WIRING 0-10V
2AMDI511IPVRDS
- FIGURE N. 3
In order to activate this mode of control/operation just connect the active control signal of 0-10V/1-10V between
the D+ and D- inputs (being careful to observe the correct polarity) and disconnect the remaining control signals.
The maximum current absorbed by 0-10V dimmer interface is 0,1 mA.
By default, the dimming curve follows a logarithmic trend proportional to the control voltage. A voltage value of less
than 1V is interpreted as load off.
In case the 0-10V/1-10V signal is disconnected, the dimmer sets the output to the saved level (see preset level
change). The preset value is zero by default.
On the first run in this mode it could be necessary to set the input to a value greater than 50% (5V or higher on DD
+ input) in order to configure the dimmer to the 0-10V/1-10V mode.
*This setting can be configured through the interface cod. 2AMIN4030000N
MODE 0-10V/1-10V PASSIVE