 SLE-LTEVI-FIRE & SLE-LTEAI-FIRE Commercial Series Dual-Path Alarm Communicators -- Installation Instructions 

 

SLE-LTEVI-FIRE 

SLE-LTEAI-FIRE

 - Commercial / Resi-

dential  Fire  LTE  Network  Compatible  alarm  capture 

Communicator.  SIM card included.  Red plastic enclo-

sure.  Rated nominal 12/24VDC input. 

 

ADDITIONAL COMPONENTS 

  In  addition  to  the 

SLE-LTEVI-FIRE

  and 

SLE-LTEAI-FIRE

 

listed above, the following sub-assemblies are available: 

SLE-WIFI-MODULE

 - Allows your Napco StarLink

 device 

to connect to the Internet by means of a wireless (Wi-Fi) 

link,  eliminating  a  wired  Ethernet  cable  connection.  

Note:

    7AH  battery  required  when  using  the 

SLE-

WIFI-MODULE

.  For more information, see WI2191. 

SLE-DLCBL

 - Download Cable, 6 feet. 

SLE-ANTEXT30

 - Extended antenna with 30 feet of cable 

SLE-ANTEXT50

 - Extended antenna with 50 feet of cable 

SLE-ANTEXT75

 - Extended antenna with 75 feet of cable 

SLE-ANTEXT100

 - Extended antenna with 100 feet of cable 

  (Any  suitable  external  cellular  antenna  is  permitted  by 

UL).    Always  follow  the  manufacturer's  installation  in-

structions.  

Note:

  Antennas are not Listed by UL.    

 
 

SPECIFICATIONS

 

  Electrical Ratings for +12V / 24V (powered by the con-

trol panel)* 

 

Input Voltage:  10-25VDC regulated (power-limited out-

put from Listed control panel Aux/Remote Fire Power).   

 

Input Current:  

10VDC standby:  162mA 

12VDC standby:  125mA 

15VDC standby:  110mA 

24VDC standby:  100mA 

25VDC standby:  100mA 

Wi-Fi Module: 

 (Optional) Add 40mA to the above.   

(With peak RF transmission current of 325mA).   

 

  Electrical Ratings for the IN 1 Fire Input: 

 

Input Voltage:  9-25VDC.   

 

Maximum  Input  Current:    Up  to  2mA  from  FACP  NAC 

circuit 

 

  Electrical Ratings for IN 2, IN 3, IN 4, and IN 5: 

  (Inputs 

IN 2, IN 3, IN 4, and IN 5 are 

Class B) 

 

Maximum Loop Voltage:  25VDC input. 

 

Maximum Loop Current:  1.7mA 

WI2326E.bLF  11/20 

R

333 Bayview Avenue, Amityville, New York 11701 

For Sales and Repairs, (800) 645-9445 

For Technical Service, (800) 645-9440 or visit us at 

http://tech.napcosecurity.com/ 

(Note:  Technical Service is for security professionals only)

 

Publicly traded on NASDAQ      Symbol: NSSC 

© NAPCO 2020 

INTRODUCTION 

  The 

SLE-LTEVI-FIRE

  and 

SLE-LTEAI-FIRE

 

Dual-Path 

Alarm Communicators 

are specifically designed to interface 

with FACP (Fire Alarm Control Panels) and to comply with 

UL  864.    The  communicators  are  equipped  with  two  dry 

relays, one for a trouble output and one for an auxiliary out-

put.    The  units  are  also  equipped  with  four  supervised  in-

puts  to  report  a  Fire  Alarm,  a  Fire  Trouble,  a  Water  Flow 

Alarm  and  a  Supervisory  Alarm,  each  triggered  from  the  

N/O and Common terminals of the associated FACP output 

relays.    These  communicators  are  for  use  as  the  primary 

means of communication with the central station and do not 

have  backup  mode  capability.    Dual  Path  Communicators 

can also be utilized as a Sole Path Cell Communicator.  No 

POTS (Telco Line) connection permitted.   

  When connected to a FACP with one or two standard RJ-

45 telephone inputs, the 

SLE-LTEVI-FIRE

 and 

SLE-LTEAI

-FIRE

 provide two RJ-45 outputs to satisfy both telephone 

inputs.  The primary RJ-45 output is supervised and reports 

a trouble  to the central station upon any open or short on 

the  primary  RJ-45  wires  that  prevent  reporting.    The  sec-

ondary telephone line is supervised by the FACP; when a 

line  fault  is  detected,  a  trouble  is  reported  to  the  central 

station through the primary telephone line.   

  The 

SLE-LTEVI-FIRE

 and 

SLE-LTEAI-FIRE

 are compati-

ble  with  most  12  or  24VDC  alarm  control  panels  (always 

adhere to the documentation provided by the control panel 

manufacturer).    Mount  to  a  single-,  dual-,  or  three-gang 

electrical box and route the wires through the back knock-

out(s), or as specified by local codes.  

See WI2140 for pro-

gramming information.  

 

  The 

SLE-LTEVI-FIRE

 and 

SLE-LTEAI-FIRE

 communica-

tors use proprietary data-capture technology that captures 

the  alarm  report  from  the  control  panel  and  transmits  the 

alarm signals to the SLE Control Center; the alarm signals 

are then forwarded to ANY central station via Contact ID or 

4/2  via  DACT  from  the  NOC  or  Sur-Gard  System  II,  Sur-

Gard  System  V,  Bosch  D6100IPV6  or  Bosch  D6600  Re-

ceiver (with ITS-D6686 Ethernet Adapter) via TCP/IP using 

standard  line  security.    The  SLE  Control  Center  reports  a 

trouble  signal  in  the  event  that  the  network  does  not  re-

ceive  the  expected  supervision  signal  from  the  wireless 

communicator.  In addition, the 

SLE-LTEVI-FIRE

 and 

SLE-

LTEAI-FIRE

  are  powered  directly  from  the  control  

panel.   

Note:

    UL  Listed  for  UL  1076  APOU  Proprietary 

Alarm  Systems  and  UL  365  APAW  Police  Connect  when 

reporting to a UL Listed Central Station Receiver Listed for 

UL  1076  APOU  Proprietary  Alarm  Systems  or  UL  365 

APAW  Police  Connect,  respectively.    For  TCP/IP  only 

Bosch D6600 or D6100IPV6 for UL1076 and UL365 appli-

cations. 

 

StarLink™ Commercial  

SLE-LTEVI-FIRE & SLE-LTEAI-FIRE  

Dual-Path Alarm Communicators  

INSTALLATION INSTRUCTIONS 

*For Commercial Fire installations, a UL Listed Fire Alarm regulated power 

supply or FACP regulated auxiliary output is required. 

AGENCY LISTINGS 

 

UL 864 Standard For Control Units and Accessories For Fire Alarm 
Systems, 10th Edition 

 

UL 1610 Standard For Central-Station Burglar-Alarm Units 

 

UL 985 Standard For Household Fire Warning System Units 

 

UL 1023 Standard For Household Burglar-Alarm System Units 

 

UL 1076 APOU Proprietary Alarm Systems 

 

UL 365 APAW Police Connect 

 

NYC Fire Dept. Certificate of Approval #6317 & 6318  

Содержание StarLink SLE-LTEVI-FIRE

Страница 1: ...icators are for use as the primary means of communication with the central station and do not have backup mode capability Dual Path Communicators can also be utilized as a Sole Path Cell Communicator...

Страница 2: ...acts TB6 IN 2 See TB5 above TB7 IN 3 Fire Alarm input Wire to FACP Fire Alarm relay N O with parallel 10K EOLR at FACP TB8 IN 3 See TB5 and TB7 above Secondary Telephone RJ 45 socket for FACP DACT con...

Страница 3: ...is blinking in any other manner please contact technical support GREEN IP NETWORK CONNECTION LED Labeled D14 or DS14 this LED is located to the right of the ETHERNET socket on the PC board Operation i...

Страница 4: ...ed at the lower right corner of the PC board The radio tower signal strength may fluctuate from day to day therefore it is best to try to find a mounting location where the LED pro vides a minimum of...

Страница 5: ...AT THE NOC NOC Originated Alarms Contact ID Event Data Sent Pulse Format Event Code Sent Initiated By Comments Supervisory Fail E356 A00 Zn000 99 Automatically by NOC if fail to receive any signal fr...

Страница 6: ...ext regular supervision transmission will occur at the interval deter mined by your rate plan Configuration Download Firmware Updates Technician on site required For Commercial Installations a technic...

Страница 7: ...olor shall be used 6 Underwriters Laboratories Inc s listing requirements and limitations shall be complied with on site during any reprogramming of the radio or control panel and must perform re perf...

Страница 8: ...connections are power limited except AC Mains and battery terminals JP1 Shunt JP1 on top 2 pins Optional Use 12 or 24VDC Listed regulated power supply Note Common radio ground and FACP ground GREEN RE...

Страница 9: ...io STARLINK RADIO HOUSING StarLink Radio Terminals PC Board All connections are power limited except AC Mains and battery terminals Optional Use 12 or 24VDC Listed regulated power supply Note Common r...

Страница 10: ...ry terminals JP1 Shunt JP1 on top 2 pins Wiring Diagram for FACP Relay Trigger Input Reporting Refer to section SUPPLYING POWER NC NORMALLY ENERGIZED FIRE TROUBLE RELAY C NO 10k Aux Power Regulated 12...

Страница 11: ...d and FACP monitors TELCO 2 Program only TELCO 1 supervision Note Connect IN2 to a panel output used for identifying Telco line cut this is the DACT interconnect wiring to the radio PC Board All conne...

Страница 12: ...12 StarLink SLE LTEVI FIRE SLE LTEAI FIRE Commercial Series Dual Path Alarm Communicators Installation Instructions This page intentionally left blank...

Страница 13: ...StarLink SLE LTEVI FIRE SLE LTEAI FIRE Commercial Series Dual Path Alarm Communicators Installation Instructions 13 Housing Template 1 1 Scale Three Gang Mounting Double Gang...

Страница 14: ...14 StarLink SLE LTEVI FIRE SLE LTEAI FIRE Commercial Series Dual Path Alarm Communicators Installation Instructions This page intentionally left blank...

Страница 15: ...and firmly secure the conductors to the pigtail using an ap propriate wire nut or crimp connector for the num ber and gauge of conductors used IMPORTANT WIRING METHODS Incorrect Correct Use pigtail a...

Страница 16: ...ncelled NAPCO neither assumes nor authorizes any other person purporting to act on its behalf to modify to change or to assume for it any other warranty or liability concerning its products In no even...

Отзывы: