GENERAL DESCRIPTION 

The NAPCO NetLink™ GEMC-NL-MOD is a device that al-
lows the reporting of alarms over a TCP/IP based (Intranet or 
Internet) network.  Alarm reporting, previously performed via 
Telco only, can now be performed over both a TCP/IP net-
work and/or Telco, or via the TCP/IP network as a backup.  
The GEMC-NL-MOD is housed in a separate plastic enclo-
sure, and is connected to the Local Download receptacle for 
the Gemini C-Series control panels. 
The GEMC-NL-MOD is supported by PCD-Windows Quick-
loader download software version 6.0 or greater.  For the pan-
els listed above, the Quickloader software will support 
downloading through the Internet or an intranet, as well as the 
uploading of logs and other data.   

 

The GEMC-NL-MOD includes a small transient protection de-
vice (named the NL-ULBD) inside its enclosure.  In addition, 
the GEMC-NL-MOD is one part of a larger system which in-
cludes a software package to allow its configuration before 
use (the NL-MODCONFIG) and a rack-mountable Receiver 
(the NL-RCV-RMPCUL) to allow the receipt of alarms, status 
and supervisory data.  A short description of each is provided 
below: 

 

NL-MODCONFIG Software

 (version 2.0 or greater): 

NL-MODCONFIG is a software program allowing the con-
figuration of the GEMC-NL-MOD with appropriate informa-
tion (such as the static IP address of the module, static IP 
address of the NL-RCV-RMPCUL Receiver, etc.).  The NL-
MODCONFIG software is run on a PC (see System Re-
quirements) and connects to the GEMC-NL-MOD via its 
network connection.  In addition, NL-MODCONFIG allows 
the updating of the GEMC-NL-MOD firmware.  

Note:

 The 

NL-MODCONFIG software and its database should be re-
tained if future access is necessary.  For more information, 
see WI1243. 

Central Station Receiver (NL-RCV-RMPCUL) 

The NAPCO Net.Link™ NL-RCV-RMPCUL (Receiver) is a 
fully UL compliant central station receiver platform.  This 
Receiver is rack-mountable in a standard 4U configuration.  
The NL-RCV-RMPCUL (Receiver) can supervise each 
GEMC-NL-MOD, receive alarms, provide a means of 
maintaining accounts and provide a means of displaying 
alarms and event history (opening/closing, etc.).  For more 
information, see the NL-RCV-RMPCUL Installation and 
programming manual, WI1491. 

 

Transient Protection (NL-ULBD) 

The GEMC-NL-MOD includes electromagnetic protection 
and meets direct and indirect ESD requirements for Infor-
mation Technology Equipment (ITE), however, burglary 
applications may call for better protection. 
The NL-ULBD is a small device which gives added tran-
sient protection and mounts entirely inside the GEMC-NL-

MOD housing.  The NL-ULBD protects the GEMC-NL-
MOD from significantly larger transients and surges which 
may emanate from the network cable or associated de-
vices.  It is connected in series between the Ethernet cable 
that provides network access and the RJ45 connector in 
the GEMC-NL-MOD.  The NL-ULBD is required for UL 
compliant installations. 
 

SPECIFICATIONS 

    Electrical Ratings 

      

Input Power:

  Nominal 12VDC, 85mA. 

      

Note:  

12V power must be supplied from GEMC-

Series motherboard 

AUX PWR

 terminals.  Available 

panel 12V combined auxiliary current is reduced by 
85mA. 

      

Output Power:

  PGM-style open collector (negative 

trigger) with a maximum sink current of 50mA.  Wire 
only to power-limited circuits less than 14VDC. 

       

Dimensions:  

1½" x 7" x 4¾" (H x W x D) 

 

MAXIMUM WIRE LENGTH 

The GEMC-NL-MOD must be mounted inside the NAPCO 
Gemini GEMC-Series control panel enclosure.  For Fire Alarm 
control panels, the GEMC-NL-MOD must be installed inside a 
separate UL 864 Listed enclosure.  In addition, no more than 
20 feet of conduit can be used if connected to a fire alarm con-
trol panel.  

NOTE: 

For a UL Supplemental Listing, the wire 

length (GEMC-NL-MOD to control panel) must be no more 
than 20 feet and the panel shall reside in the same room as 
the GEMC-NL-MOD with no intervening walls or barriers.  

NOTE:

  For best results when making RJ-45 cable assem-

blies, it is recommended to use an 

AMP

 Brand Professional 

crimping tool (part # 3-231652-0), and to always match the 
type of cable used (stranded or solid) with the correct type of 
RJ-45 plug. 
 

SYSTEM REQUIREMENTS 

System Hardware

Compatible Gemini C-Series Control Panel. 

W1077 harness (see wiring diagram). 

Access to the local area network. 

 

NL-MODCONFIG Software

Windows

®

 XP Professional or Windows

®

 2000. 

 

(Windows

®

 XP Home Edition is 

not 

supported). 

 

NL-RCV-RMPCUL Rack-Mount Receiver or NL-CSRCV 
Software

 (software not for UL installations): 

See WI1491 for the NL-RCV-RMPCUL installation and 
programming instructions. 

 
 

R

333 Bayview Avenue 

Amityville, New York 11701 

For Sales and Repairs, (800) 645-9445 

For Technical Service, (800) 645-9440 

Publicly traded on NASDAQ     Symbol: NSSC

 

© NAPCO 2010 

WI1754  08/10 

NAPCO GEMC-NL-MOD 

 

Network Communication Module 

 

INSTALLATION INSTRUCTIONS

 

Содержание GEMC-NL-MOD

Страница 1: ...ctromagnetic protection and meets direct and indirect ESD requirements for Infor mation Technology Equipment ITE however burglary applications may call for better protection The NL ULBD is a small dev...

Страница 2: ...informs the control panel that an GEMC NL MOD will be installed in the system and thus will make the appropriate adjustments to various downloading timeouts and to reporting properties Click Apply to...

Страница 3: ...hall reside in the same room as the GEMC NL MOD with no intervening walls or barriers Mount using the mounting flanges on both sides of the GEMC NL MOD enclosure using the screws appropri ate for the...

Страница 4: ...on and re main on during the GEMC NL MOD startup sequence duration is approximately 15 seconds The LED will turn off for up to 20 seconds while the GEMC NL MOD verifies its configuration The LED will...

Страница 5: ...s Connect this Supervi sory Output to control an Air Products and Controls PAM 4 relay Wire the relay contact to a zone that can be programmed for a trouble or supervisory 4 Power Up NL MOD UL Upon ap...

Страница 6: ...d users the upper and lower voltage limits can be programmed into the GEMC NL MOD To enable these settings to be changed check Edit Thresh olds Do NOT check Edit Thresholds for Fire Installa tions If...

Страница 7: ...t RJ 45 ROUTER RJ 45 ROUTER NL RCV RMPCUL Rack Mounted UL Listed for Commercial Fire and Burglary Central Station Receiver Windows is a registered trademark of the Microsoft Corporation Other products...

Страница 8: ...ocal DNLD RJ25 4 User Defined Inputs Generic FACP Control Panels Panic Bell GND 12V Terminal 1 12V Terminal 2 GND Terminal 3 DATA Terminal 4 BELL Terminal 5 IN0 Terminal 6 IN1 Terminal 7 IN2 Terminal...

Страница 9: ...reen 7 User Defined Parallel Input 2 Configured by the Optional Input Setup screen 8 User Defined Parallel Input 3 Configured by the Optional Input Setup screen 9 Supervisory Active Low 10 Ringback Ac...

Страница 10: ...10 NOTES...

Страница 11: ...11 NOTES...

Страница 12: ...ed altered damaged subjected to accident nuisance flood fire or acts of God or on which any serial numbers have been altered defaced or removed NAPCO will not be responsible for any dismantling reasse...

Отзывы: