National Instruments Corp.
11
FP-AI-100 and cFP-AI-100
Voltage Inputs
The following input signal ranges are software selectable by
channel.
Input impedance................................ 1.5 M
Ω
Effective resolution ........................... 11.3 bits
Signal input bandwidth ..................... 170 Hz
Voltage
Input Range
Typical
Offset Error at
15 to 35
°
C
Maximum
Offset Error at
–40 to 70
°
C
0–1 V
0–5 V
0–15 V
0–30 V
±
1 V
±
5 V
±
15 V
±
30 V
2.9 mV
6.5 mV
13 mV
17.5 mV
3.6 mV
9.5 mV
21.8 mV
35.1 mV
9.3 mV
17.2 mV
30 mV
33.3 mV
10.3 mV
23 mV
44.7 mV
62.5 mV
Voltage
Input
Range
With
Overranging
Typical
Gain Error
at 15 to 35 °C
(% of Reading)
Maximum
Gain Error at
–40 to 70
°
C
(% of Reading)
0–1 V
0–5 V
0–15 V
0–30 V
±
1 V
±
5 V
±
15 V
±
30 V
0–1.2 V
0–6 V
0–18 V
0–36 V
±
1.2 V
±
6 V
±
18 V
±
36 V
0.065%
0.065%
0.065%
0.065%
0.07%
0.07%
0.07%
0.07%
0.19%
0.19%
0.19%
0.19%
0.22%
0.22%
0.22%
0.22%