22 Troubleshooting
5.2 Understanding Error Codes
When an error code appears on the front panel, refer to the following chart for a definition and possible remedy for the situation.
Error Code
Reason
Self-diagnostic / Action
E003
Ignition failure
Ensure that the main gas supply valve is open.
E004
False flame detection
Ensure that the electrical cord is properly grounded.
E012
Flame loss
●
Clean the intake air filter.
●
Ensure that the electrical cord is properly grounded.
E016
Overheating of heat exchanger
●
Turn off the system for at least 30 minutes, and then restart it.
●
Clean the Heating Return filter.
●
Flush the heat exchanger.
E030
Abnormal exhaust temperature
Contact Technical Support at 1-800-519-8794.
E046
Abnormal operation: limit control
Contact Technical Support at 1-800-519-8794.
E047
Abnormal operation: exhaust thermostat
Contact Technical Support at 1-800-519-8794.
E060
Abnormal operation: dual venturi
Contact Technical Support at 1-800-519-8794.
E109
Abnormal operation: fan motor
Clean the intake air filter.
E110
Abnormal air pressure
●
Ensure that the exhaust pipe is free of obstructions.
●
Clean the intake air filter.
E205
Heating supply thermistor open or short circuit
Contact Technical Support at 1-800-519-8794.
E218
Heating return thermistor open or short circuit
Contact Technical Support at 1-800-519-8794.
E351
Abnormal Auto feeder valve (make-up water)
Contact Technical Support at 1-800-519-8794.
E352
High water pressure
Contact Technical Support at 1-800-519-8794.
E353
Abnormal operation: water pressure sensor
Contact Technical Support at 1-800-519-8794.
E407
Hot water outlet thermistor open or short circuit
Contact Technical Support at 1-800-519-8794.
E421
Cold water inlet thermistor open or short circuit
Contact Technical Support at 1-800-519-8794.
E515
Abnormal operation: PCB
●
Ensure that the electrical cord is properly grounded.
●
Reset the boiler from the front panel.
E517
Abnormal operation: DIP switch setting
Contact Technical Support at 1-800-519-8794.
E594
Abnormal operation: EEPROM
Contact Technical Support at 1-800-519-8794.
E615
Abnormal operation: input and memory
Contact Technical Support at 1-800-519-8794.
E740
Abnormal operation: outdoor temperature
sensor (appears only when the outdoor reset
curve is enabled).
●
Ensure that the outdoor reset curve is configured properly.
●
Check the outdoor temperature sensor wiring connection.
E777
Abnormal operation: LWCO
●
Check the LWCO wiring connection
●
Ensure that the system water level is appropriate.
●
Add make-up water to the system if necessary.
E782
Abnormal operation: main panel communication Contact Technical Support at 1-800-519-8794.
If any of these remedies do not resolve the problem, contact Technical Support at 1-800-519-8794.