - Enerdrive
No
Yes
No
Yes
Power consumption
20 VA
45 VA Peak, 20
VA
30 VA
50 VA Peak, 30 VA
Torque
180 in.lb. [20 Nm] at rated voltage
360 in.lb. [40 Nm] at rated voltage
Running time
through 90º
40 to 50 sec torque dependant
Power supply
28 to 32 Vdc or 22 to 26 Vac, 110 to 130 Vac 50/60Hz
Feedback
4 to 20 mA or 2 to 10 Vdc adjustable
Electrical
connection
18 AWG [0.8 mm
2
] minimum
Inlet bushing
2 inlet bushing of 7/8 in [22.2 mm]
Control signal
Analog, Digital or PWM programmable (factory set with analog control signal)
Angle of rotation
0 to 90 degrees, electronically adjustable (factory set with 90º stroke)
Direction of rotation
Reversible, Clockwise (CW) or Counterclockwise (CCW) (factory set with CW direction)
Operating
temperature
0ºF to 122ºF [-18ºC to 50ºC]
Storage temperature
-22ºF to 122ºF [-30ºC to 50ºC]
Relative Humidity
5 to 95 % non condensing.
Weight
5 lbs. [2.3 kg]
8 lbs. [3.5 kg]
Warning: Do not press the clutch when actuator is powered
Dimensions
Dimension
Imperial (in)
Metric (mm)
A
5.20
132.1
B
1.33
33.8
C
9.13
231.9
D
3.55
90.2
Caution
We strongly recommend that all Neptronic
®
products be wired to a separate transformer and that transformer shall service only Neptronic
®
products. This precaution will
prevent interference with, and/or possible damage to incompatible equipment.
When multiple actuators are wired on a single transformer, polarity must be observed. Long wiring runs create voltage drop which may affect the actuator performance.
1
Enerdrive System
U.S.A. Patent #5,278,454
Features:
•
Clutch for manual adjustments.
•
Maintenance free.
•
Position indicator.
•
Control signal fully programmable.
•
Brushless DC driven motor.
•
Fail safe by
EnerdriveSystem
1
(on model 160 & 180).
•
Auxiliary switches
(on model 120 & 180).
TM100N
TM120N
TM160N
RM100N
RM120N
RM160N
RM180N