background image

StarLink

 SLE Commercial Series Alarm Communicators -- Installation Instructions 

 

Control Center reports a trouble signal in the event that the 
network does not receive the expected supervision signal 
from the wireless communicator.  In addition, all models 
are powered directly from the control panel.   

 

For Commercial Burglary installations, under the 
armed condition, any loss of communication must be 
treated as a Burglary Alarm at the Central Station.

  

 

 

The model names are as follows: 

 

SLE-GSM-3/4G 

- Commercial / Residential Burglary and 

Residential Fire 2G, 3G and 4G Network Compatible 
GSM alarm capture Communicator, SIM card included.  
Black plastic enclosure.   

SLE-GSM-8D-3/4G 

- Commercial / Residential Burglary 

and Residential Fire 2G, 3G and 4G Network Compati-
ble GSM alarm capture Communicator. Supports re-
mote downloading to the Gemini GEM-P400, GEM-
P800, GEMP-801, Express XP-400 and XP-600 series 
control panels.  SIM card included.  Black plastic enclo-
sure.   

SLE-CDMA 

- Commercial / Residential Burglary and Resi-

dential Fire Universal CDMA alarm capture Communica-
tor.  Black plastic enclosure.   

SLE-CDMA-8D 

- Commercial / Residential Burglary and 

Residential Fire Universal CDMA alarm capture Com-
municator.  Supports remote downloading to the Gemini 
GEM-P400, GEM-P800, GEMP-801, Express XP-400 
and XP-600 series control panels.  Black plastic enclo-
sure.   

SLE-GSM-FIRE 

- Commercial / Residential Fire and Bur-

glary 2G, 3G and 4G Network Compatible GSM alarm 
capture Communicator.  SIM card included.  Red plastic 
enclosure.   

SLE-CDMA-FIRE 

- Commercial / Residential Fire and Bur-

glary CDMA radio in red plastic enclosure.   

 

ADDITIONAL COMPONENTS 

  In addition to the models listed above, the following sub-

assemblies are available: 

SLE-DLCBL

 - Download Cable, 6 feet. 

SLE-ANTEXT

 - Extended antenna with 15 feet of cable. 

WI2120.a  04/15 

333 Bayview Avenue 

Amityville, New York 11701 

For Sales and Repairs, (800) 645-9445 

For Technical Service, (800) 645-9440 or visit us at 

http://tech.napcosecurity.com/ 

(Note:  Technical Service is for security professionals only)

 

Publicly traded on NASDAQ      Symbol: NSSC 

© NAPCO 2015 

INTRODUCTION 

 The 

StarLink

 Commercial / Residential Fire and Burglary 

alarm capture radio communicators are fully supervised, 
wireless digital two-way subscriber units supported by an 
extensive nationwide wireless network.  All models are 
compatible with most 12VDC alarm control panels (always 
adhere to the documentation provided by the control panel 
manufacturer).  All can function as a backup to existing tel-
ephone lines, or as a primary communicator.  In backup 
mode, all units will automatically switch the communication 
channel from the telephone line to the network when tele-
phone line trouble is detected.  For Commercial installa-
tions, mount the unit to a single-, dual-, or three-gang elec-
trical box and route the wires through the back knockout(s), 
or as specified by local codes.  

See WI2140 for program-

ming information.  

 

 

The SLE Series radios use proprietary data-capture tech-
nology that captures the alarm report from the control panel 
and transmits the alarm signals to the SLE Control Center; 
the alarm signals are then forwarded to ANY central station 
via Contact ID or Sur-Gard System II via TCP/IP.  The SLE 

STARLINK RADIO REPORTING PATH 

 

The diagram below shows the transmission path of a 
signal from the StarLink radio to the central station.   

 

1. 

Signal from a Control Panel.  

 

2. 

StarLink

 radio receives the signal transmission 

(from the TIP an RING wires); sends RF signal 
through the GPRS network operator.  

3. 

Network Operator

, part of the vendor system, a 

section of the cellular spectrum.   

4. 

SLE Control Center

, receives and routes data. 

5. 

Central Station

(

 

(

 

(

 

(

 

(

 

(

 

(

 

(

 

(

 (     ) 

)

 

)

 

)

 

)

 

)

 

)

 

)

 

)

 

)

 

(1) 

(2) 

Control 
Panel 

Network  

Operator 

StarLink Network  

Operations Center 

(3) 

CENTRAL 

STATION 

(5) 

(4) 

StarLink 

Radio 

StarLink™ SLE  

Residential / Commercial Series  

Alarm Communicators  

INSTALLATION INSTRUCTIONS 

AGENCY LISTINGS 



UL 864 Standard For Control Units and Accessories For Fire 
Alarm Systems, 9th Edition 



UL 1610 Standard For Central-Station Burglar-Alarm Units 



UL 985 Standard For Household Fire Warning System Units 



UL 1023 Standard For Household Burglar-Alarm System 
Units 

CDMA models are 

Verizon

®

 Network Certified

 

Содержание StarLink SLE

Страница 1: ...Service is for security professionals only Publicly traded on NASDAQ Symbol NSSC NAPCO 2015 INTRODUCTION The StarLink Commercial Residential Fire and Burglary alarm capture radio communicators are fu...

Страница 2: ...ide of the end of line resistor into this PGM1 terminal and wire the other side of the resistor to the positive terminal of the zone TB4 PGM2 Open collector output This output is defaulted as Fail to...

Страница 3: ...lows GREEN RF SIGNAL STRENGTH LED Labeled D3 this LED is located at the lower right cor ner of the PC board Every 30 seconds the StarLink radio receiver section turns on and listens to the cell tower...

Страница 4: ...l garage doors etc as these Normal Standby Condition Blinks on momentarily every 10 seconds Unit is in standby waiting for an alarm to report Processing Alarm Conditions When processing an alarm this...

Страница 5: ...CKUP MODES 22 gauge wire may be used if mounted up to 50 feet from the control panel and 18 gauge wire should be used for up to 100 feet Reference the wiring diagrams further in this manual See the se...

Страница 6: ...at must be entered for each telephone number used but each telephone number may be assigned a different format CAUTION The installer should always be certain an area code is programmed into the contro...

Страница 7: ...Troubles It is required that if a StarLink radio or control panel trouble is detected that it is reported to the central station When the StarLink radio detects and sends a trouble to the control pane...

Страница 8: ...17 16 15 14 13 12 11 9 10 2 3 4 5 1 19 18 ZONE DEDICATED TO GPRS SUPERVISION CONTROL PANEL HOUSING 6 7 8 15 14 13 12 11 9 10 2 3 4 5 1 12V PGM1 PGM2 PGM3 IN1 IN2 GND IN3 RING PANEL RING TIP 2 2K 17 16...

Страница 9: ...11 9 10 2 3 4 5 1 19 18 CONTROL PANEL HOUSING 16VAC Refer to section SUPPLYING POWER AUX POWER RING TIP 6 7 8 15 14 13 12 11 9 10 2 3 4 5 1 12V PGM1 PGM2 PGM3 IN1 IN2 GND IN3 RING TIP 17 16 RTS R PAN...

Страница 10: ...5mA standby current is available HOME PHONES TO TELCO RJ31X RING TIP AUX POWER RING TIP RING TIP TELCO PHONE YELLOW BLACK Refer to section SUPPLYING POWER 6 7 8 15 14 13 12 11 9 10 2 3 4 5 1 12V PGM1...

Страница 11: ...10 2 3 4 5 1 19 18 CONTROL PANEL HOUSING 6 7 8 15 14 13 12 11 9 10 2 3 4 5 1 12V PGM1 PGM2 PGM3 IN1 IN2 GND IN3 RING PANEL RING TIP 2 2K 17 16 PANEL TIP RTS R PANEL TX B PANEL RX G StarLink Radio Term...

Страница 12: ...ING AUX POWER 16VAC Refer to section SUPPLYING POWER 6 7 8 15 14 13 12 11 9 10 2 3 4 5 1 12V PGM1 PGM2 PGM3 IN1 IN2 GND IN3 RING TIP 17 16 RTS R PANEL TX B PANEL RX G CTS Y StarLink Radio Terminals PA...

Страница 13: ...able HOME PHONES TO TELCO RJ31X TELCO T300 RJ31X RING TIP RING TIP 16VAC Transformer GRN RED YELLOW BLACK Refer to section SUPPLYING POWER 6 7 8 15 14 13 12 11 9 10 2 3 4 5 1 12V PGM1 PGM2 PGM3 IN1 IN...

Страница 14: ...O HOUSING MONITOR ZONE DEDICATED TO GPRS SUPERVISION 2 2K All connections are power limited ex cept AC Mains Telco and battery termi nals Terminals 14 17 No connections permitted COM Special Wiring In...

Страница 15: ...OUSING 6 7 8 15 14 13 12 11 9 10 2 3 4 5 1 12V PGM1 PGM2 PGM3 IN1 IN2 GND IN3 RING PANEL RING TIP 17 16 PANEL TIP RTS R PANEL TX B PANEL RX G StarLink Radio Terminals 1 2 3 4 5 6 7 8 9 10 11 12 13 14...

Страница 16: ...ailable TIP RING TIP RING TEL LINE PHONE HOME PHONES TO TELCO RJ31X Summary of connections RJ31X RED to StarLink module 10 RJ31X GREEN to StarLink module 11 RJ31X BROWN to Panel 32 RJ31X GRAY to Panel...

Страница 17: ...PANEL HOUSING 6 7 8 15 14 13 12 11 9 10 2 3 4 5 1 12V PGM1 PGM2 PGM3 IN1 IN2 GND IN3 RING PANEL RING TIP 17 16 PANEL TIP RTS R PANEL TX B PANEL RX G StarLink Radio Terminals 1 2 3 4 5 6 7 8 9 10 11 12...

Страница 18: ...standby current is available HOME PHONES TO TELCO RJ31X RING TIP Summary of connections RJ31X RED to StarLink module 10 RJ31X GREEN to StarLink module 11 RJ31X BROWN to Panel 28 RJ31X GRAY to Panel 29...

Страница 19: ...StarLink SLE Commercial Series Alarm Communicators Installation Instructions 19 Housing Template 1 1 Scale Three Gang Mounting Double Gang...

Страница 20: ...res two EOLRs Pro gram panel to report Open Close radio remembers last state of panel for Napco panels when used with local download cable 5 BURG without DACT Use IN2 or IN3 for both Alarm and Trouble...

Страница 21: ...StarLink SLE Commercial Series Alarm Communicators Installation Instructions 21 Notes...

Страница 22: ...22 StarLink SLE Commercial Series Alarm Communicators Installation Instructions Notes...

Страница 23: ...StarLink SLE Commercial Series Alarm Communicators Installation Instructions 23 Notes...

Страница 24: ...assumes nor authorizes any other person purporting to act on its behalf to modify to change or to assume for it any other warranty or liability concerning its products In no event shall NAPCO be liab...

Отзывы: