Installation
Preparation
Install the camera display and check proper working.
Install the adapter:
1.
The tank valve is closed.
2.
Remove the pipe stopper.
3.
Install the adapter, air purging tube at the bottom.
4.
The air purging tube valve is closed.
Pre-insert the antenna:
1.
Insert the antenna tip about 5 cm (2 inches) into the valve
adapter.
2.
Hand-tighten the central fitting nut.
3.
Feed the device and activate the Camera mode.
Air purging
To purge the air:
1.
Guided by the camera and display, push the purge pipe to
reach the highest spot in the transformer valve.
2.
Slightly open the purging tube valve.
3.
Slowly open pipe valve. Close the purge tube valve when air is
purged (oil will start dripping).
4.
If more air pockets are spotted thanks to the camera, reopen
the air purge valve and slowly pull the tube to catch and
evacuate them.
5.
Close the purge tube valve when done.
Insertion
To insert the antenna the tank:
1.
Completely open the transformer pipe valve.
2.
Guided by the camera and display, carefully push the antenna
through the valve, driving around obstacles using the
articulated tip handle.
3.
Once the antenna tip has reached the transformer tank, screw
the antenna grounding sleeve to the adapter.
4.
Switch to Antenna mode before taking measurements.