Connecting RSE Voltage Signals
You can connect referenced single-ended (RSE) signals to the
NI 9205.
Figure 4.
Connecting RSE Voltage Signals
NI 9205
MUX
PGIA
ADC
V
1
V
2
COM
AI1
AI0
–
–
+
+
In an RSE configuration, the NI 9205 measures each channel
with respect to COM. To connect RSE signals to the NI 9205,
you must connect the voltage ground signal to COM to keep the
maximum working voltage in the specified range.
Note
If you leave COM unconnected, the signals float
outside the working input range of the NI 9205. This
NI 9205 Getting Started Guide
|
© National Instruments
|
19