INSTALLATION AND OPERATION MANUAL

ELECTRIC HEATERS FOR 

VAV TERMINAL UNITS

Page 1 of 4

6/20  IOM-EHVAV (Supercedes 4/02) 

GENERAL INFORMATION

• Nailor electric heaters require little or no maintenance.

Be sure the heater elements are free of foreign matter,

and then check that the connections are tight and proper

control interlocks have been made before turning the

heater on.

• Heaters are open wire type and, except on very small

heaters with element wires less than 1 kW, use special

‘arrowhead’ insulators that expose the entire surface area

of the element wires to the air stream. This eliminates the

possibility of hot spots on the larger wires that can burn

the elements in half or cause spalding that enhances hot

spots.

• All electric heaters ordered from Nailor are manufactured

in-house.

• All Nailor electric coils are ETL listed for safety under UL

1995 as part of the VAV unit.

• All electric heating units have built-in controls for all

options required by the engineer.

• Single point power connection.

INSTALLATION

• All single duct terminal units with electric coils are

designed to be mounted in a horizontal plane with respect

to the "UP" arrow marked on the product label.  Fan

powered units can be flipped over in the field and will not

have "UP" arrow.

• Before applying power, make sure electric coils are not

damaged.

• All field wiring must comply with NEC and local building

codes.

• Use copper conductors only.
• Phase rotation of the incoming power is recommended

when connecting three-phase electric coils.

• Allow a minimum clearance as specified by NEC in front of

all electric coil enclosures.

• Always check product label to determine proper wire size

and current protection.

• These recommendations do not preclude NEC or local

building codes that may be in effect.

OPERATION

• To avoid possible nuisance tripping of the thermal cutouts

due to insufficient airflow, a minimum airflow of 70 cfm

(33L/s) per kilowatt must be maintained.

• For Single Duct Terminal Units, A minimum of .1” w.g. (25

Pa) of downstream static pressure is required to ensure

proper operation of the heater.

Figure 1. Fan Powered Terminal Unit with Electric Heater

Figure 2. Single Duct Terminal Unit with Electric Heater

   CAUTION: 

ELECTRIC SHOCK HAZARD

1.  Turn off power before servicing unit.
2. Do not operate unit without control cover

.

Содержание D35SE

Страница 1: ... point power connection INSTALLATION All single duct terminal units with electric coils are designed to be mounted in a horizontal plane with respect to the UP arrow marked on the product label Fan powered units can be flipped over in the field and will not have UP arrow Before applying power make sure electric coils are not damaged All field wiring must comply with NEC and local building codes Us...

Страница 2: ...EL Electric coil data are incorporated in the nameplate label which is affixed to the control enclosure cover The label shows all necessary information required by UL with respect to electrical power and circuit protection requirements HEATER CONTROL ENCLOSURE Figure 4 shows the interior of a typical heater control enclosure All components within this space work together to provide safe operation ...

Страница 3: ...re on the side of the terminal electric heater section 1 Turn off power supply before servicing 2 Locate the element rack header plate 3 Before removing wires from the element rack header plate mark where the wires are connected so they can be reconnected correctly on the new element rack 4 Remove the wires and screws holding the heater plate in the coil housing 5 Insert the new element rack into ...

Страница 4: ...600V 30Amp EC CONM30A3P SCR SSR SCR Elect Heat controller 600V 1ph 45A EC SCR SSR Elect Heat controller 600V 1ph 45A EC SSR Transformers Transformer 120V 24V 50VA EC TRANS120A Transformer 208 240V 24V 50VA EC TRANS208A Transformer 277V 24V 50VA EC TRANS277A Transformer 480V 24V 50VA EC TRANS480A Isolation Transformer 24V 24V 40VA EC TRANS2424 Transformer 120V 208 240 480 to 24V 75VA EC TRANSB Tran...

Отзывы: