PID Control
In a Fieldbus network, a PID control loop is composed of three function
blocks: an Analog Input (AI) block, a Proportional Integral Derivative
(PID) block, and an Analog Output (AO) block. Figure 4-1 shows all three
blocks and the interconnections between the blocks. The PID block’s
IN
parameter is connected to the AI block’s
OUT
parameter. The PID uses this
linkage to determine the current value of the process variable it is
controlling. The PID uses linkage from the PID’s
OUT
parameter to the AO
block
CAS_IN
parameter to adjust the AO block setpoint. To allow the
cascade to be correctly initialized, a third back calculation linkage is
created that allows the AO block to send its current setpoint back up to the
PID block. These linkages must be established by using a PC-based
Fieldbus configuration system, such as the NI-FBUS Configurator. For
more information, refer to
Example 2: Temperature Control with the
.
Table 4-2.