SCC-RLY01 Relay Module User Guide
4
ni.com
For information about how to configure the SCC-RLY01 module with
NI-DAQmx, refer to the
SCC Quick Start Guide
.
Specifications
These ratings are typical at 25 °C unless otherwise stated.
Electrical
Contact type ............................................SPDT (Form C), nonlatching
Nominal switching capacity ...................5 A at 250 VAC
5 A at 30 VDC
Signal bandwidth ....................................DC to 400 Hz
Contact resistance ...................................30 m
Ω
max
Switching time
Operate time (NC to NO) ................5 ms (10 ms max)
Release time (NO to NC) ................4 ms (5 ms max)
1
Maximum operating speed .....................30 cps at rated load
Contact lifetime ......................................5
×
10
7
operations at 180 cpm
(minimum)
1
Excluding contact bounce time
SCC-RLY01
E Series
NO
NC
COM
+5 V
PO (
X )
D GND
1
2
3
390
Ω
, 1/4 W