background image

NAPCO Gemini C-Series Control Panel Installation Instructions--Volume 2 

Page 26                                                                                                                         Installation Instructions, Volume 2 

FIRE GLOSSARY 

EZM Assignments 

        The "

EZM Assignments

" tab in the 

System Assignment 

screen in PCD-Windows Quickloader download software is used to 

setup the descriptions, type, and PGM output for all the EZM's used in an installation.  The EZM assignment types are: 

        

4 Zone Burg

 - A GEMC-EZM8 configured as a 4 zone device, wired to the Burg bus. 

        

4 Zone Fire

 - A GEMC-EZM8 configured as a 4 zone device, wired to the Fire bus. 

        

4 Zone NAC EXT 

- A GEMC-NACXX configured as a NAC extender wired to the Fire bus. 

        

4 Zone Fire PS

 - The GEMC-12V2APS wired to the Fire bus. 

        

4 Zone Burg PS

 - The GEMC-12V2APS wired to the Burg bus. 

        

8 Zone Burg

 - A GEMC-EZM8 configured as an 8 zone device, wired to the Burg bus. 

        

8 Zone Fire

  - A GEMC-EZM8 configured as a 8 zone device, wired to the Fire bus. 

        

4 Zone Burg- keypad

 - The integral GEMC-BK1 Burglary keypad EZM wired to the Burg bus 

 

Fire Drill Zones 

        Select either an unused zone dedicated for use as a Fire Drill zone or select a currently used Fire zone that will also be used 

as a Fire Drill Zone (we recommend using a dedicated zone, and program its Zone Description as a "Fire Drill").  Once the 
zone is selected, in PCD-Windows Quickloader's 

NAC/Outputs Assignment 

screen (

NAC/Output Options 

tab) program the 

zone to activate outputs desired to be turned on during a fire drill.  To initiate a fire drill, enter the GEMC-FK1 Fire keypad 
Function menu and select the "Do Fire Drill" option, and the system will activate the NAC's programmed for the selected Fire 
Drill Zone to go into alarm.  "Fire Alarm", the zone number and the zone description will display on all GEMC-FK1 Fire key-
pads.   

 

Fire Keypad Supervision Trouble 

        The system will always enunciate Fire keypad troubles and report them to the central station (except local systems).  

Note:

  If 

any Fire keypad troubles or Fire relay board troubles are detected, a "peripheral device trouble" ("E330" in Point ID, "IA" in 
SIA) will be sent to the central station; if any Fire keypad trouble restores or relay board trouble restores are detected, a 
"peripheral device trouble restore" ("R330" in Point ID, "IA" in SIA) will be sent to the central station.  See also 

Fire Trouble 

Resound

 

Fire SLC Loop Trbl 

        A short on a Class B SLC loop or an open / short on a Class A loop is detected in a GEMC-FW-SLC.  See E96 in the 

Keypad 

Trouble Messages 

table earlier in this manual. 

 

Fire SLC Recv Memory Failure 

        The GEMC-FW-SLC program does not match the panel program. 
 

Fire SLC Recv No Resp 

        GEMC-FW-SLC stopped responding to polls due to malfunction, incorrect address, or connector missing or incorrect. 
 

Fire Trouble Resound 

(required UL864) 

        Trouble sounders may be silenced by unlocking the Fire keypad and pressing the 

RESET 

button.  Troubles not restored will 

"resound" (the keypad sound will beep and the 

Trouble 

icon will flash) at least once every 24 hours until the condition is cor-

rected (

note that Fire wireless troubles resound every 4 hours

).  Enable 

Fire Trouble Resound 

to report to the central 

station when a Fire system trouble resounds (in addition, if 

Fire Trouble Resound

 is programmed, a keypad supervision trou-

ble/restore will report and Relay Board supervision troubles/restores will also report.  Program in Quickloader 

System As-

signment 

screen, 

System Reporting and Outputs 

tab.  See also 

Report Fire Keypad Supervision Trouble

 

Fire Alarm Verification (Not for use in California) 

        Fire Zones programmed for "

Fire Alarm Verification

" will, when tripped, cause all zones to power down for 5 seconds.  After 

this 5-second power-down time, power is restored and a 20-second retard time is started.  Thereafter, the zone will be active 
again.  This represents a total processing delay of 25 seconds from the time the alarm is first detected.  If an alarm condition 
still exists at this time or reoccurs within 100 seconds, an alarm will be initiated, otherwise the zone will return to its original 
state.  

NOTE:  

A zone programmed for "

Fire Alarm Verification

" must be programmed as a "

Fire Zone

" as well.  

Do not 

program for wireless devices

.  

Note: 

 The GEMC-WL-SMK does not incorporate 

Fire Alarm Verification 

and thus is not 

compliant with ANSI/SIA-CP-01.

 

 

Fire Reset 
        

When selected, pressing 

RESET

 on an unlocked GEMC-FK1 Fire keypad causes the selected output to change state (on to 

off, off to on) for the time selected in "Fire Reset Duration".  Resets GEMC-F8ZCPIM zones and re-settable power output for 
latching 4-wire smoke detectors and similar devices that require power to be removed for reset.  See 

NAC Features 

 

 

Full upload, and then put panel into service 

        This  selection,  in  the  PCD-Windows  Quickloader 

Panel Communications 

screen, operates in Local, Telco, and TCP/IP 

modes.  When this option is checked, uploads are first performed into the current account's 

User 

area, then the 

Dealer 

area, 

then the 

Description 

area of the control panel.  After the data is uploaded, Quickloader immediately performs an error check; if 

no errors are found, Quickloader will send a command to the panel to remove the system trouble (E28).  If errors are found, 

Содержание GEMINI GEMC-255

Страница 1: ...COMMUNICATOR Installing the GEMINI C Series Control Panels with the GEMC FK1 Keypad and the GEMC BK1 Keypad GEMC FK1 Keypad GEMC BK1 Keypad INSTALLATION INSTRUCTIONS VOLUME 2 R Publicly traded on NASD...

Страница 2: ...d by implications or otherwise under any patent or patent rights of Napco Microsoft and Windows are registered trademarks of the Microsoft Corporation All other trademarks cited in this manual are for...

Страница 3: ...C RM2 FWC FSLC SOM1 Devices 15 Mapping Zones to Outputs 16 Burglary Outputs 17 Fire Output Option Chart 18 Fire Burg Output Devices 19 Fire Glossary 21 37 Burglary Glossary 38 62 CP 01 Quick Reference...

Страница 4: ...Failure A problem has been detected either in a wireless transmitter or a burglary SLC Point XXXXXX The wireless SLC device 6 digit ID map number NNN associated zone number Fire Burg Keypads WL SLC TR...

Страница 5: ...the bus class A or B and or an open on a class A loop Consider moving Receiver location or repairing SLC loop Fire Burg Keypads Auto Reset RECrf slc TRBL E16 NN E17 NN SYStrbl E17 xxx MM DD YY HH MM R...

Страница 6: ...he external output number followed by a programmed 29 character NAC description multiple X characters For Burglary systems a GEMC BSLC RLY is not responding or its relay is not working correctly Fire...

Страница 7: ...but not mapped programmed to any zone Fire Keypad Only Latching E94 000 SYStrbl E94 xxx MM DD YY HH MM FslcRec NoRespon E94 000 SERVICE For Fire Systems A response failure in the GEMC FW SLC Fire SLC...

Страница 8: ...g S2 for a total of 2 5A Rule 3 All notification appliances in the same field of view must use the same sync pattern The maximum current draw from Smart Synchronized circuits on either the GEMC XXXMB...

Страница 9: ...ollows 1 Do not select option Coded Alarms by Zone in the NAC Output Options screen 2 Select Silenceable and Smart for each NAC 3 Program the selected NAC to activate on fire alarm or specific zone al...

Страница 10: ...d SILENCE is pressed Subsequent alarms that occur after silence but before all fire zones are restored will reinitiate the cadence alarm Method 3 Coded Alarm by Zone The third method of synchronizatio...

Страница 11: ...an over current condition indicating a RlyTbl E35 NN followed by the programmed description of the associated NAC GEMC NACXX NAC Over Current protection when con nected to a Gemini C Series Control Pa...

Страница 12: ...he Fire bus c Fire Wireless transmitter points maximum 125 Fire and Burg wireless devices d Fire SLC Points 2 Burg Zones a Burg GEMC EZM8 zones GEMC EZM8 wired to the Burg bus b Burg GEMC BK1 Burg key...

Страница 13: ...with no other devices on the same zone Fire Wireless transmitter points require all GEMC RECV wireless receivers to be wired to the Fire bus of the mother board preventing faults on the Burg bus from...

Страница 14: ...evices and or lack of suf ficient standby battery power There are many ways to wire zones into the Gemini C Series Panels Careful planning will allow the panel to support virtually any desired combina...

Страница 15: ...external outputs enabled in 11 groups of eight and enabled only on the addressed device Each group of eight is distinctly addressed as group 1 through group 11 and only one group of the same address m...

Страница 16: ...ART fur ther in this manual In addition the selected module must also be configured for the correct relay group 1 8 using the RELAY dip switch located on the module PC board For more information see W...

Страница 17: ...for relay contact failure that also display as outputs with descriptions on the GEMC FK1 keypad Supervised Burglary outputs require that they be configured as external relay 1 40 therefore the first 4...

Страница 18: ...EO15 N A N A N A EXT OUT 16 EO16 N A N A N A EXT OUT 17 EO17 Circle one None Burg Output on 4 wire Burg Bus BURG GEMC RM3008 or BURG GEMC OUT8 Fire Output on 4 wire Fire Bus FIRE GEMC RM3008 or FIRE...

Страница 19: ...Output on Fire SLC 2 GEMC FW FSLC 2 GEMC NACXX 2 118 2 0 9 2 1 2 NAC 1 EXT OUT 10 EO10 2 117 2 1 0 2 2 2 NAC 2 EXT OUT 11 EO11 2 116 2 1 1 2 3 2 NAC 3 EXT OUT 12 EO12 2 115 2 1 2 2 4 2 NAC 4 EXT OUT 1...

Страница 20: ...OUT 58 N A 8 68 8 5 9 8 3 N A N A EXT OUT 60 N A 8 67 8 6 0 8 4 N A N A EXT OUT 61 N A 8 66 8 6 1 8 5 N A N A EXT OUT 62 N A 8 65 8 6 2 8 6 N A N A EXT OUT 63 N A 8 64 8 6 3 8 7 N A N A EXT OUT 64 N A...

Страница 21: ...ng the access number If the communicator must delay before dialing the access number in stead of attempting to recognize the dial tone find out how many 4 second delays must be programmed Alarm Output...

Страница 22: ...the line from the house phones as well as the answering machine and the connection will subse quently be established Note For Fire systems the GEMC FK1 Fire keypad must be unlocked before downloading...

Страница 23: ...e silence able NAC output typically all NAC outputs for Enable Cadence in the NAC Output As signment screen click the NAC Output Assignments tab then check the Enable checkbox for the selected output...

Страница 24: ...it also has Selective Call Waiting and confirm the disable code with the telephone company Then program this code B70 directly before the phone numbers after dial tone detection or pre dial delay in...

Страница 25: ...keypad The message will remain until the time and date have been re programmed This option is located in the PCD Windows Quickloader Keypad Features screen Enable Telco Line 1 Enable Telco Line 2 When...

Страница 26: ...v Memory Failure The GEMC FW SLC program does not match the panel program Fire SLC Recv No Resp GEMC FW SLC stopped responding to polls due to malfunction incorrect address or connector missing or inc...

Страница 27: ...he shunt from OFF to ON to enter Burg Service Mode when maintenance or changes to the Burglary hardware must be performed while keeping the Fire system in operation Entering Burg Service Mode will pre...

Страница 28: ...ry System Trouble E02 A low battery system trouble will annunciate at the keypad when the motherboard battery terminal voltage drops below nor mal and or the charging voltage drops below the nominal 2...

Страница 29: ...other Fire alarm zone initiates an alarm before all Fire zones have reset This feature is typically selected for audible Fire alarm sounding appliances Resetable To turn off a NAC programmed for Reset...

Страница 30: ...through Telco 1 or Telco 3 for all UL Commercial Fire reporting or Burg Commercial Fire reporting accounts Disabled Report Disabled Only the four integral NAC A through NAC D circuits or the followin...

Страница 31: ...detectors activate each pull station etc When detected by the system all output circuits programmed to activate when the associated zone is in alarm will sound a single momentary chirp 5 Restore the...

Страница 32: ...MX 8000 Surgard MLR 2 Osbourne Hoffman 2000e NAPCO Net Link NL RCV RMPCUL Ademco 685 Relay Event Relay outputs can be programmed to activate on a particular event or combination of events Select the...

Страница 33: ...er Test This keypad Function Menu feature TEST COMMUNICATOR will send a programmed report code to the central station Note that in this case the report code received is not indicative of a system trou...

Страница 34: ...nciators not used for evacuation sounder or required strobes To turn off these auxiliary outputs the GEMC FK1 Fire keypad must be unlocked and the option Turn Off Aux Outputs selected Smart See NAC Fe...

Страница 35: ...wire smoke detector circuit Subscriber Identification Numbers If reporting openings and or closings program Subscriber Opening Closing Identification Numbers for each area for each telephone number u...

Страница 36: ...one Dialing with Rotary Backup see the Burglary Glossary 2 Wire 4 Wire Smoke Detectors See Smoke Detectors User Assignment Controls user authority levels The tabs are as follows User System Codes Type...

Страница 37: ...Assignment screen System Reporting and Outputs tab to allow the re porting to the central station when any Fire User Code is used to unlock a Fire keypad Waterflow Waterflow Retard Time A Waterflow Zo...

Страница 38: ...ction option locations on the Wireless Keyfobs screen in PCD Windows Quickloader This feature also requires a valid time to be entered into the Burg PGM 1 Access Control in the Time Selection screen I...

Страница 39: ...11 12 13 R 1 UL INSTALLATIONS 1 Cutting the R jumper will provide Dry Contacts for the Aux Relay no voltage on COM N C and N O contacts for use with exter nal power supplies and or loads see wiring d...

Страница 40: ...ced Subscriber Opening Closing ID Numbers and Event ID Numbers if reporting System Trouble Subscriber ID Number If Priority Area Arming is selected the Priority Area must be armed before the Arming Ar...

Страница 41: ...e system and must be installed even if AC power is present Change the batteries every 4 years or as required If the GEMC BM PS is used it requires 12V battery backup BE Bypass Enable Alarm Code featur...

Страница 42: ...gram this fea ture in the Quickloader System Assignment screen System Reporting and Outputs tab Burg SLC No Resp GEMC BSLC stopped responding to polls due to malfunction incorrect address or connector...

Страница 43: ...d Access the ACTIVATE CHIME function to enable or disable the Chime Mode from the keypad This feature is programmable by zone and for duration of tone see Time Selection A time in seconds must be prog...

Страница 44: ...Trouble on Short the trouble reported will be that programmed under Day Zone Trouble Open and or Day Zone Trouble Short Note Do not program a Day Zone Trouble for 24 hour protection The keypad will a...

Страница 45: ...ypad Features screen See Selective Bypass Disable Code Required for FM Function Mode Level 1 Intended primarily for residential applications this feature eliminates the user code requirement to access...

Страница 46: ...er code Do not program Easy Arming in UL installations If closings are reported Easy Arming will report as User 199 Easy Exit Not Evaluated by UL While armed in the Interior Bypass Stay Mode Easy Exit...

Страница 47: ...E message will be displayed Enable Report Test Mode Start End At the initiation of a test the control panel sends a message to the central station that a test is in progress The Fault Find function a...

Страница 48: ...een armed with Exit Delay Restart enabled when the exit door is opened and then closed the pro grammed exit delay will restart at 60 seconds Thus if a long exit delay is programmed it will be reduced...

Страница 49: ...full protec tion in ARMED AWAY mode by arming without the E button The next time the zone is disarmed the zone will be come a full protected zone Interior zones can be made to be normally bypassed by...

Страница 50: ...pad is desired also program a Panel Access Code Keyfob Disarm Activates Entry Lighting Disarming with a keyfob can activate Remote Relays or X 10 Devices by programming the event Ext Burg Rel 1 or Ext...

Страница 51: ...Code must be Bypass Enabled 2 Press the B button The display will read BYPASS ENABLED 3 Press the B button again 4 Enter the zone The display will read BYPASSED ZONE 5 To bypass another zone repeat st...

Страница 52: ...enabled a chime will sound at the keypad while armed or disarmed when that zone is opened This feature is suggested for use as a driveway monitor or similar application NL MOD IP Address Panel IP Addr...

Страница 53: ...ut a correct PC security code Each sub field of the PC security code is ranged from 0 to 255 The user can toggle to the next sub field by either pressing the tab key or the key This PC security code w...

Страница 54: ...articular event or combination of events Select the event s in the Quick loader NAC Output Assignment screen NAC Output Events tab Click in the Event Alarm Type Condition column and the Relay Event di...

Страница 55: ...mode Select option by enabling the Program Change located in the System Assignment screen System Reporting Outputs tab Required in Fire reporting ac counts RF Receiver Trouble An trouble is generated...

Страница 56: ...s the Burg Bell to chirp instead of the Burg Module PGM1 Output upon remote arming Selective Bypass Disable Code Required for EZ Bypass Not for UL installations Any or all zones 1 255 programmed for S...

Страница 57: ...it entry door will cause an instant alarm To manually start the exit delay select the START EXIT TIME function then press ENTER to execute Note 1 If this feature is selected Exit Entry Follower Zones...

Страница 58: ...E ARMED ENABLE BURG RF RECEIVER TAMPER SOUND BURG ALARM ONLY IF ANY AREA ARMED Removing the cover of an expansion zone module will cause the sounder to pulse and the SYS TBL reminder to flash The keyp...

Страница 59: ...BOX Remember that a zero entry represents 10 Example Program Entry Delay 1 for 1 minutes 1 Entry Delay 1 is in units of seconds thus delay time is 90 seconds 2 Divide by 16 90 16 5 quotient 10 remaind...

Страница 60: ...BURG PGM2 MINUTES 4 HR 15 MIN 255 MIN 2 N A CHIME SECONDS 63 25 SEC 255 QTR SEC 3 N A BURG AUX RELAY MINUTES 4 HR 15 MIN 255 MIN N A BURG PGM1 MINUTES 4 HR 15 MIN 255 MIN 2 N A BURG PGM1 ACCESS CONTR...

Страница 61: ...each code can be assigned four different Authority Levels 0 1 2 or 3 and five Attributes Initially Off BV User Program BE and Overview and can be assigned to Area s 2 8 with Area 1 being reserved for...

Страница 62: ...include a Panic Zone as part of any Group Auto Reset must be programmed for each Zone ANDing Zone Note Any zone that is bypassed or goes into Swinger Shutdown will automatically disable Zone Anding f...

Страница 63: ...ble time is 255 seconds The panel uses the existing programmable by zone feature Entry Exit 1 to comply with CP 01 At least one Entry Exit zone must be programmed for each area The existing programmab...

Страница 64: ...tation that Test Mode is in progress Fault Find can not be initiated from an armed panel and all digital dialer reporting in same area is inhibited while in Fault Find Keypad will display the followin...

Страница 65: ...ed less than 10 seconds after the Ambush Code for an ambush report to be sent When ENABLE GLOBAL AMBUSH is selected and no Ambush code has been entered and the keypads have been selected for AMBUSH th...

Страница 66: ...em Sensor Format thus requiring System Sensor Synchronized Horn Strobes be installed All 4 NAC s are synchronized not offset as required for more than 4A total alarm current The AUX Fire relay is prog...

Страница 67: ...24V7A and GEMC BM 2 12V 7AH 7 154 225 2 5A 3 5A 0 750 2 12V 8AH 8 190 278 2 5A 4A 0 750 4 12V 7AH 14 405 591 2 5A 7A 0 750 4 12V 8AH 16 480 700 2 5A 7A 0 750 6 12V 7AH 21 667 974 2 5A 7A 0 750 6 12V 8...

Страница 68: ...0 0 500 4 12V 8AH 16 480 700 2 5A 7A 0 750 0 500 6 12V 7AH 21 667 974 2 5A 7A 0 750 0 500 6 12V 8AH 24 780 1138 2 5A 7A 0 750 0 500 8 12V 7AH 28 930 1357 2 5A 7A 0 750 0 500 8 12V 8AH 32 1100 1400 2 5...

Страница 69: ...NAPCO Gemini C Series Control Panel Installation Instructions Volume 2 Installation Instructions Volume 2 Page 69 NOTES...

Страница 70: ...NAPCO Gemini C Series Control Panel Installation Instructions Volume 2 Page 70 Installation Instructions Volume 2 NOTES...

Страница 71: ...NAPCO Gemini C Series Control Panel Installation Instructions Volume 2 Installation Instructions Volume 2 Page 71 NOTES...

Страница 72: ...red by others improperly installed improperly used abused altered damaged subjected to accident nuisance flood fire or acts of God or on which any serial numbers have been altered defaced or removed N...

Отзывы: