Appendix C
Fieldbus Parameters
©
National Instruments Corporation
C-3
FieldPoint FP-3000 User Manual
Table C-1.
Error Codes
Error Code
Code
Description
Other
0x0001
Undefined block error condition.
Block Configuration Error
0x0002
The block has detected an error in its configuration.
This usually indicates a static parameter has been left
uninitialized.
Link Configuration Error
0x0004
The logical connection between this block and another
block is misconfigured.
Simulate Active
0x0008
For I/O function blocks, this indicates that simulation is
enabled. For the resource block, this indicates that the
simulate jumper has been set, allowing simulation to be
enabled in other blocks.
Local Override
0x0010
The block has locally overridden the output value.
This can be the result of an interlock or faultstate.
Device Faultstate Set
0x0020
The block’s faultstate behavior is active.
Device Needs
Maintenance Soon
0x0040
The device is reporting performance degradation that
will soon require maintenance.
Input Failure/BAD PV
Status
0x0080
Either the input transducer channel has reported a
failure, or the input parameter from an upstream block
has reported a failure. For an AI block, this could be
caused by an open circuit being detected on the
FP-AI-100 input module.
Output Failure
0x0100
The output transducer channel has reported a failure. For
an AO block, this could indicate that the FP-AO-200
cannot drive the current request, perhaps due to an open
circuit.
Memory Failure
0x0200
The storage for nonvolatile and static parameters was
corrupted.
Lost Static Data
0x0400
The device was unable to restore the values of static
parameters after a restart.
Lost NV Data
0x0800
The device was unable to restore the values of
nonvolatile parameters after a restart.
Readback Check Failed
0x1000
The value read back from the output channel does not
match the value the output channel was set to.