Minimum chassis cooling clearances
Above
44.45 mm (1.75 in)
Rear
76.20 mm (3.00 in)
Sides
44.45 mm (1.75 in)
Environmental
Maximum altitude
4,600 m (570 mbar) (at 25 °C ambient)
Note
Fan speed selector must be set to High to meet the maximum altitude
specification.
Pollution Degree
2
Indoor use only.
Operating Environment
Ambient temperature range
0 °C to 50 °C
Relative humidity range
10% to 90%, noncondensing
Storage Environment
Ambient temperature range
–40 °C to 71 °C
Relative humidity range
5% to 95%, noncondensing
Shock and Vibration
Operational shock
30 g peak, half-sine, 11 ms pulse
Random Vibration Operating
5 to 500 Hz, 0.3 g
rms
Caution
When using a single power supply unit, you must use a power supply
filler panel (NI part number 784057-01) in the empty slot to meet operational shock
and vibration specifications.
Acoustic Emissions
Sound Pressure Level (at Operator Position)
Auto fan (up to ~30 °C ambient)
57.0 dBA
High fan
69.0 dBA
38
|
ni.com
|
PXIe-1086DC User Manual and Specifications