 SLE Commercial LTEVI & LTEAI Series Dual-Path Alarm Communicators -- Installation Instructions

 



Input Current: 200mA maximum 



Maximum Charging Current:  200mA 

 

  Electrical Ratings for +12V / 24V  

  For Models without Power Supply

 



Input Voltage:  10-25VDC regulated (power-limited out-

put from Listed control panel).   



Input Current:  

10VDC standby:  162mA 

12VDC standby:  125mA 

15VDC standby:  110mA 

24VDC standby:  100mA (Commercial Fire models) 

25VDC standby:  100mA (Commercial Fire models) 

Wi-Fi Module: 

 (Optional) Add 40mA to the above. 

(With peak RF transmission current of 325mA).   

 

  Electrical Ratings for the IN 1 Fire Input: 



Input Voltage:  9-25VDC.   



Maximum Input Current:  Up to 2mA from FACP NAC 

circuit 

 

  Electrical Ratings for IN 2, IN 3, IN 4, and IN 5: 

 (Inputs 

IN 2, IN 3, IN 4, and IN 5 are 

Class B) 



Maximum Loop Voltage:  25VDC.   



Maximum Loop Current:  1.2mA 



End of Line Resistor (EOLR) Value:  10K (2 req'd) 

 

  Electrical Ratings for PGM3 Output: 



Open Collector Output:  Maximum Voltage 3V when 

active; 25V maximum when not active.   



Maximum PGM Sink Current:  50mA (up to 15VDC), 

25mA (15.1VDC - 25VDC) 

 

  Physical (W x H x D) 



Metal Housing:  11½ x 9½ x 3½" (29.2 x 24.1 x 8.9cm) 



Mounting:  Metal housing includes two keyhole slots for 

wall mounting (see measurements on page 7)   

 

 Environmental 



Operating Temperature:  0°C - 49°C (32°F - 120°F)  



Humidity:  Maximum 93% Non-Condensing 



Indoor / dry location use only 

 

 

TERMINAL DESCRIPTIONS 

Configure all inputs and outputs using the Management 

Center screen (located at 

www.NapcoNOC.com

).  Located 

at the bottom of the StarLink radio PC board, the 17 termi-

nals are described as follows: 

 

TB1:  PWR (+10 - 25VDC)

     

 

(Refer to section "

STEP 4:  APPLY POWER

") 

TB2:  PWR GND (–)

 

 

(Refer to section "

STEP 4:  APPLY POWER

") 

TB3: PGM3 

(–):

  Open collector output.  PGM3 is normally 

on (active low).  When it is triggered (for example, a 

trouble is detected) it becomes open collector/high.  

To have a zone dedicated to an StarLink radio trou-

ble, insert one side of the end of line resistor into this 

PGM3 terminal, and wire the other side of the resis-

tor to the positive terminal of the zone.   

TB4:  IN 1 (+):

  Smart Channel input.  Active high input 

for wiring to the control panel bell output.  When this 

input detects a pulsing temporal 3 high, it sends a 

Fire alarm; a pulsing temporal 4 (CO Alarm), a CO 

alarm is sent.  When used, these conductors must 

be run in conduit (max 20 feet for Commercial Fire, 

and 3 feet for Residential Fire).  For this input to re-

port to a central station, the StarLink radio must be 

configured with the central station telephone number 

and correct reporting formats and codes.  For more 

information, see WI2140 located at 

www.NapcoNOC.com

.   

TB5:  IN 2 (+):

  Fire Trouble input**.  Wire to FACP trou-

ble relay N/O with parallel 10K EOLR at FACP. 

 

Note: 

 Inputs 

IN 2

IN 3

IN 4

 and 

IN 5

 can be su-

pervised end-of-line resistor inputs that can be trig-

gered with N/O or N/C relay contacts.    

TB6:  IN 2 (–):

  See 

TB5

, above. 

TB7:  IN 3 (+):

  Fire Alarm input**.  Wire to FACP Fire 

Alarm relay N/O with parallel 10K EOLR at FACP. 

TB8:  IN 3 (–):

  See 

TB5

 and 

TB7

, above. 

 

Secondary Telephone:

  RJ-45 socket for FACP DACT 

connection.

 

 

Primary Telephone:

  RJ-45 socket for FACP DACT con-

nection.

 

 

TB9: IN 4 (+):

  Supervisory Alarm input**.  Wire to 

FACP Supervisory relay N/O with parallel 10K EOLR 

at FACP. 

TB10:  IN 4 (–):

  See 

TB5

 and 

TB9

, above. 

TB11: IN 5 (+):

  Water Flow Alarm input**.  Wire to FACP 

Water Flow relay with parallel 10K EOLR at FACP. 

TB12:  IN 5 (–):

  See 

TB5

 and 

TB11

, above. 

TB13: GND:

  Earth ground terminal. 

 

Ethernet:

  Connect the SLE Dual-Path radio communica-

tor to your broadband modem, router or switch.  

Note:

 The cable modem/router and switch (if any) 

at the premises requires standby power, therefore a 

UL 1481 / UL 864 or UL Listed ITE (

Information 

Technology Equipment

) UPS must be used at the 

premises to power these devices for a minimum of 

24 hours.   

 

TB19: N/O OUT1:

  Normally open.  Dry contact Form C 

For Commercial Fire installations, a UL Listed Fire Alarm regulated power supply or FACP regulated auxiliary output is required. 

*Reverse polarity / energized state. 

**Factory programmed options; may be changed at the NOC website (

www.NapcoNOC.com

). 

Supervised Fire Input Wiring Option

 

10K

 

10K

 

C

 

C

 

N/O

 

Alarm

 

N/O

 

TBL*

 

To StarLink 

Terminals 

IN2 (TB5)  

-or- 

IN3 (TB7)

 

Radio GND 

(TB6 and 

TB88)

 

 

The EOLR must be installed and located within the control panel housing.

 

(Radio) 

 

(Alarm Panel)

 

5  7 

-or- 

N/C

 

6  8 

-or- 

N/C

 

Содержание StarLink SLE-LTEVI Series

Страница 1: ...ential Fire alarm capture radio IP communicators are fully supervised wireless digital two way subscriber units All models are compatible with most 12 24VDC alarm control panels always adhere to the d...

Страница 2: ...Smart Channel input Active high input for wiring to the control panel bell output When this input detects a pulsing temporal 3 high it sends a Fire alarm a pulsing temporal 4 CO Alarm a CO alarm is se...

Страница 3: ...or wet contacts TB22 N O OUT2 Normally open Dry contact Form C relay TB23 C OUT2 Common Dry contact Form C relay Relay rated 30V AC DC 500mA TB24 N C OUT2 Normally closed Dry contact Form C relay LED...

Страница 4: ...ded on the premises then only 4 hours of UPS backup are required JUMPER DESCRIPTIONS Jumper block labeled X5 from top to bottom as detailed in the table below Note Contact ID is always available in re...

Страница 5: ...s STEP 2 SELECT A MOUNTING LOCATION The mounting location should be indoors within the protect ed area and selected based on RF performance It is HIGHLY recommended that the installer carefully adhere...

Страница 6: ...ly trouble output relay to the two terminals of the control panel zone dedicated to the trouble With the GEMC Commercial Fire control panels use the dry contacts of the Power Supply relay by removing...

Страница 7: ...apcoNOC com to enable Tip Ring Wiring Fault Report Refer to wiring diagram Supervision Time Schedule Considerations If a status change alarm trouble etc is transmitted the radio supervision timer is r...

Страница 8: ...8 StarLink SLE Commercial LTEVI LTEAI Series Dual Path Alarm Communicators Installation Instructions This page intentionally left blank...

Страница 9: ...ition maintain a minimum 1 4 separation of all primary wiring in the transformer compartment from the yellow secondary wires of the transformer Remove shunt J2 to isolate relay OUT1 common from ground...

Страница 10: ...C 20VA transformer Optional if not used connect 10K resistor between terminals 9 and 10 IN4 StarLink BATTERY RED BLACK 8 9 10 N C COM N O J2 Note Battery leads are not power limited 10k 10k 10k TELCO...

Страница 11: ...s 1 and 2 observing polarity 10k 12V or 24V AUX PWR 10k 10k Refer to section SUPPLYING POWER DO NOT USE EOLR EOLR J2 jumper off This connection only used with Power Supply SLE ULPS R These connections...

Страница 12: ...ol Panel PC Board Refer to section SUPPLYING POWER Not required if JP2 shunt is removed and FACP monitors TELCO 2 Program only TELCO 1 supervision Note Connect IN2 to a panel output used for identifyi...

Страница 13: ...telephone connections primary and secondary for supervision and central station reporting through the StarLink SLE LTEVI FIRE radio By removing the JP2 shunt and enabling the feature Tip Ring Wiring F...

Страница 14: ...that opening the enclosure door will cause a tamper alarm Wiring a normally closed sensor loop for tamper supervision wire to a zone on the control panel GEM Tamperkit consists of Description QTY SC2...

Страница 15: ...TRF12 T123 TRANSFORMER FOR CONNECTION TO SLE CHARGER BOARD UL LISTED SURFACE OR FLUSH MOUNT OUTLET BOX AND NON SWITCHED RECEPTACLE WALL TRANSFORMER SECONDARY WIRING CONDUIT LIMITED TO 20 FEET MAXIMUM...

Страница 16: ...ay not be compromised or circumvented or that the product or system will prevent any personal injury or property loss by burglary robbery fire or otherwise nor that the product or system will in all c...

Отзывы: