NAPCO Security Systems

 

GEM-P1632 Installation Instructions

WI808B 8/98

Page 21

This section provides a brief overview of system operation. For detailed operation, refer to the User's Guide fur-

nished with the keypad (OI234 for the GEM-RP1CAe2; OI192 for the GEM-RP2ASe2) and to the Keypad Programming
Modes at the end of this manual. NOTE: Keypad displays shown in this text are for the GEM-RP1CAe2 keypad. GEM-
RP2ASe2 displays will be similar, although abbreviated, and will scroll automatically.

"#

(Refer to the GEM-P1632 Programming Instructions (WI897) for a detailed explanation of programming.) Up to 32
personal user codes may be programmed at the keypad. NOTE: The Area Options associated with each User Code may
only be programmed in the Dealer Program Mode.

Default User Code.

The first code programmed should replace the default (User 01) code, “U01 123 • • • - • • - • • ”, (1,2,3), which should

not be selected as a user code.

Each user should be assigned his own dissimilar code and should be cautioned against divulging his code to anyone

else. Thus should it become necessary to remove a user from the system, that one code may be cancelled without af-
fecting other codes, and that user would then be prevented from entry. NOTE: Napco's PCD3000 Quickloader Software
provides enabling and disabling User Codes at programmed times using the scheduling menus. Ambush code should
not contain digits used as the first digits of any user code.

Changing or Canceling a Code

To change any code, merely program over the existing code as described in the Programming Instructions. Similarly, to
cancel a code, blank out each number of the code.

Arm/Disarm Code (Programmable in Dealer Program Mode only)

An Arm/Disarm Code may be used to arm/disarm the area in which it is programmed. Up to 6 digits may be programmed
or it may be programmed as a two-digit code for the purposes of quick arming.

Arm-Only Code (Programmable in Dealer Program Mode only)

An Arm-Only Code may only be used to arm the area in which it is programmed; it never has any disarm capability. Up to
6 digits may be programmed or it may be programmed as a two-digit code for the purposes of quick arming.

Service Code (Programmable in Dealer Program Mode only)

A Service Code is an Arm/Disarm Code that is easily activated when needed, and dormant at other times. Intended for the
occasional or temporary user (maid, repairman, etc.) who would otherwise be denied access to the premises. It is
activated by arming with it; an “S” will appear in the display (GEM-RP1CAe2 only) after the exit-delay countdown,
indicating that a Service Code has been activated. It may then be used to arm and disarm just as any other User Code.
Service code can be armed/disarmed from a disarmed state, but it cannot be armed/disarmed from an armed state, after
another user code has been entered.

Access Code

The Access Code will trip the panel's PGM2 Output Relay while disarmed if “Access Control on PGM2 Output” and
“PGM2 Output Access Control Time” is programmed. The Access Code is programmed as any other User Code but
without arm/disarm capability. 

Caution: 

Do not use the same code as any Arm/Disarm Code. Note: These systems have

not been investigated by UL for compliance with UL294 (Access Control Systems).

Ambush Code

The Ambush Code is a two-digit code entered by the user just prior to disarming, typically to cause a silent report to be
sent to the central station. Thus, should the user be forced to disarm by an assailant, he can silently signal an emergency
while appearing to be merely disarming the panel. (Check the glossary for programming required to enable this feature.)
Ambush Code should not contain digits used as the first two digits of any user code.

BA

SIC OPERA

T

ION

R

    

ARM

E D

STA

TU

S

 

   

 

 





NEXT/YES

PRIO R/NO

ARE A

Содержание Gemini P1632

Страница 1: ...WI808B 8 98 Napco 1998 R HARDWIRE WIRELESS...

Страница 2: ...ity Systems Inc 333 Bayview Avenue Amityville New York 11701 For Sales and Repairs call toll free 800 645 9445 For direct line to Technical Service call toll free 800 645 9440 Internet http www napcos...

Страница 3: ...17 KEYPAD CONFIGURATION MODE 18 Keypad Installation 18 Configuring the Keypads 18 BASIC OPERATION 21 User Codes Zone Descriptions 21 Arming and Disarming the System 22 Bypassing Zones 24 Alarm Indica...

Страница 4: ...may be quickly and easily downloaded to the control panel using a PC compatible computer with Napco s PCD3000 Quickloader software and PCI2000 computer interface Or the panel may be programmed using...

Страница 5: ...tary dial and TouchTone TM with Rotary backup Three 20 digit telephone numbers Backup Reporting Double Reporting Split Reporting 32 User Codes with Opening Closing Reporting by user AC Failure Reporti...

Страница 6: ...IAL FIRE 16 5VAC TRANSFORMER BATTERY 12 VDC STANDBY CURRENT ALARM CURRENT STANDBY TIME 40VA 50VA 7 AH 120 mA 520 mA 1 24 Hours 40VA 50VA Two 7 AH 360 mA 280 mA 1 24 Hours 20VA 7 AH 120 mA 360 mA 1 24...

Страница 7: ...78 Line Reversal Module PS3002 Power Supply Module 13 2Vdc 1 9A EOL2 2K End of Line Resistor Assy 2 2kW for Fire Circuit FT2200 End of Line Relay Resistor Supervisory Module RB1000 Relay Board RBATH1...

Страница 8: ...anic connect only to UL listed holdup devices All zones must be programmed for Priority Do not program any zones for Keyswitch Arming System must be serviced at least once every 3 years Residential Fi...

Страница 9: ...es for the machine screws it may be discarded after use Keypad A keypad should be located near each exit entry door The keypad features a handy pull up reference label Before mounting the keypad onto...

Страница 10: ...tility room furnace room and hallways Heat detec tors rather than smoke detectors are recommended in kitchens attics and garages due to conditions that may result in false alarms and improper operatio...

Страница 11: ...Range Wireless System The RM3008 may be used to interface the GEM P1632M control panel to the Ademco 7720 transmitter in order to meet UL Central Station Grade A or Grade B requirements by using a dig...

Страница 12: ...transmitters proceed as follows Note Wireless systems have not been investigated by UL 1 Enter the Fault Find Mode 2 Fault a point of the transmitter to be tested by opening the loop If the signal st...

Страница 13: ...e connected When connecting a mechanical bell it must be supervised using a 2 2k Ohm resistor To connect 8 Ohm Speakers use a Siren Driver with the proper polarity observed NOTE Refer to the GEM P1632...

Страница 14: ...ted if the longest cable run from the panel to the farthest keypad daisy chained or home run is less than 1000 feet The maximum distance for seven keypads is 300 feet using 22 AWG wire NOTE When runni...

Страница 15: ...the use of EZM Modules To do so simply select EZ Zone Doubling in programming refer to the GEM P1632 Programming Instructions and connect zones as shown above NOTE If both zones in a zone pair configu...

Страница 16: ...ire smoke detectors are connected to zones 7 8 If Fire Alarm Verification is desired to reset the smoke detectors select this option for the desired fire zone zone 7 or 8 WIRING CONNECTIONS 4 WIRE SMO...

Страница 17: ...nto an approved USOCRJ31X jack or a CA31A jack for Canadian installations The Telco Line is used by the control panel to dial the central station and for downloading This line should not be connected...

Страница 18: ...er e EZM address and f zone response To enter the GEM RP1CAe2 Configuration Mode 1 Move jumper JP1 located at the upper right corner of the control panel board from Pins 1 2 top two to Pins 2 3 bottom...

Страница 19: ...to continue or press the button to exit Zone Response The normal loop response of each keypad expansion zone is 750mS however the response time of any zone can be reduced to 50mS as follows 1 Of the f...

Страница 20: ...ed that a GEM RP1CAe2 be selected as Keypad 1 Assign the keypad address number by selecting Jumpers J1 3 in accor dance with the table at left Note 1 Keypads are factory supplied with no jumpers insta...

Страница 21: ...ay be programmed or it may be programmed as a two digit code for the purposes of quick arming Arm Only Code Programmable in Dealer Program Mode only An Arm Only Code may only be used to arm the area i...

Страница 22: ...r disarm an Arm Only Code may only be used to arm Arming To arm enter a valid User Code then press the button If a wrong code is entered the keypad will display The green STATUS LED will go off the re...

Страница 23: ...n be armed The display will read then automatically scroll through all unsecured zones If a system trouble is indicated display the system trouble Area Arming Manager s Mode In a partitioned system ei...

Страница 24: ...forward or backward using the and the buttons respectively To return to normal keypad operation press the button The keypad will automatically return to its normal operating mode if no activity is de...

Страница 25: ...nd a 2 second warning and the keypad will begin a 15 minute countdown with the sounder pulsing The sounder may be silenced by pressing the button but it will come back on one minute before arming With...

Страница 26: ...Y Battery below 11 volts If not recharged within 24 hours replace it E03 00 COMM FAIL Unsuccessful communication to central station Note Will also display if panel improperly programmed to report i e...

Страница 27: ...lighting disabled cut Jumpers W1 W2 W3 2 Backlighting disabled cut Jumpers A B C 3 Add 0 010A for each energized relay 4 Standby Time in Hours 1 STANDBY CURRENT X Amps AH STANDBY CURRENT Amps DEVICE Q...

Страница 28: ...board be necessary use this wiring legend to relocate wire leads to their proper terminals Enter wire identification number or color code in WIRE NUMBER column and enter wire function in DESCRIPTION...

Страница 29: ...RT FUNCTION MODE Keypad Commands NEXT YES PRIOR NO AREA Scroll Down Scroll Up Exit Yes No Press Bell Test Activated Chime Toggle On Off Exit Automatically No Yes Yes System to Arm in number of hours e...

Страница 30: ...Bypassed Display Activated Bell Test Activated Chime Toggle On Off Exit Automatically Reset System Trouble Exit Automatically Activate Fault Find Download Activated Keypad Commands No No No No No No N...

Страница 31: ...Zone Numbers in Area 1 Enter Entry Exit Zone Numbers in Area 1 Enter Central Station 1 Telephone Number No No Yes Yes Enter Number of Keypads in Area 1 Enter of Zones in Area 1 Press at any time Go to...

Страница 32: ...er Program Option Enabled Bell Test Activated Chime Toggle On Off Exit Automatically No No Yes Yes System to Arm in number of hours entered w delay Exit Automatically Download Activated No No No Yes Y...

Страница 33: ...1 ALARM CURRENT CAN BE INCREASED BY REDUCING STANDBY CURRENT BY THE SAME AMOUNT 2 THE FOLLOWING DEVICES MAY BE PLACE ON THE REMOTE BUS GEM RP1CAe2 GEM RP2ASe2 GEM EZM816 GEM X10 GEM RECV8 GEM RECV16...

Страница 34: ...GEM P1632 Installation Instructions NAPCO Security Systems WI808B 8 98 Page 34 NOTES...

Страница 35: ...ary the user should consult the dealer or an experienced radio television technician for additional suggestions The user may find the following booklet prepared by the Federal Communications Commissio...

Страница 36: ...ssumes nor autho rizes any other person purporting to act on its behalf to modify to change or to assume for it any other warranty or liability concerning its products In no event shall NAPCO be liabl...

Отзывы: