background image

Technical Data

1446

Power Supply

24 VAC, ±20%, 50/60 Hz, 24 VDC, 0% / 

+50%

Power consumption in operation 27 VA
Power consumption in rest 

position

3 W, 6.5 VA, End stop 55 VA, 2.5 A slow 

blow fuse *

Transformer sizing

40 VA (class 2 power source)

Shaft Diameter

1/2” to 1.05” round, centers on 1/2” and 

3/4” with insert, 1.05” without insert

Electrical Connection

18 GA, 3 ft [1 m], 2 color coded wires

Overload Protection

electronic throughout 0° to 95° rotation

Electrical Protection

actuators are double insulated

Angle of rotation

95°

Torque motor

70 in-lb [8 Nm] from 32...350°F [0...177°C]

direction of rotation motor

reversible with CW/CCW mounting

direction of rotation spring-return reversible with cw/ccw mounting
Position indication

visual indicator, 0° to 95°  (0° is full spring 

return position)

Running Time (Motor)

15 sec between 32...350°F [0...177°C], <15 

sec at rated voltage & torque

Running Time (Fail-Safe)

15 sec

Ambient humidity

5...95% r.H. non-condensing

Ambient temperature

32...122°F [0...50°C]

Non-operating temperature

-40...176°F [-40...80°C]

Degree of Protection

IP40, NEMA 1

Housing material

zinc coated steel

Gears

steel, permanently lubricated

Agency Listing

cULus listed to UL873 and CAN/CSA C22.2 

No.24, UL 2043 Listed for air plenum 

installation per NEC 300.22 and IMC 

Section 602 

NYC Department of Buildings MEA 197-

07-M.California State Fire Marshal Listing 

3210-1593:101.

Noise level, motor

45 dB (A) motor, 62 dB (A) spring, 

inaudible holding 

Maintenance

maintenance free

Quality Standard

ISO 9001

Weight

5.71 lb [2.8 kg]

† UL File XAPX.E108966

Fire & Smoke damper actuator

Application

The type FSNF spring-return actuator is intended for the operation of smoke 

and combination fire and smoke dampers in ventilation and air-conditioning 

systems. The actuator will meet requirements of UL555 and UL555S when 

tested as an assembly with the damper and will meet requirements of UBC for 

15 second opening and closing at 350°F. Square footage of damper operated 

will depend on make and model and the temperature required.

IMPORTANT 24VDC NOTE: The FSNF24 & -S models will not operate below 
24VDC. A filtered and regulated power supply must be used.

Operation

Mounting of the actuator to the damper axle shaft or jackshaft (3/8” to 1.05”) is 

via a cold-weld clamp. Teeth in the clamp and V-bolt dig into the metal of both 

solid and hollow shafts maintaining a perfect connection. The specially designed 

clamp will not crush hollow shafts. The bottom end of the actuator is held by an 

anti-rotation strap or by a stud provided by the damper manufacturer.

The actuator is mounted in its fail safe position with the damper blade(s) closed. 

Upon applying power, the actuator drives the damper to the open position. The 

internal spring is tensioned at the same time. If the power supply is interrupted, 

the spring moves the damper back to its fail-safe position.

Dimensions (Inches[mm])

Standard:
       1/2" to 1.05"
     

Optional*
       3/8" to 3/4"

*with K4 US clamp

1.97"

3.15" [80

]

3.86" [98

]

2.24"  [57]

[5

]

[50]

1.93" [49]

2.89" [73.5]

2.64"

[67]

0.26" [6.5]

5.85" [148.5]

10.20" [259]

0.35" [9]

0.39" [10]

0.65" [16.5]

0.19" [5]

[ø41.2]

ø1.62"

[191.6]

7.54"

0.19" 

3.25" [82.7]

Safety Notes

* Neither UL nor Belimo require local over-current protection. The FSNF 

actuators draw higher peak current when driving against any type of stop. If 

used, this requires the value of a local fuse or breaker to be increased to avoid 

nuisance opening or tripping. A 2.5 amp slow blow should be used for 24VAC. 

A 0.5 amp slow blow should be used for 120 VAC. A 0.25 amp slow blow 

should be used for 230V and a 0.3 amp slow blow for 208 VAC. Transformers: 

Note that while a 24V 100VA transformer would handle 2 actuators, a 4 A 

breaker or plug fuse is insufficient. A 5 amp slow blow would be required. 

Belimo Fire & Smoke actuators have passed the AMCA 520 and UL 555S Long 

Term Holding test. No special cycling is required during prolonged periods 

when actuator is driven open and held there. Periodic testing of dampers and 

actuators per local codes and NFPA 80 and NFPA 105 are required. 

The actuator contains no components which the user can replace or repair. 

A 1/2” threaded connector is standard.  FSNFxx-FC models have a 3/8” Flex 

Connector. Other than the connector, these actuators are identical to the 

conduit connector version.

 WARNING: For Belimo Products sold in California, these Products do or 

may contain chemicals which are known to the State of California to cause 

cancer and or birth defects or other reproductive harms. For more information 

see www.p65warnings.ca.gov.

FSNF24 US

On/Off, Spring Return, 350°F [177°C] for a half hour, 15 Seconds Cycle Time

800-543-9038 USA

866-805-7089 CANADA

203-791-8396 LATIN AMERICA / CARIBBEAN

Date created, 04/10/2019 - Subject to change. © Belimo Air

controls (USA), Inc.

Содержание 1210SS

Страница 1: ...es Jackshaft 1 2 13 dia stainless steel Jamb Seals Cambered stainless steel Sizes Damper W x H Note Dampers with duct heights less than 8 203 require a Type B sleeve enclosure Model 1212SS Units less than 8 203 in width only or in both width and height require a Type C enclosure Model 1213SS BASE MODEL SELECTION 1210SS With side actuator mounting plate 1211SS Standard factory sleeve caulked to UL ...

Страница 2: ... bolted to blades Jackshaft 1 2 13 dia stainless steel Jamb Seals Cambered stainless steel Sizes Duct W x H Note Duct sizes less than 8 203 in width only or in both width and height require a Type C enclosure Model 1213SS SLEEVE ENCLOSURE SELECTION 1212SS Standard factory sleeve caulked to UL requirements 16 long x 20 ga 406 x 1 0 18 ga for dampers over 84 2134 in width 1212SS Non standard sleeve ...

Страница 3: ...tainless steel double bolted to blades Jackshaft 1 2 13 dia stainless steel Jamb Seals Cambered stainless steel Sizes Duct Diameter SLEEVE ENCLOSURE SELECTION 1213SS Standard factory sleeve caulked to UL requirements 16 long x 20 ga 406 x 1 0 18 ga for dampers over 84 2134 in width 1213SS Non standard sleeve Specify _______ length _____ ga Available up to 36 914 in length and 10 through 20 ga 3 5 ...

Страница 4: ... Axles 1 2 13 dia stainless steel double bolted to blades Jackshaft 1 2 13 dia stainless steel Jamb Seals Cambered stainless steel Sizes Duct W x H SLEEVE ENCLOSURE SELECTION 1213SS Standard factory sleeve caulked to UL requirements 16 long x 20 ga 406 x 1 0 18 ga for dampers over 84 2134 in width 1213SS Non standard sleeve Specify _______ length _____ ga Available up to 36 914 in length and 10 th...

Страница 5: ...ctric Resettable Link Damper Test Switch ERL Reset Temp 165 F 212 F 250 F 350 F ERL DTS 12 19 DTS Push To Test Press and hold down Momentary push button until damper has fully cycled The electric resettable link is manual reset type L2 L1 BLK BLK ELECTRIC ACTUATOR OR EP SWITCH WHT MOUNTED ON DAMPER FACTORY WIRING TERMINATES AT SPLICE POINTS INDICATED INSIDE 4 x 4 ELECTRICAL BOX HEAT SENSOR ERL M B...

Страница 6: ...S 12 19 ERL DTS Combination Fire Smoke Damper DTO DTS Combination Fire Smoke Damper DTS Smoke Damper Model Series Open OP Closed CL MSXX04 Yellow Yellow Blue Blue MSXX20 Yellow Yellow Blue Blue Honeywell Actuator Aux Switch Wiring Connections WHT BLK BLK BLK BLK RED L2 L1 CLOSED RED LIGHT OPEN GREEN LIGHT CONTROL SWITCH NORMAL MS2 DAMPER CLOSED LOWER MICROSWITCH BLU BLU YEL YEL MS1 DAMPER OPEN UPP...

Страница 7: ...CT SIZE 1 4 6 NOTE Smoke Dampers shall be installed in accordance with NFPA 90A latest edition and Nailor installation instructions see IOM SDINST Dampers must be installed within 24 610 of the smoke barrier to conform with installation requirements SMP SIDE ACTUATOR MOUNTING PLATE JACKSHAFT DRIVE MODELS 9 229 WIDTH NOM DUCT SIZE 1 8 3 HEIGHT NOM DUCT SIZE 1 4 6 5 127 1 25 16 406 STD 12 305 MIN W ...

Страница 8: ...Reversible mounting facilitates use in either clockwise cw or counterclockwise ccw spring rotation Integral spring return ensures level of return torque Stainless steel internal spring Fifteen second spring return timing No special cycling required during long term holding See Operation section No audible noise during holding Patent pending design eliminates need for limit switches to reduce power...

Страница 9: ...ntrol system Refer to National Fire Protection Association NFPA National Fire Codes NFPA90A NFPA92A and NFPA92B for your application NFPA recommends periodic examination of each fire smoke damper semi annually or annually to ensure proper performance Mounting Self centering shaft adapter Round Damper Shafts 0 5 to 1 06 in Square Damper Shafts 1 2 to 3 4 in Actuator can be mounted with shaft in any...

Страница 10: ...ion Control Reversible Mount Spring Return 20 175 lb in 20 Nm F Fire and Smoke US 1 No Feedback 0 No Auxiliary Switches 2 Two Auxiliary Switches XX System Controlled Numbers M S 41 20 F 1 2 XX Table 3 Actuator Selection S20 Series S Fail Safe Function Spring Return 20 20 Nm 175 lb in 24 24 Vac 2 position Control Reversible Mount Spring Return 230 230 Vac 2 position Control Reversible Mount Spring ...

Страница 11: ... housing can damage actuator Mount actuator to allow it to float along its vertical axis Preparation Before mounting the actuator onto the damper shaft determine the Damper valve opening direction for correct spring return rotation The actuator can be mounted to provide clockwise or counterclockwise spring return Damper shaft size see Specifications section Determine Appropriate Mounting Orientati...

Страница 12: ... on damper housing 3 Remove actuator and mounting bracket 4 Drill or center punch holes for mounting screws or use no 10 self tapping sheet metal screws NOTE If necessary use a field fabricated steel base plate secured with sheet metal screws 5 Turn damper blades to desired normal closed position 6 Place actuator and mounting bracket back into position and secure bracket to damper box with sheet m...

Страница 13: ...equipment circuitry Disconnect power supply before installation CAUTION Electrical Shock or Equipment Damage Hazard Disconnect all power supplies before installation Motors with auxiliary switches can have more than one disconnect IMPORTANT 1 All wiring must comply with local electrical codes ordinances and regulations 2 Voltage and frequency of transformer used with MS8120F S and S2024 F must cor...

Страница 14: ...al 230 Vac wiring S20 Series M20678A BLUE BROWN 230 VAC S2024 F SW2 MS8120S L1 L2 BLACK BLUE BLACK RED BLACK YELLOW GRAY RED GRAY BLUE GRAY YELLOW 85 AUXILIARY SWITCH 7 AUXILIARY SWITCH M20680A BLUE BROWN 230 VAC S20230 F SW2 MS4620S L1 L2 BLACK BLUE BLACK RED BLACK YELLOW GRAY RED GRAY BLUE GRAY YELLOW 7 AUXILIARY SWITCH 85 AUXILIARY SWITCH ...

Страница 15: ...ould drive the damper 3 If the actuator does not run remove power for at least two seconds 4 If the actuator spring returns allow it to close entirely then return to step 2 5 If the actuator does not spring return verify that the actuator is properly installed See Installation section 6 If the actuator is correctly installed but neither runs nor spring returns replace the actuator MS4620F S20230 F...

Страница 16: ...ation DK Installasjonsinstruks S Installations Instrukioner I Istruzioni per I Installazione N Installationsinstrukioner E Instrucciones de montage A A1 A4 A2 A5 A3 A6 M20730B a b 10 mm M20729A a b d c b M20728A b a M20727A M20726A ASSEMBLY EINBAU MONTAGE MONTAGGIO MONTAGE MONTERE MONTERING ASENTAMINEN MONTERA MONTAJE D F I NL DK N FIN S E 24 VAC 120 VAC 230 VAC M12030 a b ...

Страница 17: ...TING TWO POSITION ACTUATORS 63 2584 10 10 B B1 B4 B3 B2 M20735B M20734A a M20733B M20732A a b M20731B 24 VAC 120 VAC 230 VAC DISASSEMBLY AUSBAU DÉMONTAGE SMONTAGGIO DEMONTAGE AFMONTERE DEMONTERE PURKAMINEN NEDMONTERA DESMONTAJE D F I NL DK N FIN S E ...

Страница 18: ...MS4120F MS4620F MS8120F S2024 F S20230 F FAST ACTING TWO POSITION ACTUATORS 11 63 2584 10 ...

Страница 19: ...Douglas Drive North Golden Valley MN 55422 customer honeywell com U S Registered Trademark 2012 Honeywell International Inc 63 2584 10 M S Rev 03 12 Printed in United States Teflon is a registered trademark of the E I du Pont de Nemours and Company National Fire Codes is a registered trademark of the National Fire Protection Association NFPA ...

Страница 20: ...n either clockwise cw or counterclockwise ccw spring rotation Integral spring return ensures level of return torque Fifteen second spring return timing No special cycling required during long term holding See Operation section No audible noise during holding Patent pending design eliminates need for limit switches to reduce power consumption Models available for 24 120 and 230 Vac Ninety five degr...

Страница 21: ...or coded leads Mounting Round 1 2 inch shaft adapter with 1 4 inch set screws Threads 20 UNC 2A Material Alloy Steel hardened to HRC 45 53 Thread Lock Nylon Patch IMPORTANT Honeywell does not recommend using linkages with these actuators because side loading of the output hub reduces actuator life Temperature Ratings Ambient 0 F to 130 F 18 C to 55 C Shipping and Storage 40 F to 140 F 40 C to 60 C...

Страница 22: ...nal codes for periodic testing of the entire smoke control sys tem Refer to National Fire Protection Association NFPA National Fire Codes NFPA90A NFPA92A and NFPA92B for your application NFPA recommends periodic examination of each fire smoke damper semi annually or annually to ensure proper perfor mance Design Life at Rated Voltage 30 000 full stroke cycles Approvals See Table 3 Environmental Pro...

Страница 23: ... Location and Mounting The actuators are designed to open a damper by driving the damper shaft in either clockwise or counterclockwise direction The actuator housing has two slots on the bottom that with a 205649 Mounting Bracket secure it flush to a damper box see Fig 2 When mounted correctly these slots allow the actuator to float without rotating relative to the damper shaft CAUTION Equipment D...

Страница 24: ...ing min imum 100 lb in maximum 130 lb in torque Use 1 4 in wrench see Specifications for details to tighten set screws Wiring See Fig 3 through 5 for typical wiring diagrams WARNING Electrical Power Hazard Line voltage can cause death or serious injury and short equipment circuitry Disconnect power supply before installation CAUTION Electrical Shock or Equipment Damage Hazard Low voltage can shock...

Страница 25: ...rsion to 350 F 176 C CHECKOUT MS4104F MS4109F 120 Vac model 1 Check damper position 2 Connect 120 Vac to the black and white leadwires to drive the damper to the open position The actuator should drive the damper 3 If the actuator does not spring return verify that the actu ator is properly installed See Installation section 4 If the actuator is correctly installed but neither runs nor spring retu...

Страница 26: ...7 63 2740 05 ...

Страница 27: ...rol Solutions Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 customer honeywell com U S Registered Trademark 2013 Honeywell International Inc 63 2740 05 M S Rev 12 13 Printed in United States ...

Страница 28: ...limiting property damage including damage to the HVAC system itself Refer to NFPA Standards 72 90A and 92 to determine when and where duct smoke detectors are required The DSD NF detector can be factory installed to side of sleeve on Nailor Model Series 1210 1260 1280 1220 and 1270 A minimum airflow velocity of 100 fpm 0 5 m s is required for Model DSD LF OPERATION Upon detection of smoke the smok...

Страница 29: ...e from spreading within the HVAC system is vital to preventing injury as well as limiting property damage including damage to the HVAC system itself Refer to NFPA Standards 72 90A and 92 to determine when and where duct smoke detectors are required The DSD NF detector features a low profile design for optimum pressure drop and will operate with airflow in either direction It can be factory install...

Страница 30: ...pply must be used Operation Mounting of the actuator to the damper axle shaft or jackshaft is via a cold weld clamp Teeth in the clamp and V bolt dig into the metal of both solid and hollow shafts maintaining a perfect connection The specially designed clamp will not crush hollow shafts The bottom end of the actuator is held by an anti rotation strap or by a stud provided by the damper manufacture...

Страница 31: ...ode requirements Wiring Diagrams APPLICATION NOTES Provide overload protection and disconnect as required 45 Actuators may be powered in parallel Power consumption must be observed 75 Ground present on some models 45 2 Hot 1 Neutral 3 Ground 1 N White L1 Black 120 VAC Detector or relay F S Damper 2 1 HOT 165 F To alarm system Manual reset Actuator N L2 or COM Typical containment damper control wir...

Страница 32: ...e used Operation Mounting of the actuator to the damper axle shaft or jackshaft is via a cold weld clamp Teeth in the clamp and V bolt dig into the metal of both solid and hollow shafts maintaining a perfect connection The specially designed clamp will not crush hollow shafts The bottom end of the actuator is held by an anti rotation strap or by a stud provided by the damper manufacturer The actua...

Страница 33: ... code requirements Wiring Diagrams APPLICATION NOTES Provide overload protection and disconnect as required 45 Actuators may be powered in parallel Power consumption must be observed 75 Ground present on some models N Blue L1 Brown 1 N L2 2 Hot 3 Ground 45 1 230 VAC Detector or relay F S Damper 2 1 HOT 165 F To alarm system Manual reset Actuator N L2 or COM Typical containment damper control wirin...

Страница 34: ...ulated power supply must be used Operation Mounting of the actuator to the damper axle shaft or jackshaft is via a cold weld clamp Teeth in the clamp and V bolt dig into the metal of both solid and hollow shafts maintaining a perfect connection The specially designed clamp will not crush hollow shafts The bottom end of the actuator is held by an anti rotation strap or by a stud provided by the dam...

Страница 35: ...s will be provided per code requirements Wiring Diagrams APPLICATION NOTES Provide overload protection and disconnect as required 45 Actuators may be powered in parallel Power consumption must be observed 75 Ground present on some models 24 VAC Detector or relay F S Damper 2 1 HOT 165 F To alarm system Manual reset Actuator N L2 or COM Typical containment damper control wiring Detector or relay F ...

Страница 36: ...e metal of both solid and hollow shafts maintaining a perfect connection The specially designed clamp will not crush hollow shafts The bottom end of the actuator is held by an anti rotation strap or by a stud provided by the damper manufacturer The actuator is mounted in its fail safe position with the damper blade s closed Upon applying power the actuator drives the damper to the open position Th...

Страница 37: ... Belimo FSTF FSLF FSNF or FSAF actuators All substitutions must be approved before submission of bid Damper and actuator shall have UL 555S Listing for 250 F 350 F Actuator shall have been tested to UL 2043 per requirements of IMC 602 2 and NEC 300 22 c Where position indication is required S models with auxiliary switches or damper blade switches will be provided per code requirements Wiring Diag...

Страница 38: ...ction The specially designed clamp will not crush hollow shafts The bottom end of the actuator is held by an anti rotation strap or by a stud provided by the damper manufacturer The actuator is mounted in its fail safe position with the damper blade s closed Upon applying power the actuator drives the damper to the open position The internal spring is tensioned at the same time If the power supply...

Страница 39: ... shall be provided with Belimo FSTF FSLF FSNF or FSAF actuators All substitutions must be approved before submission of bid Damper and actuator shall have UL 555S Listing for 250 F 350 F Actuator shall have been tested to UL 2043 per requirements of IMC 602 2 and NEC 300 22 c Where position indication is required S models with auxiliary switches or damper blade switches will be provided per code r...

Страница 40: ...e clamp and V bolt dig into the metal of both solid and hollow shafts maintaining a perfect connection The specially designed clamp will not crush hollow shafts The bottom end of the actuator is held by an anti rotation strap or by a stud provided by the damper manufacturer The actuator is mounted in its fail safe position with the damper blade s closed Upon applying power the actuator drives the ...

Страница 41: ...tuators All substitutions must be approved before submission of bid Damper and actuator shall have UL 555S Listing for 250 F 350 F Actuator shall have been tested to UL 2043 per requirements of IMC 602 2 and NEC 300 22 c Where position indication is required S models with auxiliary switches or damper blade switches will be provided per code requirements Wiring Diagrams INSTALLATION NOTES Provide o...

Страница 42: ...0 Vdc Standard Mounting MS1 is damper open signal MS2 is damper closed signal Non Standard Mounting Important Installer must double check continuity of MS1 and MS2 before wiring to determine which switch signals the damper s open or closed position EXTERNAL RIGHT HAND MOUNTING FRONT VIEW LESS COVER COVER A A 2 7 8 73 3 76 4 1 8 105 MS 2 MS 1 BLUE YELLOW SECTION A A JACKSHAFT DRIVESHAFT EXTENSION C...

Страница 43: ... MS4604F1210 MS4609F1210 Ratings maximum load 120 VAC 24 VDC 3A resistive Settings fixed 7 nominal stroke 85 nominal stroke Model MS8104F1210 MS8109F1210 Ratings maximum load 24 VAC DC 3A resistive Settings fixed 7 nominal stroke 85 nominal stroke Model MS4120F1204 MS4620F1203 MS8120F1200 Ratings maximum load 250 VAC 5A resistive Settings fixed 7 nominal stroke 85 nominal stroke Belimo Model FSTF1...

Отзывы: