Страница 2: ...Construction 4 Types and Dimensions Chapter Two Technical characteristic 1 Discharge Curve 2 Charge Performance 3 Choose Battery 4 Internal resistance and short circuit current Chapter Three Operatio...

Страница 3: ...uld not be carefully handled it would bring a lot of endangers to environment and heath Please check laws to get the validity ways or send the equipment to service center z The changer of battery can...

Страница 4: ...100 the remaining capacity above 94 when storage for 3 months 25 z Remarkable high rate discharge performance Low internal resistance Patented grid design Large section copper structure z Supply the U...

Страница 5: ...z Correspondence exchange and transmission system z Mobile communication system z Power plant and power transformer system z Navigation aid signaling system z Solar energy system z Radio and broadcas...

Страница 6: ...19 0 EosG400 2 400 300 220 166 184 5 360 5 372 25 0 EosG500 2 500 375 275 194 5 184 5 360 5 372 30 0 EosG600 2 600 450 330 223 184 5 360 5 372 35 5 EosG800 2 800 600 440 154 229 555 566 52 7 EosG1000...

Страница 7: ...acteristics of 100 DOD EosG500 battery with current of 0 1C10A and limit voltage of 2 35V Cell 25 1 95 2 05 2 15 2 25 50 DOD 60 40 20 0 8 4 0 0 00 0 05 24 20 16 12 ChargeTime h ChargeCurrent Charge Ca...

Страница 8: ...98 0 116 9 85 8 58 2 50 2 40 0 33 2 15 0 7 8 4 2 1 65V 496 8 418 8 300 0 187 8 114 2 83 7 56 7 49 5 39 5 32 9 14 9 7 7 4 2 1 70V 466 8 400 2 276 0 179 4 110 0 81 3 56 3 48 9 38 8 32 4 14 8 7 7 4 1 1 7...

Страница 9: ...7 19 3 10 5 1 90V 642 9 514 3 418 7 306 1 213 3 171 7 121 7 106 1 85 6 71 8 34 3 18 0 9 7 EosG1000 EV cell 5min 15min 30min 1h 2h 3h 5h 6h 8h 10h 24h 48h 100h 1 60V 1455 0 1224 3 994 9 655 6 403 7 296...

Страница 10: ...78 1 43 5 1 70V 3846 9 3271 6 2489 2 1764 0 1136 4 826 4 554 2 478 1 379 3 311 6 144 8 77 5 42 8 1 75V 3628 9 3079 3 2295 2 1653 7 1094 6 807 5 544 7 471 1 374 1 308 9 143 5 76 6 41 7 1 80V 3428 4 28...

Страница 11: ...4h 5h 6h 8h 10h 24h 1 60V 1434 6 1201 5 956 7 676 5 436 5 323 3 257 8 213 6 182 4 142 6 116 4 52 5 1 65V 1364 4 1153 0 904 9 625 1 400 4 303 4 244 6 206 1 176 6 137 3 113 6 51 5 1 70V 1311 8 1112 1 88...

Страница 12: ...9 434 7 371 2 291 0 245 5 112 8 1 90V 2351 8 1911 9 1462 2 1045 3 700 8 570 1 478 5 406 2 346 8 272 2 227 7 105 7 EosG1500 End voltage per cell 5min 15min 30min 1h 2h 3h 4h 5h 6h 8h 10h 24h 1 60V 423...

Страница 13: ...6 1 75V 7488 5 6306 8 5021 8 3394 4 2225 5 1672 6 1372 5 1165 9 1003 6 767 4 644 4 296 6 1 80V 7281 7 6011 4 4844 6 3315 7 2184 2 1613 6 1328 2 1133 4 974 0 747 8 634 6 292 2 1 85V 6621 9 5474 8 4308...

Страница 14: ...don not discharge the depth of battery too much You d better control the DOD below the 80 especially in the power shortage areas Fig 2 3 Selection Curve of Cell Type end voltage per cell 1 80V 4 Inter...

Страница 15: ...Internal resistance and short circuit current 25 Type Internal Resistance m Short Circuit Current A EosG200 0 66 3098 EosG260 0 53 3560 EosG300 0 48 4025 EosG400 0 34 5231 EosG500 0 33 6083 EosG600 0...

Страница 16: ...the battery in the short time the sufficient electricity The user acts according to the locus the power supply category comparative table 3 1 The solar system parameter establishment is table 3 2 Tab...

Страница 17: ...ient of capacity life is 1 25 The coefficient of capacity in winter temperature reference to Fig 3 1 2 Capacity and Influence Factor The capacity of battery is the capacity that battery can be dischar...

Страница 18: ...ruption the grid and shorten the life of the battery If the floating voltage is lower the battery can t be kept in fully charged state this will crystallize PbSO4 decrease the capacity and also shorte...

Страница 19: ...tes T the actual ambient temperature LT is designed life at T ambient temperature L25 is designed life at 25 ambient tempe rature Ambient temperature elevating also will accelerate the battery slab la...

Страница 20: ...ing table table3 3 is in different discharge the time need for 0 1C10A and 0 2C10A battery 2 On condition of constant voltage the value of charge current hasn t varied for continuous three hours Fig 3...

Страница 21: ...eries are recommended as follows z Monthly Maintenance Implement the under mentioned inspection every month Keep the battery room clean Measure and record the ambient temperature of the battery room C...

Страница 22: ...such as water loss life decrease heat out of control deformation etc Too low end voltage The end voltage is also an important parameter for battery The battery shall stop discharge when reach a certai...

Страница 23: ...anual V3 7 23 VRLA Battery Regular Maintenance Record Type Place Status Number of battery Total Voltage V Current A Temperature No Voltage V No Voltage V 1 13 2 14 3 15 4 16 5 17 6 18 7 19 8 20 9 21 1...