background image

Nature Sauna Inc. Canada.    3625 Loreto Rue, Brossard, QC, Canada. TEL: (1)514-663-2291    Website: www. naturesauna.com 

 

Rearrange  the  stones  in  the heater  at  least  once  a  year  or  twice  if  it  is  in  frequent  use  (maximum  500  hours).  To 

decide the correct volume of stones in the heater, refer to technical data provided (table 1). 

CHART 5

:(

PILING OF THE SAUNA STONES

 

 

Air Ventilation of SAUNA ROOM 

CHART 6

LOCATION OF INLET AND OUTLET VENT

 

 

1.

 

Air supply vent. 

2.

 

Optional air supply vent if mechanical exhaust ventilation is used, the opening should be located 20” above 

the heater. 

3.

 

Exhaust air vent. 

4.

 

Drying vent, which is closed during heating and bathing. The sauna can also be dried by leaving the door 

open after bathing.   

If there is an exhaust vent in the sauna room only, leave a MIN 2” opening under the sauna room door. (Mechanical 

ventilation is recommended). 

 

To ventilate the Sauna room, we mean that drawing air around the heater and moving the heat to the farthest 

part of sauna room. 

 

Considering air ventilation of sauna room, the inlet vent and the outlet vent should be installed. 

The inlet vent should be installed on the wall below the heater (chart 6a). When using mechanical ventilation, inlet 

vent is placed at least 20” above the heater (chart 6b) or on the ceiling above the heater (chart 6c). The heavy cold air 

that is blown into sauna room is mixed with the light hot air from the heater, bringing in fresh air for the users. The inlet 

vent should have a diameter of 2”-4”. 

The  outlet vent should be placed diagonally opposite to the inlet. It is advised  the outlet vent  is placed under the 

platform in a sauna room as far as possible from the inlet vent. It can be installed near the floor, or lead outside through a 

pipe from the floor going to a vent to the sauna ceiling, or under the door (to the washroom). 

In this case, the sill slot must be at least 2” and it is recommended there is mechanical ventilation in the washroom . The 

size of the outlet should be twice of the inlet. 

Warning:                1. Do not turn on power when install or maintain the heater. 

2. Do not cover heater with clothes which may cause a risk of fire. 

 

Содержание NTSB-20

Страница 1: ...M80MI AM90DI AM80DI AM60DI AM45DI AM30DI AM30D The Heater Installation Operation AM60MI AM45MI AM30MI AM30M USER HANDBOOK MODEL Welcome to select the above AM Heater Kead the user handbook before using the heater NTSB 20 NTSB 30 NTSB 45 NTSB 60 NTSB 80 NTSB 90 NTSB2 9 20110110 Please read the user handbook BEFORE using the heater ...

Страница 2: ...CE TO SHELF OVER 20 in ABOVE THE FLOOR inch CEILING inch FLOOR inch 240V60Hz SINGLE PHASE STONES lb NTSB 20 2 0 70 141 75 2 5 43 7 120V16 7A 3 12AWG 26 NTSB 30 3 0 70 141 75 2 5 43 7 12 5A 3 12AWG 26 NTSB 45 4 5 106 212 75 3 2 5 43 7 18 75A 3 12AWG 40 NTSB 60 6 0 176 317 75 4 6 43 7 25A 3 10AWG 40 NTSB 80 8 0 282 423 75 5 2 8 43 7 33 3A 3 10AWG 44 NTSB 90 9 0 318 459 75 5 2 8 43 7 37 5A 3 8AWG 44 ...

Страница 3: ...UNA ROOM must be sealed splash proof and have a moisture condensing vent with 3 8 diameter its maximum height from the floor must not exceed 20 see chart 2 NOTE The screw must be tighten leave about 3 mm between screw head and the wall CHART 1A CHART 1B CHART 1C 0 12 16 14 1 57 14 57 23 6 5 9 B SCREW 7 43 A min 75 CHART 1D TABLE 2 CHART 2 2 NTSB 20 11 11 11 11 A MIN STOVE B MIN NTSB 30 NTSB 45 6 5...

Страница 4: ...s operating time Turn the knob to anywhere between 1 4 hours on the operating time scale if wish to skip the preset time and start the heater immediately CONTROL TEMP With outer controller NTS 200 Please check the CONTROLLER CON3 INSTRUCTIONS MANUAL for instruction and operation of the outer controller Please check diagram 9 for circuit diagram ATTENTION Check sauna room before restart the timer S...

Страница 5: ...st part of sauna room Considering air ventilation of sauna room the inlet vent and the outlet vent should be installed The inlet vent should be installed on the wall below the heater chart 6a When using mechanical ventilation inlet vent is placed at least 20 above the heater chart 6b or on the ceiling above the heater chart 6c The heavy cold air that is blown into sauna room is mixed with the ligh...

Страница 6: ...d the panel Spruce wood is recommended as material of wall and ceiling Heating Ensure there is nothing near the heater before switching on it The heater and the stones may emit smells when you use the heater for the first time Make sure that the sauna room has been efficiently ventilated or open the sauna room door It will take about an hour to reach suitable temperature in sauna room if the outpu...

Страница 7: ...CIRCUIT DIAGRAM CONTREL INSIDE NTSB 20 5 4 6 3 2 1 L N 120VAC60Hz Timer Limit Control Thermostat Contactor 240VAC60Hz L1 L2 1 2 3 6 4 5 3 2 1 Heating elements M al a b bo CHART 9 CIRCUIT DIAGRAM CONTREL OUTSIDE Heating elements SAUNA HEATER 240VAC60Hz L3 1 L3 L4 L4 1 2 3 5 4 6 3 2 L3 L4 CONTROL BOX L4 L3 L4 L4 L3 L3 ...

Страница 8: ...Calor de Hogar Av Tecnológico 735 PB San Salvador Tizatlalli Metepec 52172 Edo de México Teléfono 722 216 3330 55 1163 6038 www calordehogar com servicio calordehogar om c ventas calordehogar com ...

Отзывы: