NeoTech AAD-10 Скачать руководство пользователя страница 1

Models • Modelli  

AAD-10 • AAR-10S • AAT-10

 

ENGLISH 

This instruction sheet provides you with the information required to safely own 
and operate your product. Retain these instructions for future reference. 
The  product  you  have  purchased  is  of  the  highest  quality  workmanship  and  
material, and has been engineered to give you long and reliable service. This 
product  has  been  carefully  tested,  inspected,  and  packaged  to  ensure  safe 
delivery and operation. Please examine your item(s) carefully to ensure that no 
damage occurred during shipment. If damage has occurred, please contact the 
place of purchase. They will assist you in replacement or repair, if required. 

READ  THESE  INSTRUCTIONS  CAREFULL  Y  BEFORE  ATTEMPTING  TO 
INSTALL  ,  OPERATE,  OR  SERVICE  YOUR  PROD  UCT.  KNOW  THE    
PROD UCT’S APPLICATION, LIMITATIONS, AND POTENTIAL HAZARDS. 
PROTECT  YOURSEL  F  AND  OTHERS  BY  OBSERVING  ALL  SAFETY  IN-
FORMATION.  FAILURE  TO  COMPLY  WITH  THESE  INSTRUCTIONS 
COULD RESULT IN PERSONAL INJURY AND/OR PROPERTY DAMAGE! 
 

DECLARATION OF CONFORMITY 

We, Steelpumps, declare that our pumps AAD, AAR & AAT with pump type and 
serial  number  as  shown  on  the  nameplate  are  constructed  in  accordante  with 
Directives  2006/95/EC  and  89/336/EEC  and  assume  full  responsibility  for    
conformity with the standards laid down therein. 
 

DESCRIPTION 

Your  Steelpumps  peristaltic  condensate  pump  is  designed  as  a  fully  automatic 
condensate  removal  system  for  the  water  dripping  off  an  air  conditioner     
evaporator coil. The pump is not for contiuous use applications. The pump you 
have  purchased  is  a  small  but  powerful  drain  pump  for  the  positive  displace-
ment of condensate from fan coils and air conditioners. The design of this pump 
allows  the  air  handler  to  be  located  away  from  gravity  water  drains  since  the 
condensate can be pumped to a common drain a distance away. The peristaltic 
pump is designed to remove condensation from fan coil, wall-mount, ceiling and 
cassette air conditioning equipment. 
 

SAFETY GUIDELINES 

 
 

SHUT  OFF  ELE  CTRICAL  POWER  AT  FUSE  BOX  BEFORE    ATTEMPTING 
TO SERVICE, DISCONNECT, CONNECT OR REMOVE ANY COMPONENT! 

1.  This pump is not to be used to pump flammable or explosive fluids such as 

gasoline,  fuel  oil,  kerosene,  etc.  Do  not  use  this  pump  in  explosive      
atmospheres. 

2.  Do  not  handle  pump  with  wet  hands  or  when  standing  on  a  wet,  damp 

surface or when standing in water. 

3.  In  any  installation  where  property  damage  and/or  personal  injury  might 

result  from  an  inoperative  or  leaking  pump  due  to  power  outages,       
discharge  line  blockage,  or  any  other  reason,  a  backup  system(s)  and/or 
alarm should be used. 

4.  Support  pump  and  piping  when  assembling  and  when  installed.  Failure  to 

do so may cause piping to break, pump to fail, motor bearing failures, etc; 
or may cause the pump to malfunction. 

5.  Place pump in an area where there is no danger of ingress of water. 
 

SPECIFICATIONS 

Maximum suction head: 2m (6.5 ft) 
Maximum delivery head: 14m (49 ft) 
Maximum ambient temperature: 50°C (122°) 
 

PRE-INSTALL ATION 

1.  Check  the  pump  label  for  proper  voltage  and  frequency  required.  Do  not    

connect to voltage and frequency other than that shown. 

2.  It  is  recommended  to  use  ¼”  I.D.  or  6  mm  I.D.  tubing  for  both  the  inlet 

and  outlet.  Inlet  tubing  is  connected  to  the  inlet  fitting  identified  by  an 
upward  arrow. Outlet or  discharge  tubing  is connected to the outlet  fitting 
identified by a downward arrow. 

3.  Make sure the transparent cover is closed before operating. 
 

INSTALLATION 

Pump Mounting Installation: 

The  pump  can  be  mounted  adjacent,  below  or  above  (but  not  more  than  2m 
above) the condensate water source. 
For  best  results,  mount  the  pump  with  the  hose  connections  facing  down  as 
shown in Figure 1B 

The pump may also be positioned on any side, but not placed rotor downward 
(Figure  1C)  or  upward  (Figure  1A).  Connect  6.0mm  or  1/4”  tubing  (not      
provided)  to  the  pump  intake  indicated  by  the  arrow  pointing  upward  on  the 
transparent  cover.  Position  the  other  end  of  the  intake  tube  in  the  drip  tray 
drain  hose  and  seal  it  accordingly  or  place  the  intake  tube  in  the  drip  tray 
(Figure 2). Be careful not to twist, kink, or collapse the tubing. Run a length of 
6.0mm or ¼” tubing (not provided) from the discharge of the pump to a gravity 
drain.  Refer  to  Figure  2  for  maximum  vertical  and  horizontal  discharge       
capabilities. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

FIGURE 2 

CAUTION: 

Be certain that there are no sharp bends or kinks in the suction and 

discharge  tubing.  Keep  all  tubing  and  cables  clear  of  moving  parts  in  the  air 
handler.  If  using  Ty-raps  to  secure  tubing,  be  certain  the  Ty-rap  does  not  
collapse tubing. 

Collection Reservoir Installation (R Series only): 

Locate  the  float  reservoir  in  a  suitable  position  below  the  bottom  level  of  the 
drip  tray  of  the  air  conditioner.  Be  certain  that  the  reservoir  is  within  (+/-)  15 
degrees of being level. Optimum performance is achieved when the reservoir is 
level.  If  the  reservoir  is  not  mounted  properly,  the  float  mechanism  may  not 
function properly and may overflow. 
Attach the 13mm (1/2”) tube (provided) to the reservoir intake and the drip tray 
outlet or drain  hose. Be certain to support the reservoir when  attaching  tubing 
and make sure the tubing is not twisted, kinked or collapsed when reservoir is in 
place. Connect the long 4 x 6 mm (5/32”) tubing (provided)to the discharge of 
the  reservoir  marked  “PUMP”.  Connect  the  other  end  of  the  4  x  6  mm  (5/32”) 
tubing  to  the  provided  4  x  6  mm  adapter.  Use  a  short  piece  of  6  mm  or  ¼” 
tubing (not provided) to connect the 4 x 6 mm adapter to the pump inlet fitting 
identified  by  an  upward  arrow.  Connect  the  short  4  x  6  mm  (5/32”)  tubing 
(provided)  to  the  outlet  of  the  reservoir  marked  “VENT”.  The  free  end  of  the 
tubing  must  be  directed  upward  above  the  drip  tray  to  prevent  overflow.  Be 
certain the tubing is not twisted, kinked or collapsed when installed. 

 

ELE CTRICAL CONNECTIONS 

 
 

SHUT  OFF  ELECTRICAL  POWER  AT  FUSE  BOX  BEFORE  MAKING  ANY         
CONNECTIONS. ALL WIRING MUST COMPLY WITH LOCAL CODES. CHECK THE 
PUMP  LABEL  FOR  PROPER  VOLTAGE  REQUIRED.  DO  NOT  CONNECT  TO    
VOLTAGE OTHER THAN THAT SHOWN. 
 

AAD  Series 

(compressor  or  cooling  signal)  -  Connect  the  brown  wire  to  the 

main  phase  (line),  the  blue  wire  to  the  neutral  phase  (common).  The  pump 
must not be connected to a switched line. Electricity should always be provided 
on this line. Connect the orange wire to the compressor or cooling signal (Figure 
3).  When  the  compressor  engages,  a  230V  supply  voltage  will  be  sent  to  start 
the  pump.  When  the  compressor  stops  operating,  the  pump  will  not  stop.  The 
pump is programmed to continue operating for another 5 minutes to collect any 
residual condensate before stopping. 

Note

:  The  compressor  or  cooling  signal  neutral  phase  (common)  needs  to  be 

the  same  neutral  phase  (common)  that  is  used  to  supply  power  to  the 
controller. 

AAT  Series 

(temperature  signal)  FOR  PROPER  PUMP  OPERATION,  PLEASE 

FOLLOW  THESE  INSTRUCTIONS:  Connect  the  brown  wire  to  the  main  phase 
(line)  and  the  blue  wire  to  the  neutral  phase  (common)  (Figure  2).  Make  sure 
power is off when connecting the temperature sensor to the pump. Connect the 
sensor cable to the pump by connecting the 4-prong plug to the corresponding 

FIGURE 1 

Отзывы: