background image

 

BT-X4/060303

 

     

     

    

 1 

Actuator for smoke damper 

Specification 

& Installation instruction

 

 

Technical Data 

BT060X4 BT160X4 BT260X4 BT080X4 BT180X4 BT280X4 

Power supply 

22 to 26VAC 

50/60Hz or 24VDC 

110 to 130 VAC 

50/60Hz 

220 to 250 VAC 

50/60Hz 

22 to 26VAC 

50/60Hz or 24VDC 

110 to 130 VAC 

50/60Hz 

220 to 250 VAC 

50/60Hz 

Auxiliary switches  

No 

2 switches rated 250VAC, 5A 

switching points: 5˚ & 85˚ +/-5˚ 

Torque 

35 in.lb. [4 Nm] at rated voltage 

Fail safe - Enerdrive 

Yes 

Power consumption 

Running 15VA, Holding 5VA 

Control signal 

2 wire / 2 position 

Running time through 90º 

20 to 30 sec Torque dependant  

Fail safe: 15 sec. max at rated torque. 

Electrical connection 

18 AWG [0.8mm

2

] minimum 

Inlet bushing 

2 inlet bushing of 5/8 in [15.9 mm] & 7/8 in [22.2 mm] 

Angle of rotation 

0 to 90 degrees, mechanically adjustable (factory set with 90º stroke) 

Direction of rotation 

Reversible, Clockwise (CW) or Counterclockwise (CCW) (factory set with CW direction) 

Ambient temperature 

Operation 

0ºF to +122ºF [-18º C to +50º C] 

3 cycles at +250˚F [+121º C] 

Storage temperature 

-22ºF to +122ºF [-30º C to +50º C] 

Relative Humidity 

5 to 95 % non condensing. 

Enclosure type 

NEMA type 2 / IP42 

Weight 

3 lbs. [1.4 kg] 

Warning: Do not press the clutch when actuator is powered 
Warning for BT160/260/180/280X4: High Voltage. Risk of electric chock. 

 

Dimensions

 

A

B

C

D

 

 
 

Dimension Inches 

Metric 

(mm) 

1.50 38.1 

3.26 82.8 

6.60 167.5 

D

 

3.01 76.4 

 

 

Caution 

We strongly recommend that all neptronic® products be wired to a separate transformer and that transformer shall service only neptronic® products. This precaution will 
prevent interference with, and/or possible damage to incompatible equipment. 
When multiple actuators are wired on a single transformer, polarity must be observed. Long wiring runs create voltage drop which may affect the actuator performance. 

                                                 

1

 

Enerdrive System

 U.S.A. Patent #5,278,454 

BT060X4 
BT160X4 
BT260X4 
BT080X4 
BT180X4 
BT280X4 

 

 

Feature: 

  Designed to operate reliably in smoke control systems requiring 

Underwriter’s Laboratories UL555S (rated at 250˚F). 

  Mounts easy on round & square shaft (optional). 

  External clutch for manual adjustments. 

 Maintenance 

free. 

 Position 

indicator. 

  Fail safe by 

Enerdrive System

1

 

  2 auxiliary switches (only on models 080, 180 & 280) 

 