Chime Zones in Area 1
(New Program Only)
•
Enter the zone numbers which are to be used as Chime Zones.
•
Valid entries are from 01 to 32. Directly enter each zone number, including leading zeros.
•
Press
u
to save and then repeat for any additional zone(s), press
p
to proceed.
NOTE:
A chime time of 2 seconds will be automatically programmed.
Chime 2 Zones in Area 1
(New Program Only)
•
Enter the zone numbers which are to be used as Chime 2 Zones.
•
Valid entries are from 01 to 32. Directly enter each zone number, including leading zeros.
•
Press
u
to save and then repeat for any additional zone(s), Press
p
to proceed.
NOTE:
A chime time of 2 seconds will be automatically programmed.
Chime 2 zones give a distinct pulsating tone when zone is faulted.
Exit/Entry2 Zones in Area 1
(New Program Only)
•
Enter the zone numbers of zones to be used as Exit/Entry zones.
•
Valid entries are from 01 to 32. Directly enter each zone number, including leading zeros.
•
Press
u
to save and repeat for any additional zone(s); press
p
to proceed.
NOTE:
An Exit/Entry 2 Entry Time of 30 seconds will automatically be programmed.
50 mS Loop Response Zones
(New Program Only)
•
Enter the zone numbers of zones to be have a 50mS loop response.
•
Valid entries are from 01 to 08. Directly enter each zone number, including leading zeros.
•
Press
u
to save and then repeat for any additional zone(s), Press
p
to proceed.
Note:
Only
panel zones 01-08 can be programmed for Quick Loop Response. Time can also be adjusted via ad-
dress 2280.
Aux Output Activated on Alarm Zones
(New Program Only)
•
Enter the zone numbers of zones to activate the PGM2 upon alarm.
•
Valid entries are from 01 to 32. Directly enter each zone number, including leading zeros.
•
Press
u
to save and then repeat for any additional zone(s), Press
p
to proceed.
NOTE:
A PGM2 Timeout of 15 minutes will automatically be programmed.
Sensor Watch Zones
(New Program Only)
•
Enter the zone numbers of zones to be Sensor Watch zones.
•
Valid entries are from 01 to 32. Directly enter each zone number, including leading zeros.
•
Press
u
to save and then repeat for any additional zone(s), Press
p
to proceed.
NOTE:
A Sensor Watch Time of 24 hours will automatically be programmed.
Keypad Sounder On Alarm Zones
(New Program Only)
•
Enter the zone numbers of all zones to activate the Keypad Sounder upon alarm.
•
Valid entries are from 01 to 32. Directly enter each zone number, including leading zeros.
•
Press
u
to save and then repeat for any additional zone(s), Press
p
to proceed.
Auto Bypass Re-entry Zones
(New Program Only)
•
Enter the zone numbers of zones to be Auto Bypass Re-entry zones.
•
Valid entries are from 01 to 32. Directly enter each zone number, including leading zeros.
•
Press
u
to save and then repeat for any additional zone(s), Press
p
to proceed.
•
Auto Bypass Re-entry Zones allow the system to be armed with the zone faulted but come back into
the system (armed) when the zone is subsequently closed.
Enable No EOLR Zones
(New Program Only)
•
Press YES to program all zones except 24 Hr & fire zones for No End Of Line Resistor. Press
q
to continue.
Enable Telco Line Fault Test?
•
Press
p
to enable Telco Line Fault Test.
•
Press
q
to continue.
NOTE: If enabled, a Telco Line Fault Test Delay of 60 seconds will
automatically be programmed.
(Direct Entry)
C h i m e Z o n e s
E n t e r Z o n e # ° °
(Direct Entry)
C h i m e 2 Z o n e s
E n t e r Z o n e # ° °
(Direct Entry)
E x i t / E n t r y 2 Z o n e s
E n t e r Z o n e # ° °
(Direct Entry)
5 0 m S L o o p Z o n e s
E n t e r Z o n e # ° °
(Direct Entry)
A u x O u t p u t Z o n e s
E n t e r Z o n e # ° °
(Direct Entry)
S e n s o r W a t c h Z n s
E n t e r Z o n e # ° °
(Direct Entry)
K P S n d r A l r m Z n s
E n t e r Z o n e # ° °
(Direct Entry)
A u t o B y p R E n t Z n
E n t e r Z o n e # ° °
(Press YES or NO)
E n a b l e N o E O L R
Z o n e s Y / N
(Press YES or NO)
Enable Telco
Line Test? Y/N
Содержание GEM-DXK1
Страница 56: ...LIBRA LIB P432EX Series Programming Instructions NAPCO Security Systems Page 56 LIB P432EX WIRING DIAGRAM...
Страница 57: ...NAPCO Security Systems LIBRA LIB P432EX Series Programming Instructions Page 57 LIB P432EXT WIRING DIAGRAM...
Страница 58: ...LIBRA LIB P432EX Series Programming Instructions NAPCO Security Systems Page 58 LIB P432EXT 230 WIRING DIAGRAM...
Страница 59: ...NAPCO Security Systems LIBRA LIB P432EX Series Programming Instructions Page 59 NOTES...