FieldPoint
™
Note to Users
Using FieldPoint and
Compact FieldPoint Safely
in Hazardous Locations
This product is suitable for use in U.S. and Canada: Class I,
Division 2, Groups A, B, C, D, T4 hazardous locations; and
nonhazardous locations.
Cautions
Explosion hazard—Substitution of
components may impair suitability for Class I,
Division 2.
Explosion hazard—Do not disconnect equipment unless
power has been switched off or the area is known to be
nonhazardous.
Equipment must be used within its electrical and
environmental ratings. Refer to the
Specifications
section
of the product manual. Refer to the product label for
manufacturing location.
This product must be installed in an enclosure rated at least
IP 54.
For screw-terminal connections on the FP-1000, FP-1001, and
FP-TB-1, use 16–26 AWG copper wire with 7 mm (0.28 in.) of
insulation stripped from the end. Tighten screw terminals to
0.5–0.6 N
⋅
m (4.4–5.3 lb
⋅
in.) of torque.