LT-X11/060303
1
Actuator for smoke damper
Specification
& Installation instruction
Technical Data
LT060X11 LT080X11 LT160X11 LT180X11 LT260X11 LT280X11
Auxiliary switches
No Yes No Yes No Yes
Power supply
22 to 26VAC 50/60Hz or 22 to 26VDC
110 to 130 VAC 50/60Hz
220 to 240 VAC 50/ 60Hz
Weight
4.5 lbs. [2 kg]
4.8 lbs. [2.2 kg]
Fail safe - Enerdrive
Yes
Power consumption
Running 24VA, Holding 5VA
Control signal
2 wire / 2 position
Running time through 90º
20 to 30 sec Torque dependant
Fail safe: 15 sec. max at rated torque.
Torque
90 in.lb. [11 Nm] at rated voltage
Electrical connection
18 AWG [0.8 mm
2
] minimum
Inlet bushing
2 inlet bushing of 7/8 in [22.2 mm]
Angle of rotation
0 to 90 degrees, mechanically adjustable with SLD (optional), (factory set with 90º stroke)
Direction of rotation
Reversible, Clockwise (CW) or Counterclockwise (CCW) (factory set with CW direction)
Ambient temperature
Operation
0ºF to +122ºF [-18º C to +50º C]
3 cycles at +250˚F [+121º C]
Storage temperature
-22ºF to +122ºF [-30º C to +50º C]
Relative Humidity
5 to 95 % non condensing.
Enclosure type
NEMA type 2 / IP42
Warning: Do not press the clutch when actuator is powered
Warning for LT160/180/260/280X11: High Voltage. Risk of electric chock.
Dimensions
Dimension Inches Metric
(mm)
A
5.20 132.1
B
1.33 33.8
C
9.13 231.9
D
3.52 89.4
Caution
We strongly recommend that all neptronic® products be wired to a separate transformer and that transformer shall service only neptronic® products. This precaution will
prevent interference with, and/or possible damage to incompatible equipment.
When multiple actuators are wired on a single transformer, polarity must be observed. Long wiring runs create voltage drop which may affect the actuator performance.
1
Enerdrive System
U.S.A. Patent #5,278,454
LT060X11
LT080X11
LT160X11
LT180X11
LT260X11
LT280X11
Feature:
•
Designed to operate reliably in smoke control systems requiring
Underwriter’s Laboratories UL555S (rated at 250˚F).
•
Mounts easy on round shaft.
•
Maintenance
free.
•
Position
indicator.
•
Fail safe by
Enerdrive System
1