background image

USER GUIDE

SCC-AO10 Isolated Analog 
Output Module

The SCC-AO10 is an isolated voltage output module with an output range 
of ±10 V. The output voltage level is controlled by the DAC output of an 
E/M Series DAQ device. You can increase the output voltage level to 
±20 V by connecting two SCC-AO10 modules in series.

Conventions

The following conventions are used in this guide:

»

The 

»

 symbol leads you through nested menu items and dialog box options 

to a final action. The sequence 

File»Page Setup»Options

 directs you to 

pull down the 

File

 menu, select the 

Page Setup

 item, and select 

Options

 

from the last dialog box.

This icon denotes a note, which alerts you to important information.

This icon denotes a caution, which advises you of precautions to take to 
avoid injury, data loss, or a system crash.

 

When this symbol is marked on 

the product, refer to the 

Read Me First: Safety and Radio-Frequency 

Interference

 document, shipped with the product, for precautions to take.

When symbol is marked on a product it denotes a warning advising you to 
take precautions to avoid electrical shock.

When symbol is marked on a product it denotes a component that may be 
hot. Touching this component may result in bodily injury.

bold

Bold text denotes items that you must select or click in the software, such 
as menu items and dialog box options. Bold text also denotes parameter 
names.

italic

Italic text denotes variables, emphasis, a cross-reference, an introduction 
to a key concept, or text as it appears on a hardware label. Italic text also 
denotes text that is a placeholder for a word or value that you must supply.

Содержание Isolated Analog Output Module SCC-AO10

Страница 1: ...a caution which advises you of precautions to take to avoid injury data loss or a system crash When this symbol is marked on the product refer to the Read Me First Safety and Radio Frequency Interfere...

Страница 2: ...ies signal conditioning module What You Need to Get Started To set up and use the SCC AO10 you need the following items Hardware SC 2345 2350 with one of the following SCC PWR01 SCC PWR02 and the PS01...

Страница 3: ...t covers or connecting disconnecting any signal wires Plug the SCC AO10 into either SC 2345 2350 analog output socket J X 17 where X is 0 or 1 The SC 2345 2350 routes the voltage output of E M Series...

Страница 4: ...CC AO10 Connected to a Load with a High Common Mode Voltage Connecting Two SCC AO10 Modules in Series You can increase the maximum total output voltage to 20 V by connecting two SCC AO10 modules in se...

Страница 5: ...late the total output voltage from both SCC AO10 modules where VOutTotal is the total output voltage from both SCC AO10 modules VOUT1 is the voltage across terminals 1 and 3 of the SCC AO10 module in...

Страница 6: ...ground or chassis ground Refer to the Connecting the SCC AO10 to a Load section for ways to use the isolated ground in signal connections Calibrating Gain and Offset Errors The SCC AO10 is calibrated...

Страница 7: ...on the top of the SCC AO10 until the voltmeter reads 9 9 VDC The gain is now calibrated Specifications These ratings are typical at 25 C unless otherwise stated Electrical Number of output channels On...

Страница 8: ...no load 15 V 6 mA max at full load 5 73 mA max with no load Digital power 5 V 1 15 W max at full load 600 mW max with no load 5 V 230 mA max 120 mA max with no load Physical Figure 4 SCC AO10 Dimensio...

Страница 9: ...ges no greater than 42 4 Vpeak or 60 VDC Do not use this device for connection to signals or for measurements within Categories II III or IV Isolation Voltage Channel to earth isolation Continuous 60...

Страница 10: ...lass A emissions FCC 47 CFR Part 15B Class A emissions ICES 001 Class A emissions Note For the standards applied to assess the EMC of this product refer to the Online Product Certification section Not...

Страница 11: ...th which NI complies as well as other environmental information not included in this document Waste Electrical and Electronic Equipment WEEE EU Customers At the end of the life cycle all products must...

Страница 12: ...al Instruments products technology refer to the appropriate location Help Patents in your software the patents txt file on your media or the National Instruments Patent Notice at ni com patents 2002 2...

Отзывы: