StarLink

 SLE

-

MAXVI

-

FIRE & SLE

-

MAXAI

-

FIRE Commercial Series Sole/Dual

-

Path Alarm Communicators 

--

 Installation Instructions

 

11

 

Name

 

Format Type

 

Handshake Frequency

 

Speed

 

Ademco Slow

 

4/2

 

1400 Hz or 2300Hz

 

10pps

 

Ademco Slow

 

4/2 checksum

 

1400 Hz or 2300Hz

 

10pps

 

Radionics Slow

 

4/2

 

2300Hz

 

10pps

 

Radionics Slow

 

4/2 checksum

 

2300Hz

 

10pps

 

Silent Knight Fast

 

4/2

 

1400 Hz or 2300Hz

 

20pps

 

Silent Knight Fast

 

4/2 checksum

 

1400 Hz or 2300Hz

 

20pps

 

Radionics Fast

 

4/2

 

2300Hz

 

40pps

 

Radionics Fast

 

4/2 checksum

 

2300Hz

 

40pps

 

Universal High Speed

 

4/2

 

1400 Hz or 2300Hz

 

40pps

 

Universal High Speed

 

4/2 checksum

 

1400 Hz or 2300Hz

 

40pps

 

4/2 P

ulse 

Dialin

Fo

rm

at 

 

Com

pat

ibilit

y

 

Note

:

  

T

h

e

 SL

E Se

ri

e

s Co

m

m

u

n

ic

a

to

rs

 

a

re

 c

o

m

pa

tib

le

 w

ith

 a

n

y Ce

rti

fie

d

 4

/2

 

Rec

e

iv

e

su

ch

 a

s t

he

 Ad

em

co

 6

8

5

.

 

REN

  =  0.    The 

Ringer  Equivalence  Number

  (

REN

)  indicates  the  maximum  number  of 

devices  allowed  to  be  connected  to  a  telephone  interface.    The  termination  of  an 
interface may consist of any combination of devices subject only to the requirement that 
the sum of the 

REN

s of all the devices not exceed five (5).

 

Alternate Telco Line to Alarm Panel Supervision

 

The following wiring and programming method allows an existing FACP to use its two telephone connections 

(primary and secondary) for supervision and central station reporting through the StarLink SLE

-

MAXVI

-

FIRE 

communicator.  By removing the 

JP2

 shunt and enabling the feature "

Tip/Ring Wiring Fault Report

", when any 

communicator trouble is detected, the StarLink communicator will remove voltage from the secondary telephone 

output, triggering the FACP to locally annunciate the Telco trouble and report the trouble to the central station.  

Note: 

Some FACPs require 

J7 

shunt to be removed for Primary Phone line to restore correctly.

 

 

To  terminate  more  than  two  conductors 

or 

conductors  of  different  wire  sizes  to  a  terminal, 

use the "pigtail" type wiring method as shown at 

right.  Use insulated wire for the pigtail, and firmly 

secure the conductors to the pigtail using an ap-

propriate wire nut or crimp connector for the num-

ber and gauge of conductors used.

 

I M P O R TAN T   W I R I N G   M E T H O D S

 

Incorrect

 

Correct 

--

 Use UL Certified pigtail or wire nut / crimp connector

 

PIGTAIL

 

WIRE NUT OR 

CRIMP

 

CONNECTOR

 

PIGTAIL

 

For  single

-

conductor  terminal 

blocks 

(like  the  type  shown  at 

left),  to  terminate  more  than  one 

conductor  to  a  terminal,  use  the 

wiring methods shown at right:

 

WIRE NUT OR 

CRIMP

 

CONNECTOR

 

PIGTAIL

 

In

 

For  "barrier"  type  terminal 

blocks

  (like  the  type  shown  at 

left),  to  terminate  two  conductors 

to a terminal, use the wiring meth-

ods shown at right:

 

Correct 

--

 Separate incoming and outgoing conductors

 

In

 

Out

 

Incorrect

 

Incorrect

 

In

 

Out

 

Correct 

--

 Single incoming and/or pigtail with UL Certified wire nut / crimp connectors

 

Содержание StarLinkFire SLE-MAXVI-FIRE

Страница 1: ...ENCY LISTINGS UL 864 Standard For Control Units and Accessories For Fire Alarm Systems 10th Edition UL 1610 Standard For Central Station Burglar Alarm Units UL 985 Standard For Household Fire Warning...

Страница 2: ...Indoor dry location use only TERMINAL DESCRIPTIONS Configure all inputs and outputs using the Management Center screen located at www NapcoNOC com Located at the bottom of the StarLink communicator PC...

Страница 3: ...ard Operation is as follows 1 Blink Low Aux Power input voltage 2 Blinks Check Input Power 3 Blinks Alarm report Failed to Communicate will restore only when the communicator path is restored 4 Blinks...

Страница 4: ...ing in any other manner please contact technical support GREEN IP NETWORK CONNECTION LED Labeled D14 or DS14 this LED is located to the right of the ETHERNET socket on the PC board Operation is as fol...

Страница 5: ...be used if mounted up to 50 feet from the control panel and 18 gauge wire should be used for up to 100 feet Reference the wiring diagrams further in this manual See the section CONTROL PANEL PROGRAM M...

Страница 6: ...ouble relay can be used to trigger a report to the central station The wiring between the control panel and the StarLink communicator is over several wires as follows TB1 PWR Regulated DC TB2 PWR GND...

Страница 7: ...ns jumper 1 may be removed to permit uploading and downloading without a technician on site however the dealer is responsible for ensuring the system is operating correctly after any downloads or chan...

Страница 8: ...TARLINK COMMUNICATOR HOUSING StarLink Communicator Terminals PC Board All connections are power limited except battery terminals Optional Use 12 or 24VDC Certified regu lated power supply Note Common...

Страница 9: ...terminals JP1 Shunt JP1 on top 2 pins Wiring Diagram for FACP Relay Trigger Input Reporting Refer to section SUPPLYING POWER NC NORMALLY ENERGIZED FIRE TROUBLE RELAY C NO 10k Aux Power Regulated 12 2...

Страница 10: ...10 StarLink SLE MAXVI FIRE SLE MAXAI FIRE Commercial Series Sole Dual Path Alarm Communicators Installation Instructions Housing Template 1 1 Scale Three Gang Mounting Double Gang...

Страница 11: ...nd central station reporting through the StarLink SLE MAXVI FIRE communicator By removing the JP2 shunt and enabling the feature Tip Ring Wiring Fault Report when any communicator trouble is detected...

Страница 12: ...cancelled NAPCO neither assumes nor authorizes any other person purporting to act on its behalf to modify to change or to assume for it any other warranty or liability concerning its products In no ev...

Отзывы: