GV5/GV3.5 OPERATIONS & MAINTENANCE MANUAL
OPERATING THE TRANSMITTER
VERSION 0.2 2014-07-23
PAGE 3.2.165
Turn-On Behaviour
The
Turn-on Behaviour
) allows users to delay the start-up (RF on) of the
transmitter when recovering from an ac power loss, in order to limit the simultaneous power demand
from multiple transmitters on a common generator by staggering their turn on sequence.
Enter a value for Turn-On Delay in the allowable range of 0-120 seconds, defaulted to 0
seconds (disabled).
Enter a value for Ramp-Up Speed in the allowable range of 0-100%, defaulted to 100%
(normal).
Press
Apply
to save the change or
Cancel
to discard changes.
Figure 3.2.142: Turn-On Delay