10.
CPE - PERFORMANCE DATA
MODEL
COOLING
BTUH
HEATING
BTU @ 240V
HEATING
BTU @ 208V
EER
(outside temp.)
HEATING
KW
SHIP
WT.
95°
240
208
CPE41205-D
12,000
17,061
12,966
9.0
5
3.8
315
CPE41207-D
12,000
25,591
12,966
9.0
7.5
5.6
325
CPE41210-D
12,000
34,121
25,591
9.0
10
7.5
315
CPE41805-D
18,000
17,061
12,966
9.0
5
3.8
325
CPE41807-D
18,000
25,591
19,108
9.0
7.5
5.6
325
CPE41810-D
18,000
34,121
25,591
9.0
10
7.5
325
CPE41815-D
18,000
51,182
38,557
9.0
15
11.3
325
CPE42405-D
22,400
17,061
12,966
9.0
5
3.8
350
CPE42407-D
22,400
25,591
19,108
9.0
7.5
5.6
350
CPE42410-D
22,400
34,121
25,591
9.0
10
7.5
350
CPE42415-D
22,400
51,182
38,557
9.0
15
11.3
350
CPE43010-D
27,400
34,121
25,591
9.0
10
7.5
360
CPE43015-D
27,400
51,182
38,557
9.0
15
11.3
360
CPE - ELECTRICAL DATA
MODEL
VOLTAGE
COMPRESSOR
INDOOR
BLOWER
MOTOR
OUTDOOR
FAN MOTOR
TOTAL
AMPS
MINIMUM
CIRCUIT
AMPACITY
MAXIMUM
OVERCURRENT
PROTECTOR
RLA
LRA
HP
FLA
LRA
HP
FLA
LRA
CPE41205-D
208-230/60/1
5.5
26.0
1/3
3.0
-
1/4
1.8
3.6
24.2
30.3
35
CPE41207-D
208-230/60/1
5.5
26.0
1/3
3.0
-
1/4
1.8
3.6
41.7
46.0
50
CPE41210-D
208-230/60/1
5.5
26.0
1/3
3.0
-
1/4
1.8
3.6
41.7
57.5
60
CPE41805-D
208-230/60/1
8.3
44.0
1/3
3.0
-
1/4
1.8
3.6
25.8
30.3
35
CPE41807-D
208-230/60/1
8.3
44.0
1/3
3.0
-
1/4
1.8
3.6
41.7
46.0
50
CPE41810-D
208-230/60/1
8.3
44.0
1/3
3.0
-
1/4
1.8
3.6
46.0
57.5
60
CPE41815-D
208-230/60/1
8.3
44.0
1/3
3.0
-
1/4
1.8
3.6
67.8
84.6
90
CPE42405-D
208-230/60/1
9.5
58.0
1/3
3.0
-
1/4
1.8
3.6
25.8
30.3
35
CPE42407-D
208-230/60/1
9.5
58.0
1/3
3.0
-
1/4
1.8
3.6
43.3
48.0
50
CPE42410-D
208-230/60/1
9.5
58.0
1/3
3.0
-
1/4
1.8
3.6
47.6
57.5
60
CPE42415-D
208-230/60/1
9.5
58.0
1/3
3.0
-
1/4
1.8
3.6
69.4
84.6
90
CPE43010-D
208-230/60/1
11.6
74.0
1/3
3.0
-
1/4
1.8
3.6
47.0
57.5
60
CPE43015-D
208-230/60/1
11.6
74.0
1/3
3.0
-
1/4
1.8
3.6
68.9
84.6
90
OPTIONAL ACCESSORIES
CPWS
wALL SLeeVe (UNASSeMBLeD)
CPWSA
wALL SLeeVe ADAPTOR (UNASSeMBLeD)
CPLG
ARCHiTeCTURAL LOUVeR GRiLLe
CPLG-S
ARCHiTeCTURAL LOUVeR FOR SLeeVe
CPLG-P
ARCHiTeCTURAL LOUVeR GRiLLe (PAiNTeD)
CPLG-SP
ARCHiTeCTURAL LOUVeR FOR SLeeVe (PAiNTeD)
PAINTED LOUVER
STAMPeD GRiLLe (PAiNTeD)
-DF (CALL FOR DETAILS)
SLOTTeD FiLTeR DOOR
-DD (CALL FOR DETAILS)
SeCONDARY DRAiN PAN
-DP (CALL FOR DETAILS)
OMiTeD STAMPeD LOUVeR AND GRiLLe
-DB (CALL FOR DETAILS)
COMBiNATiON OF (-DD) AND (-DP) See ABOVe
CONSULT FACTORY FOR OTHeR COMBiNATiONS
National Comfort Products offers
Architectural Louver Grilles for all models.
Outdoor grilles provided by others must be
approved by National Comfort Products to
maintain unit performance and warranty
coverage. See Architectural Louver Grilles
Specification Sheet for more details.
COMFORT PACK AIR FLOW
MODEL
Ton
HP
Static
0.1
0.2
0.3
0.4
CPE412
1
1/3
400
380
362
344
CPE418
1.5
1/3
650
618
588
559
CPE424
2
1/3
715
680
647
615
CPE430
2.5
1/3
820
780
740
700
15 13/16"
11 1/16"
3 9/16"
1 25/32"
43"
28"
1 17/32"
7/8"
7 11/16"
31 7/16"
23 9/16”
7 15/16”
OPENING
15/16”
FRONT TO
DRAIN TUBE
OPENING
24"
7 3/4"
Option (DF)
Slotted Filter Door
for Open Returns
Note: Unit must be
mounted a minimum
of 8” above finished floor.
Solid Filter Door
for Ducted Returns
Return
Junction
Box
Low Voltage
Thermostat
Connection
Drain
Note: All specifications are subject to change without notice.