3.
Verify that the fan is properly installed by pulling it forward with a light force without
pressing the latch. If the fan does not slide out without pressing in the latch, it is installed
correctly.
4.
Close the fan door.
Specifications
This document contains specifications for the PXIe-1086DC chassis.
Electrical
AC Input
Input rating
210 to 300 VDC, 3.5 to 6 A
100 to 240 VAC, 12 to 6 A
Operating voltage range
1
210 to 300 VDC
90 to 264 VAC
Nominal AC input frequency
50/60 Hz
Operating AC frequency range
1
47 to 63 Hz
Efficiency
70% typical
Power disconnect
The AC/DC power cable provides main power
disconnect. Do not position the equipment so
that it is difficult to disconnect the power cord.
The front-panel power switch causes the
internal chassis power supply to provide DC
power to the CompactPCI/PXI Express
backplane. You also can use the front panel
terminal block 4-pin connector and power
mode switch to control the internal chassis
power supply.
DC Output
Table 7. DC Current Capacity (I
mp
)
Voltage
Maximum Current Single Power
Supply
Maximum Current Dual Power
Supplies
+3.3 V
50 A
60 A
+5 V
40 A
49 A
1
The operating range is guaranteed by design.
PXIe-1086DC User Manual and Specifications
|
© National Instruments
|
35