7
Problem solving
7.1
General causes
General
Malfunctioning can for example be caused by:
•
Mistakes made during installation
•
Pressures below the minimum pressure
•
Excessive amount of condensate (overloading)
•
Blocked or shut off outlet line
•
Excessive amount of dirt particles
•
Frozen piping
7.2
Faults and remedies
Danger:
Before starting any maintenance or repairs, close the air outlet valve and press the
test button on top of the electronic water drain to depressurize the air system.
Note:
Apply all relevant instructions in section Safety precautions.
Problem solving
Error
Reason
Solution
The drain does not discharge
condensate: the condensate
drain does not indicate an
alarm.
There is no condensate in the
condensate drain:
•
The external shut-off valve
between the discharge
point and the condensate
drain is closed.
•
The externally installed
filter is clogged.
•
The condensate drain has
not been installed correctly.
There may be a siphon
effect and/or air bubble
upstream of the
condensate drain.
•
The supply voltage is not
powering the condensate
drain.
•
Check the supply shut-off
valve of the condensate
drain.
•
Check the filter that might
be installed externally in
the condensate supply line.
•
Check the installation.
•
Ensure that the tube
leading to the compensate
drain is free.
•
Ensure that there is
electrical power.
•
If the aforementioned
points have been verified,
the condensate drain is
operating correctly.
•
Try a manual discharge
with the TEST button.
Instruction book
2920 7213 30
35