 SLE Commercial LTEVI & LTEAI Series Dual-Path Alarm Communicators -- Installation Instructions 



(Place 

JP1 

shunt on bottom two pins) 

 

 

Wiring Methods 



Strip wire carefully to avoid exposed conductors after 

installation, etc. 



Use UL Listed wire, ensuring that all conductors are to 

be insulated for the maximum voltage of any conductor 

in the enclosure 



All wiring methods must be performed in accordance 

with NFPA 70, Articles 725, and 800 

 

STEP 4:  APPLY POWER 



Attach antennas before applying power ! 



Apply 12/24VDC to terminals 1 and 2.  (For models 

without the charger board 

SLE-ULPS-R

).  For models 

with the 

SLE-ULPS-R

, apply power to the unit.   

 

STEP 5:  SIGNAL VERIFICATION 

 



Verify Online

:  To verify that the signals have been 

received by the StarLink radio Network online, go to 

www.NapcoNOC.com

, log in with your Username and 

Password, enter your 

Company ID 

number and the 

StarLink 

Radio Number

, then click 

Signal Log

.   

 

 IMPORTANT

:  Verify that the signals transmitted by the 

StarLink radio have been properly received by your central 

station before leaving the premises. 

 

 

NAPCO GEMINI C-SERIES (GEMC)  

CONTROL PANEL PROGRAMMING 

 

To program the central station receiver reporting format, 

use PCD-Windows Quickloader download software.  Open 

the 

Digital Communications 

screen, 

Central Station Re-

ceivers 

tab, as shown in the following image: 

 

 

A "Point ID" (also called "Contact ID") receiver format pro-

gramming example is shown: 

 

 
 

 

 

 

 

 

 
 

 

 

 

 

 

 
 

 

 

 

 

 

 
 

 

 

 

 

 

 
 

 

 

 

 

 

 

 
 

 

 

 

 

 

 
 

 

 

 

 

 

 
 

 

 

 

 

 

 
 

 

 

 

 

 

 
 

 

 

 

 

 

 
 

 

The radio can transmit to any central station capable of 

receiving SIA Contact ID or 4/2 via DACR technology or 

the DSC Sur-Gard Model System II or Sur-Gard System V 

central station receivers, Bosch D6100IPV6 or Bosch 

D6600 Receiver (with ITS-D6686 Ethernet Adapter) via 

TCP/IP using standard line security. 

 

 Note:

  A receiver reporting format must be entered for 

each telephone number used, but each telephone number 

may be assigned a different format. 

 

 

Note:

  UL Listed for UL 1076 APOU Proprietary Alarm 

Systems and UL 365 APAW Police Connect when report-

ing to a UL Listed Central Station Receiver Listed for UL 

1076 APOU Proprietary Alarm Systems or UL 365 APAW 

Police Connect, respectively.  For TCP/IP only Bosch 

D6600 or D6100IPV6 for UL1076 and UL365 applications. 

 

CAUTION:

  The installer should always be certain an 

area code is programmed into the control panel.   

Optional:

  If you wish the StarLink radio to report a code 

and zone number (Contact ID by default) to the central sta-

ules registered via the Internet are enabled for activation 

within 24 hours. 

 

STEP 2:  SELECT A MOUNTING LOCATION 

The mounting location should be indoors within the protect-

ed area and selected based on RF performance.  It is 

HIGHLY recommended that the installer carefully adhere to 

the following recommendations BEFORE any wires are 

installed. 

 



Generally, high locations are best.  DO NOT mount ra-

dio in basements or below grade as unpredictable per-

formance may result. 



DO NOT mount the 

radio 

in non-climate controlled envi-

ronments (i.e. attics may become extremely hot in sum-

mer, garages may become extremely cold in winter). 



Avoid mounting locations within 3 feet of AC power 

lines, fluorescent light fixtures, or large metal objects (air 

conditioners, metal garage doors, etc.) as these loca-

tions have been shown to have a detrimental effect on 

signal strength. 



A fair amount of care may be required to mount the 

StarLink radio 

so as to achieve an optimal RF path.  The 

installer should spend as much time as needed to obtain 

the highest signal level possible. 

 

a. 

Before applying power, be sure to connect the 

antenna

.  Temporarily connect power to the 

StarLink radio from a fully charged 12V (4AH mini-

mum) battery.  DO NOT mount the radio at this 

time.  Press 

Tamper 

switch to send a signal. 

b. Position the unit in the desired mounting location, 

with antenna oriented vertically.  The signal strength 

is displayed by the Green "Signal Strength LED" 

labeled "D3" (located at the lower right corner of the 

PC board).  The radio tower signal strength may 

fluctuate from day to day, therefore it is best to try to 

find a mounting location where the LED provides a 

minimum of 2 blinks

c.  Once a location has been selected based on signal 

coverage, permanently secure the unit using #8 

screws (not supplied) in the two mounting holes. 

 

 WARNING: 

 

To ensure user safety and to satisfy FCC 

RF exposure requirements, this unit must be installed so 

that a minimum separation distance of 60cm (24") is al-

ways maintained between the antenna of the transmitting 

device and nearby persons.   

 

STEP 3:  WIRING (PRIMARY MODE)

 

22-gauge wire may be used if mounted up to 50 feet from 

the control panel, and 18-gauge wire should be used for up 

to 100 feet.  Reference the wiring diagrams further in this 

manual.  See the section 

CONTROL PANEL PROGRAM-

MING

 further in this manual. 

 

For Primary Mode: 

The wiring between the control panel and the StarLink ra-

dio is over several wires, as follows: 

 



TB1:  PWR (+12V):

  Rated 12/24VDC input. 



TB2:  PWR GND (–)

 



TB21:  N/C OUT1:

  Wired to the (+) of a zone dedi-

cated to monitoring the radio status.  Should be pro-

grammed on Napco GEMC control panels as Monitor 

or Supervisory Zone.   



TELCO PRIMARY 

to FACP Telco 1 RJ-45 socket. 



TELCO SECONDARY 

to FACP Telco 2 RJ-45 socket. 

Содержание StarLink SLE-LTEVI Series

Страница 1: ...ential Fire alarm capture radio IP communicators are fully supervised wireless digital two way subscriber units All models are compatible with most 12 24VDC alarm control panels always adhere to the d...

Страница 2: ...Smart Channel input Active high input for wiring to the control panel bell output When this input detects a pulsing temporal 3 high it sends a Fire alarm a pulsing temporal 4 CO Alarm a CO alarm is se...

Страница 3: ...or wet contacts TB22 N O OUT2 Normally open Dry contact Form C relay TB23 C OUT2 Common Dry contact Form C relay Relay rated 30V AC DC 500mA TB24 N C OUT2 Normally closed Dry contact Form C relay LED...

Страница 4: ...ded on the premises then only 4 hours of UPS backup are required JUMPER DESCRIPTIONS Jumper block labeled X5 from top to bottom as detailed in the table below Note Contact ID is always available in re...

Страница 5: ...s STEP 2 SELECT A MOUNTING LOCATION The mounting location should be indoors within the protect ed area and selected based on RF performance It is HIGHLY recommended that the installer carefully adhere...

Страница 6: ...ly trouble output relay to the two terminals of the control panel zone dedicated to the trouble With the GEMC Commercial Fire control panels use the dry contacts of the Power Supply relay by removing...

Страница 7: ...apcoNOC com to enable Tip Ring Wiring Fault Report Refer to wiring diagram Supervision Time Schedule Considerations If a status change alarm trouble etc is transmitted the radio supervision timer is r...

Страница 8: ...8 StarLink SLE Commercial LTEVI LTEAI Series Dual Path Alarm Communicators Installation Instructions This page intentionally left blank...

Страница 9: ...ition maintain a minimum 1 4 separation of all primary wiring in the transformer compartment from the yellow secondary wires of the transformer Remove shunt J2 to isolate relay OUT1 common from ground...

Страница 10: ...C 20VA transformer Optional if not used connect 10K resistor between terminals 9 and 10 IN4 StarLink BATTERY RED BLACK 8 9 10 N C COM N O J2 Note Battery leads are not power limited 10k 10k 10k TELCO...

Страница 11: ...s 1 and 2 observing polarity 10k 12V or 24V AUX PWR 10k 10k Refer to section SUPPLYING POWER DO NOT USE EOLR EOLR J2 jumper off This connection only used with Power Supply SLE ULPS R These connections...

Страница 12: ...ol Panel PC Board Refer to section SUPPLYING POWER Not required if JP2 shunt is removed and FACP monitors TELCO 2 Program only TELCO 1 supervision Note Connect IN2 to a panel output used for identifyi...

Страница 13: ...telephone connections primary and secondary for supervision and central station reporting through the StarLink SLE LTEVI FIRE radio By removing the JP2 shunt and enabling the feature Tip Ring Wiring F...

Страница 14: ...that opening the enclosure door will cause a tamper alarm Wiring a normally closed sensor loop for tamper supervision wire to a zone on the control panel GEM Tamperkit consists of Description QTY SC2...

Страница 15: ...TRF12 T123 TRANSFORMER FOR CONNECTION TO SLE CHARGER BOARD UL LISTED SURFACE OR FLUSH MOUNT OUTLET BOX AND NON SWITCHED RECEPTACLE WALL TRANSFORMER SECONDARY WIRING CONDUIT LIMITED TO 20 FEET MAXIMUM...

Страница 16: ...ay not be compromised or circumvented or that the product or system will prevent any personal injury or property loss by burglary robbery fire or otherwise nor that the product or system will in all c...

Отзывы: