 SLE Commercial LTEVI & LTEAI Series Dual-Path Alarm Communicators -- Installation Instructions 



When processing an alarm, this LED will blink variably 

during each part of the process (dialing, handshaking, 

data transmission, etc.). 

 

  RED TROUBLE LED 

 Labeled "

D5

", this LED is located at the bottom right of 

the PC board.  Operation is as follows: 



1 Blink: 

 Low Aux Power input voltage 



2 Blinks: 

 Battery trouble 



3 Blinks:

  Alarm report Failed to Communicate (will 

restore only when the radio path is restored) 



4 Blinks:

  RF trouble (antenna connection or cellu-

lar registration)  



5 Blinks:

  Radio poll or check-in failure (radio and/or 

Ethernet).  Either or both paths will trigger the trouble, 

but for the trouble to clear, unit requires both IP and 

radio polling/checkins to be operational  



6 Blinks: 

 Unit disabled (reporting or control panel 

downloading not allowed)  



7 Blinks:

  Unit was shutdown and has no function-

ality; requires a restart (full power down and full power 

up sequence) to restore operation   



8 Blinks:

  Telco Line Cut 

 

  RED DIAGNOSTIC LED 

 Labeled 

"

D7

", this LED is located in the middle of the PC 

board.  One blink indicates a weak or non-existent signal 

from the network (green LED is off). If this red LED is 

blinking in any other manner, contact technical support.   

 

  GREEN IP NETWORK CONNECTION LED 

 Labeled 

"

D14

" (or 

DS14

), this LED is located to the right 

of the 

ETHERNET 

socket on the PC board.  Operation is 

as follows: 

 

Off 

= No network cable detected  

 

Fast Flash 

= No IP connection (Occurs just after pow-

er on, while trying to obtain a IP address)  

 

Slow Flash 

= Normal IP network operation  



1 Blink: 

 Static IP  



2 Blinks: 

 DHCP  



3 Blinks:

  Auto IP (If unable to acquire DHCP ad-

dress, then after 5 minutes it will convert to Auto IP  

relay.  Add shunt to lower two pins of JP1 for wet 

contacts.   

TB20: C OUT1:

  Common.  Dry contact Form C relay.  

Add shunt to lower two pins of JP1 for wet contacts 

(connects relay Common to system ground).  Relay 

rated 30V AC/DC, 500mA. 

TB21: N/C OUT1:

  Normally closed.  Dry contact Form 

C relay.  Add shunt to lower two pins of JP1 for wet 

contacts.   

TB22: N/O OUT2:

  Normally open.  Dry contact Form C 

relay. 

TB23: C OUT2:

  Common.  Dry contact Form C relay.  

Relay rated 30V AC/DC, 500mA. 

TB24: N/C OUT2:

  Normally closed.  Dry contact Form 

C relay.   

 

 

LED DESCRIPTIONS 

  The PC board contains several LED's, as follows: 

 

  GREEN RF SIGNAL STRENGTH LED

 

 Labeled 

"

D3

", this LED is located at the lower right corner 

of the PC board.   

 

Every 30 seconds, the StarLink radio receiver section 

turns on and listens to the cell tower.  Depending on the 

signal strength detected, it will blink the Signal Strength 

LED from 1 to 5 times, providing a signal strength indica-

tor that is updated constantly and is always displayed.  

 

 

 

Green LED Operation 

 

Signal strength (as received by the radio) is displayed by 

this LED blinking 1 to 5 times at a constant rate (with a 

short delay between blink cycles).  

Acceptable power lev-

el is greater than or equal to 2 blinks

.   

 

  YELLOW OPERATIONAL STATUS LED 

 Labeled "

D4

", this LED is located at the bottom right of 

the PC board.  Operation is as follows: 

 

  Normal Standby Condition: 



Blinks on momentarily every 10 seconds:  

Unit is in 

standby waiting for an alarm to report. 

  Processing Alarm Conditions: 

FIRE PROGRAMMING OPTION 

PERMITTED IN 

UL864? (Y/N) 

AVAILABLE SETTINGS 

REQUIRED UL 864  SETTINGS

 

Unattended Remote Downloading 

No 

Enable / Disable 

Disabled (Jumper 1 installed).  Also required for Commercial installations. 

 Note:

  

See page 7 "

Configuration Download / Firmware Updates

" for jumper instruc-

tions.   

IN2

 and 

IN3 

Unsupervised 

Yes 

Supervised / Unsupervised 

Unsupervised using conduit within 20 feet of FACP (default).  If not using conduit, 
install Jumpers 4 and 5 and EOL Resistors.  Inputs 2 an 3 can be unsupervised 
with jumpers 4 and 5 removed; IN4 and IN5 always require EOLR 

7 Day Supervision, Radio to NOC 

No 

200 seconds, 5 minutes, 6 

minutes, 60 minutes, 6 

hours, 7 days 

200 seconds, 5 minutes, 60 minutes.  6 Hours permitted in Commercial Fire UL 
864 with Dual Path enabled.   

Trouble on Radio or IP Path 

(Annunciate / Report)  

Yes 

Either Path or Both Paths  Either Path (annunciation and report of trouble) 

NOTICE TO AUTHORITIES HAVING JURISDICTION, USERS, INSTALLERS,  

DEALERS, AND OTHER AFFECTED PARTIES 

Wi-Fi Module 

Yes 

Enable / Disable 

May be enabled as a primary reporting path for Fire  

Содержание StarLink SLE-LTEVI Series

Страница 1: ...ential Fire alarm capture radio IP communicators are fully supervised wireless digital two way subscriber units All models are compatible with most 12 24VDC alarm control panels always adhere to the d...

Страница 2: ...Smart Channel input Active high input for wiring to the control panel bell output When this input detects a pulsing temporal 3 high it sends a Fire alarm a pulsing temporal 4 CO Alarm a CO alarm is se...

Страница 3: ...or wet contacts TB22 N O OUT2 Normally open Dry contact Form C relay TB23 C OUT2 Common Dry contact Form C relay Relay rated 30V AC DC 500mA TB24 N C OUT2 Normally closed Dry contact Form C relay LED...

Страница 4: ...ded on the premises then only 4 hours of UPS backup are required JUMPER DESCRIPTIONS Jumper block labeled X5 from top to bottom as detailed in the table below Note Contact ID is always available in re...

Страница 5: ...s STEP 2 SELECT A MOUNTING LOCATION The mounting location should be indoors within the protect ed area and selected based on RF performance It is HIGHLY recommended that the installer carefully adhere...

Страница 6: ...ly trouble output relay to the two terminals of the control panel zone dedicated to the trouble With the GEMC Commercial Fire control panels use the dry contacts of the Power Supply relay by removing...

Страница 7: ...apcoNOC com to enable Tip Ring Wiring Fault Report Refer to wiring diagram Supervision Time Schedule Considerations If a status change alarm trouble etc is transmitted the radio supervision timer is r...

Страница 8: ...8 StarLink SLE Commercial LTEVI LTEAI Series Dual Path Alarm Communicators Installation Instructions This page intentionally left blank...

Страница 9: ...ition maintain a minimum 1 4 separation of all primary wiring in the transformer compartment from the yellow secondary wires of the transformer Remove shunt J2 to isolate relay OUT1 common from ground...

Страница 10: ...C 20VA transformer Optional if not used connect 10K resistor between terminals 9 and 10 IN4 StarLink BATTERY RED BLACK 8 9 10 N C COM N O J2 Note Battery leads are not power limited 10k 10k 10k TELCO...

Страница 11: ...s 1 and 2 observing polarity 10k 12V or 24V AUX PWR 10k 10k Refer to section SUPPLYING POWER DO NOT USE EOLR EOLR J2 jumper off This connection only used with Power Supply SLE ULPS R These connections...

Страница 12: ...ol Panel PC Board Refer to section SUPPLYING POWER Not required if JP2 shunt is removed and FACP monitors TELCO 2 Program only TELCO 1 supervision Note Connect IN2 to a panel output used for identifyi...

Страница 13: ...telephone connections primary and secondary for supervision and central station reporting through the StarLink SLE LTEVI FIRE radio By removing the JP2 shunt and enabling the feature Tip Ring Wiring F...

Страница 14: ...that opening the enclosure door will cause a tamper alarm Wiring a normally closed sensor loop for tamper supervision wire to a zone on the control panel GEM Tamperkit consists of Description QTY SC2...

Страница 15: ...TRF12 T123 TRANSFORMER FOR CONNECTION TO SLE CHARGER BOARD UL LISTED SURFACE OR FLUSH MOUNT OUTLET BOX AND NON SWITCHED RECEPTACLE WALL TRANSFORMER SECONDARY WIRING CONDUIT LIMITED TO 20 FEET MAXIMUM...

Страница 16: ...ay not be compromised or circumvented or that the product or system will prevent any personal injury or property loss by burglary robbery fire or otherwise nor that the product or system will in all c...

Отзывы: