StarLink
™
SLE-LTEVI-FIRE & SLE-LTEAI-FIRE Commercial Series Dual-Path Alarm Communicators -- Installation Instructions
7
ble signal shall be sent to Central Station within 5
minutes of failure by the remained active channel.
d. Reliability of the signal shall be achieved by any of the
following:
Signal repetition - multiple transmissions repeating
the same signal
Parity check - a mathematically check sum algorithm
of a digital message that verifies correlation between
transmitted and received message
An equivalent means that provides a certainty of
99.99 percent that the received message is identical
to the transmitted message
e. The maximum duration between the initiation of an
alarm signal at the protected premises, transmission of
the signal, and subsequent display and recording of
the alarm signal at the Central Station shall not exceed
90 seconds
f. A spare Central Station Receiver shall be provided at
the Central Station and shall be able to be switched
into the place of a failed unit within 30 seconds after
detection of failure
g. All applicable requirements of Federal Communica-
tions Commission (FCC) shall be complied with.
3. When used DACT for Central Station communication, two
means of communication are required. The primary
channel shall be telephone line. Cellular or internet com-
munication shall be limited for the secondary means of
communication and comply with 26.6.3 NFPA 72, 2010
edition. Another telephone line also may be used as sec-
ondary mean of communication.
4. The above-referenced equipment shall be used only with
listed fire alarm control panels and devices, with which
the compatibility has been determined by UL Listing Re-
port
5. Only enclosures painted red in color shall be used.
6. Underwriters Laboratories Inc.'s listing requirements and
limitations shall be complied with.
on site during any reprogramming of the radio or control
panel and must perform / re-perform acceptance testing.
To perform a download or update the radio firmware, jump-
er 1 must be removed. UL requires that the jumper be re-
placed after the download is complete.
Failure to replace
the jumper would allow downloads to the radio without
a technician on-site
.
For Residential installations jumper 1 may be removed to
permit uploading and downloading without a technician on
site, however, the dealer is responsible for ensuring the
system is operating correctly after any downloads or
changes to the system.
NYC Fire Department Requirements
1. All uses, configurations, arrangements and functions, appli-
cations and installations shall comply with the provisions of
New York City Construction Codes, specifically Building
Code Chapter 9 & 1RCNY §3616-04. Further, the installa-
tion shall be in accordance with applicable provisions of
New York City Fire Code, New York City Electrical Code,
manufacturer's installation requirements, and UL Standard
864.
2. When used Dual Path LTE Communicator (IP and Cellular)
for Central Station communication both primary and sec-
ondary channels of communication shall be required and
shall meet the conditions of 4.1 – 4.7. IP communication
shall be used as primary channel of communication with
Central Station and Cellular Communicator shall be used
as the secondary channel of communication or in reverse
order: Cellular Communicator as primary and Internet con-
nection as the secondary channel.
a. Each communication channel shall be monitored for
integrity at intervals not exceeding 24 hours.
b. Failure any channel of communication shall be annunci-
ated at the protected premises within 5 minutes of fail-
ure.
c. When any channel of communication has failed, a trou-