Actuator
Specification & Installation instructions
BT/070628
1
BT000 BT005 BT020 BT060 BT065 BT080
Technical Data
BBT1000A BBT1005A BBT1021A BBT1060A BBT1065A BBT1080A
Auxiliary switches
No
No Yes
(2) No
No Yes
(2)
Feedback
No Yes No No Yes No
Fail safe - Enerdrive
No Yes
Power consumption
6 VA
15VA Peak, 6VA
Control signal
3 wire / 2 position, 3 wire / 3 point floating
2 wire / 2 position, 4 wire / 3 point floating
Running time through
90º
20 to 30 sec Torque dependant
Torque
50 in.lb. [5,6 Nm] at rated voltage
Power supply
22 to 26 VAC or 28 to 32 VDC
Electrical connection
18 AWG [0.8 mm
2
] minimum
Inlet bushing
2 inlet bushing of 5/8 in [15.9 mm] & 7/8 in [22.2 mm]
Angle of rotation
0 to 90 degrees, mechanically adjustable (factory set with 90º stroke)
Direction of rotation
Reversible, Clockwise (CW) or Counterclockwise (CCW) (factory set with CW direction)
Ambient temperature
-22ºF to +122ºF [-30ºC to +50ºC]
Storage temperature
-22ºF to +122ºF [-30ºC to +50ºC]
Relative Humidity
5 to 95 % non condensing.
Weight
3 lbs. [1.4 kg]
Ingress protection
IP22 equivalent to Nema type 2,
IP54 equivalent to Nema type 3R if water tight inlet bushings (not supplied NEP617) are installed
Warning: Do not press the clutch when actuator is powered
Dimensions
A
B
C
D
Dimension Inches Metric
(mm)
A
1.50 38.1
B
3.26 82.8
C
6.60 167.5
D
3.01 76.4
Caution
We strongly recommend that all neptronic® products be wired to a separate transformer and that transformer shall service only neptronic® products. This precaution will
prevent interference with, and/or possible damage to incompatible equipment.
When multiple actuators are wired on a single transformer, polarity must be observed. Long wiring runs create voltage drop which may affect the actuator performance.
1
Enerdrive System
U.S.A. Patent #5,278,454
Old Number
BBT1000A BT000
BBT1005A BT005
BBT1021A BT020
BBT1060A BT060
BBT1065A BT065
BBT1080A BT080
Feature:
•
Mounts easy on round
& square shaft (with option –8).
•
External clutch for manual adjustments.
•
Maintenance
free.
•
Position
indicator.
•
Fail safe by
Enerdrive System
1
(on model 060, 065 & 080).
•
Auxiliary switches
(on model 020 & 080).