GEM-P1632 Installation Instructions
NAPCO Security Systems
WI808B 8/98
Page 16
2 -W IR E S M O K E
D E T E C T O R W IR IN G
The GEM-P1632 can use conventional 12 VDC 4-wire
smoke detectors. To use them, select fire zone pro-
gramming option and do not select 2-wire smoke detec-
tor programming option for the desired fire zone (refer
to the GEM-P1632 Programming Instructions). Set JP3
to the position as shown, if zones 7 or 8 are to be used.
Two-wire smoke detectors can only be connected to zones 7 and 8. To use them,
select fire zone programming option and select 2-wire smoke detector program-
ming option for the desired fire zone 7 or 8 (refer to the GEM-P1632 Programming
Instructions) and set JP3 to the position as shown. Connect the 2-wire smoke
detectors as shown.
If the Zone Doubling is used (see EZ Zone Doubling Configuration), the respective
complementary zones (15 & 16) are disabled when 2-wire smoke detectors are
connected to zones 7 & 8.
If Fire Alarm Verification is desired to reset the smoke detectors, select this option
for the desired fire zone (zone 7 or 8).
$%
%
WI
RI
NG CONNECTI
ONS
4-WIRE SMOKE DETECTOR WIRING
6
( - )
The GEM-P1632 can use conventional 12 VDC 4-wire smoke detectors. To use
them, the select fire zone programming option and do not select 2-wire smoke
detector programming option for the desired fire zone (refer to the GEM-P1632
Programming Instructions). Set JP3 to the position as shown, if zones 7 or 8 are to
be used.
Four wire smoke detectors may be connected to any programmed fire zone (1-8) as
shown, within the panel. If the Zone Doubling is used (see EZ Zone Doubling
Configuration), the respective complementary zones (9-16) are disabled when 4-wire
smoke detectors are connected to zones 1-8. If external EZMs are used for zones
9-32, then 4-wire smoke detectors may be connected to any programmed fire zones
(9-32).
Power must be obtained from terminal 25 and 6. If Fire Alarm Verification is desired
to reset the smoke detectors, select this option for the desired fire zone.