 SLE Commercial LTEVI & LTEAI Series Dual-Path Alarm Communicators -- Installation Instructions

 

Wiring Diagram for Generic FACPs 

with TELCO RJ Sockets 

 

F A C P     P C   B O A R D  

(CONTROL PANEL HOUSING) 

Refer to section "

SUPPLYING POWER

". 

TELCO RJ SOCKET (SECONDARY) 

Optional:

  When Power Supply 

SLE-ULPS-R is not used, connect 

FACP Aux Power or Listed power 

supply (+12V or +24V) to StarLink 

terminals 1 and 2 (observing 

polarity) 

(

+

) (

+12V or +24V 

AUX PWR 

(STARLINK RADIO HOUSING) 

StarLink Radio Terminals

 

PC Board:  All connections are power limited except AC Mains and battery terminals.   

LOCAL 

DOWNLOAD  

TELCO  

SECONDARY 

TELCO  

PRIMARY 

ETHERNET 

(+) 

(

POWER  PGM3 

IN1 

IN2 

IN3 

(

(+) 

(+) 

(

(

(+) 

(+) 

10 

(

12 

(

11 

(

+

13 

EGND 

19 

N/O 

21 

N/C 

20 

IN4 

IN5 

OUT1 

22  N/

C

 

24  N/

O

 

23  C 

OU

T2

 

Power Supply (SLE-ULPS-R)  

Either the 

TRF12/

T123 (16.5V / 

20VA) transformer 

or the chassis-

mounted 16.5VAC / 

20VA transformer 

Optional; if not used, connect 10K 

resistor between terminals 9 and 

10 (IN4) 

StarLink 

BATTERY 

(+) 

 RED 

(–) 

BLACK 

10

 

N/C 

COM

 N/O 

J2 

Note:  Battery 

leads are not 

power limited 

10k

 

10k

 

10k

 

TELCO RJ SOCKET (PRIMARY) 

EOLR 

(

J2

 jumper off) 

(This connection only used with 

Power Supply SLE-ULPS-R) 

The feature "

Tip/Ring 

Wiring Fault Report

"   is 

required for supervision. 

Requires all 8 wires in 

the RJ-45 cable 

JP1 

Shunt 

JP1

 on 

bottom 2 pins 

when using the 

SLE-ULPS-R 

Shunt on top 2 

pins when NOT 

using the 

SLE-

ULPS-R

 

(These connections 

only used without 

Power Supply) 

EOLR 

JP2 

Remove shunt 

on 

JP2

 to enable 

TELCO 2 trouble 

*

Not required if 

JP2

 shunt is removed and FACP monitors TELCO 2. 

To FACP Zone 

Dedicated to Radio 

Trouble

*

 

When using 

JP2 

option (monitoring Telco 2) with power supply wire:  

1.  Move Power Supply 

IN1 

from Radio 

OUT1 

terminal 21 to power 

supply terminal 4 (-). 

2.  Do not wire power supply trouble relay to FACP zone. 
3.  Wire power supply terminal in series with 10K EOLR to Radio 

IN4 

(+). 

4. Program 

IN4 

to report power supply trouble. 

Содержание StarLink SLE-LTEVI Series

Страница 1: ...ential Fire alarm capture radio IP communicators are fully supervised wireless digital two way subscriber units All models are compatible with most 12 24VDC alarm control panels always adhere to the d...

Страница 2: ...Smart Channel input Active high input for wiring to the control panel bell output When this input detects a pulsing temporal 3 high it sends a Fire alarm a pulsing temporal 4 CO Alarm a CO alarm is se...

Страница 3: ...or wet contacts TB22 N O OUT2 Normally open Dry contact Form C relay TB23 C OUT2 Common Dry contact Form C relay Relay rated 30V AC DC 500mA TB24 N C OUT2 Normally closed Dry contact Form C relay LED...

Страница 4: ...ded on the premises then only 4 hours of UPS backup are required JUMPER DESCRIPTIONS Jumper block labeled X5 from top to bottom as detailed in the table below Note Contact ID is always available in re...

Страница 5: ...s STEP 2 SELECT A MOUNTING LOCATION The mounting location should be indoors within the protect ed area and selected based on RF performance It is HIGHLY recommended that the installer carefully adhere...

Страница 6: ...ly trouble output relay to the two terminals of the control panel zone dedicated to the trouble With the GEMC Commercial Fire control panels use the dry contacts of the Power Supply relay by removing...

Страница 7: ...apcoNOC com to enable Tip Ring Wiring Fault Report Refer to wiring diagram Supervision Time Schedule Considerations If a status change alarm trouble etc is transmitted the radio supervision timer is r...

Страница 8: ...8 StarLink SLE Commercial LTEVI LTEAI Series Dual Path Alarm Communicators Installation Instructions This page intentionally left blank...

Страница 9: ...ition maintain a minimum 1 4 separation of all primary wiring in the transformer compartment from the yellow secondary wires of the transformer Remove shunt J2 to isolate relay OUT1 common from ground...

Страница 10: ...C 20VA transformer Optional if not used connect 10K resistor between terminals 9 and 10 IN4 StarLink BATTERY RED BLACK 8 9 10 N C COM N O J2 Note Battery leads are not power limited 10k 10k 10k TELCO...

Страница 11: ...s 1 and 2 observing polarity 10k 12V or 24V AUX PWR 10k 10k Refer to section SUPPLYING POWER DO NOT USE EOLR EOLR J2 jumper off This connection only used with Power Supply SLE ULPS R These connections...

Страница 12: ...ol Panel PC Board Refer to section SUPPLYING POWER Not required if JP2 shunt is removed and FACP monitors TELCO 2 Program only TELCO 1 supervision Note Connect IN2 to a panel output used for identifyi...

Страница 13: ...telephone connections primary and secondary for supervision and central station reporting through the StarLink SLE LTEVI FIRE radio By removing the JP2 shunt and enabling the feature Tip Ring Wiring F...

Страница 14: ...that opening the enclosure door will cause a tamper alarm Wiring a normally closed sensor loop for tamper supervision wire to a zone on the control panel GEM Tamperkit consists of Description QTY SC2...

Страница 15: ...TRF12 T123 TRANSFORMER FOR CONNECTION TO SLE CHARGER BOARD UL LISTED SURFACE OR FLUSH MOUNT OUTLET BOX AND NON SWITCHED RECEPTACLE WALL TRANSFORMER SECONDARY WIRING CONDUIT LIMITED TO 20 FEET MAXIMUM...

Страница 16: ...ay not be compromised or circumvented or that the product or system will prevent any personal injury or property loss by burglary robbery fire or otherwise nor that the product or system will in all c...

Отзывы: