background image

 

LT-X11/060303

 

     

     

    

 1 

Actuator for smoke damper 

Specification 

& Installation instruction

 

Technical Data 

LT060X11 LT080X11 LT160X11 LT180X11 LT260X11 LT280X11 

Auxiliary switches 

No Yes No Yes No Yes 

Power supply 

22 to 26VAC 50/60Hz or 22 to 26VDC 

110 to 130 VAC 50/60Hz 

220 to 240 VAC 50/ 60Hz 

Weight 

4.5 lbs. [2 kg] 

4.8 lbs. [2.2 kg] 

Fail safe - Enerdrive 

Yes 

Power consumption 

Running 24VA, Holding 5VA 

Control signal 

2 wire / 2 position 

Running time through 90º 

20 to 30 sec Torque dependant  

Fail safe: 15 sec. max at rated torque. 

Torque 

90 in.lb. [11 Nm] at rated voltage  

Electrical connection 

18 AWG [0.8 mm

2

] minimum  

Inlet bushing 

2 inlet bushing of 7/8 in [22.2 mm] 

Angle of rotation 

0 to 90 degrees, mechanically adjustable with SLD (optional), (factory set with 90º stroke) 

Direction of rotation 

Reversible, Clockwise (CW) or Counterclockwise (CCW) (factory set with CW direction) 

Ambient temperature 

Operation 

0ºF to +122ºF [-18º C to +50º C] 

3 cycles at +250˚F [+121º C] 

Storage temperature 

-22ºF to +122ºF [-30º C to +50º C] 

Relative Humidity 

5 to 95 % non condensing. 

Enclosure type 

NEMA type 2 / IP42 

Warning: Do not press the clutch when actuator is powered 
Warning for LT160/180/260/280X11: High Voltage. Risk of electric chock. 

 

Dimensions

 

 

 
 

Dimension Inches Metric 

(mm) 

5.20 132.1 

1.33 33.8 

9.13 231.9 

3.52 89.4 

 

 

Caution 

We strongly recommend that all neptronic® products be wired to a separate transformer and that transformer shall service only neptronic® products. This precaution will 
prevent interference with, and/or possible damage to incompatible equipment. 
When multiple actuators are wired on a single transformer, polarity must be observed. Long wiring runs create voltage drop which may affect the actuator performance. 

                                                 

1

 

Enerdrive System

 U.S.A. Patent #5,278,454 

LT060X11 
LT080X11 
LT160X11 
LT180X11 
LT260X11 
LT280X11 

 

 

Feature: 

  Designed to operate reliably in smoke control systems requiring 

Underwriter’s Laboratories UL555S (rated at 250˚F). 

  Mounts easy on round shaft. 

 Maintenance 

free. 

 Position 

indicator. 

  Fail safe by 

Enerdrive System

1

 

 

Отзывы: