Neosens Skidsens Скачать руководство пользователя страница 1

Manual

SKIDSENS

Fouling Sensor

by Neosens

Quick User Manual

Installation Guide

Advantage Controls

P.O. Box 472

Muskogee, OK  74402

Phone: 800-743-743

Fax: 888-686-622

www.advantagecontrols.com

email: [email protected]

3/20

Содержание Skidsens

Страница 1: ... Fouling Sensor by Neosens Quick User Manual Installation Guide Advantage Controls P O Box 1472 Muskogee OK 74402 Phone 800 743 7431 Fax 888 686 6212 www advantagecontrols com email support advantagecontrols com 3 2011 ...

Страница 2: ...ng Monitoring 0 1 mm 0 to 0 039 in Accuracy 1 of Full scale Material PVC body 316L SS sensor tip Connection Sensors are supplied with a 1 2 54 cm slip and a 1 MNPT PVC quick release adaptor The PVC adaptor has a maximum temperature rating of 125o F Peak sensor body has 1 2 straight BMPT Shipping Weight 4 lbs 1 814 kg Sensor Length 9 375 23 8 cm Insertion Depth Approx 3 375 8 57 cm ...

Страница 3: ...ensor If the sensor is giving a 3mA output after being installed for at least 2 hours in the minimum flow rate of 3 5 gpm the following steps can be followed to test and reset the sensor s operation 1 Power OFF the Skidsens 2 Assuming the Skidsens was maintained in water with the required flow rate 3 5gpm power ON the Skidsens and check the analog output reading during the first 20 seconds as the ...

Страница 4: ...put 1 4 20mA Input 1 4 20mA Input 2 4 20mA Input 2 4 20mA Input 3 4 20mA Input 3 4 20mA Input 4 4 20mA Input 4 4 20mA Input 5 4 20mA Input 5 4 20mA Input 6 4 20mA Input 6 LED 4 20mA Input Card Note The number of channels or 4 20mA inputs depends on on the number ordered 4 20mA Input 7 4 20mA Input 7 4 20mA Input 8 4 20mA Input 8 Wiring Diagram for MegaTron Connection ...

Страница 5: ...t RED BLUE WHITE BROWN GREEN GND GREEN GND 36 VDC Signal BLACK HOT WHITE NEU SKIDSENS Probe Power Cord Input 1 Input 1 Input 2 Input 2 MegaTron SS 4 20mA Input Rev D Part SS MAI 2 Input 3 Input 3 Wiring Diagram for MegaTron SS Connection ...

Страница 6: ...to the previous screen CUSTOMIZE mA INPUT 1 NAME FOULING UNITS mm NUMBER x xxx Step 6 From here push the UNITS Button 2 to go to the next screen CUSTOMIZE mA INPUT 1 NAME FOULING UNITS mm NUMBER x xxx Step 7 This is the Customize mA Units screen From here select the type of units i e mm by using the Arrow buttons Then press ENTER to confirm and return to the previous screen CUSTOMIZE mA INPUT 1 NA...

Страница 7: ...his is the mA Input Calibration Screen From here choose the MAX or MIN Button 3 and 4 to go to the next screen mA INPUT CALIBRATION 20 mA 19649 4 mA 3913 MAX 1 000 mm MIN 0 000 mm OFFSET Enabled Step 5 This is the mA Input MAX screen From here adjust the MAX reading by using the number keys MAX should be set to 1 000 mm and MIN should be set to 0 000 mm Then press ENTER to confirm and return to th...

Страница 8: ...all of your water treatment equipment needs Cooling Tower Controllers Boiler Blow Down Controllers Blow Down Valve Packages Solenoid Valves Water Meters Chemical Metering Pumps Corrosion Coupon Racks Chemical Solution Tanks Solid Feed Systems Feed Timers Filter Equipment Glycol Feed Systems Pre Fabricated Systems Get the Advantage ...