SCHEDULE TYPE:
PROJECT:
ENGINEER:
CONTRACTOR:
DATE
B SERIES
SUPERSEDES DRAWING NO.
5 - 7 - 12
1200
3 - 21 - 11
1210SS-4
STAINLESS STEEL SMOKE DAMPER
AIRFOIL BLADE • HIGH PERFORMANCE
ULTRA-LOW LEAKAGE • SQUARE,
RECT. OR OVAL DUCT CONNECTION
MODEL: 1213SS (TYPE C SLEEVE ENCLOSURE)
Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
For installation instructions, see IOM-SDINST.
Dimensions are in inches (mm).
The 1210SS Series dampers are ideal for high humidity, mildly corrosive
or, with optional Type 316 construction, more severe environments where
building codes require a leakage rated smoke damper as part of a static
smoke control or dynamic smoke management system.
The 1210SS Series has been especially designed and tested to offer
premium performance. The 1210SS Series provides the lowest leakage
class available and is qualified for vertical or horizontal installation with
airflow in either direction. Airfoil blade design and elimination of blade
sills, top and bottom, provide lowest pressure drop. Unique inter-locking
double skin blade design eliminates combustible blade seals and provides
flame and smoke seal under fire conditions.
STANDARD SPECIFICATION:
Frame:
5" x 7/8" x 16 ga. (127 x 22 x 1.6) stainless steel hat channel.
Blades:
14 ga. (2.0) equivalent stainless steel formed airfoil on
5 1/2" (140) centers.
Linkage:
Concealed in frame. 12 ga. (2.7) stainless steel.
Bearings:
1/ 2" (13) dia. sintered stainless steel.
Axles:
1/ 2" (13) dia. stainless steel double bolted to blades.
Jackshaft:
1/2" (13) dia. stainless steel.
Jamb Seals:
Cambered stainless steel.
Sizes (Duct W x H):
SLEEVE/ENCLOSURE SELECTION:
❑
1213SS
Standard factory sleeve (caulked to UL requirements) 16"
long x 20 ga. (406 x 1.0) (18 ga. for dampers over 84"
[2134] in width).
❑
1213SS
Non-standard sleeve. Specify _______ length _____ ga.
Available up to 36" (914) in length and 10 through 20 ga.
(3.5 through 1.0).
CONSTRUCTION TYPE:
❑
304
Type 304 Stainless Steel construction (Standard).
❑
316
Type 316 Stainless Steel construction (Optional).
LEAKAGE CLASS / ELEVATED TEMPERATURE:
❑
I
❑
II @ 250°F
DYNAMIC VELOCITY/PRESSURE RATING:
24
2000 fpm @ 4" w.g.
ACTUATOR SELECTION:
❑
Electric
❑
Pneumatic
'C' ENCLOSURE BOTH ENDS
D –
1/8" (3)
(D –
1/4" (6)
OVER
36"
(914))
16" (406) STANDARD
5" (127)
8" (203)
STANDARD
JACKSHAFT
ACTUATOR LOCATION:
❑
External
(std.)
❑
Internal
(in the airstream)
ACTUATOR FAIL POSITION:
❑
Normally Closed
(std.)
❑
Normally Open
OPTIONS:
❑
MLS-300
Position indicator switch pack
W = NOM. DUCT
S
IZE
W + 2" (51) (MIN.
8
" [20
3
])
H =
NOM.
DUCT
S
IZE
H
+
2"
(51)
CCW
TO
OPEN
W + 2" (51
) (MIN.
8
" [20
3
])
W
H
H
+
2"
(51)
*
*
*
or 8" (203) min.
QUALIFICATIONS:
• UL 555S CLASSIFIED SMOKE DAMPER (File # R9492)
Leakage Class I or II at 250°F elevated temperature.
• Meets NFPA 90A, 92A, 92B, 101 and 105 as well as IBC and
NBC (Canada) Building Code requirements.
• California State Fire Marshal Listing No. 03230-0935:107.
• City of New York MEA# 366-03-M.
• Maximum velocity: 2000 fpm@ 4" w.g.
Velocity/
Pressure
Rating
Elevated
Temp.
°F
Minimum
Maximum
Single Section
Single Section
Multiple Section
Vertical/Horizontal
Vertical/Horizontal Vertical/Horizontal
24
250
4" x 4" (102 x 102)
(Overall damper size is
8" x 8" [203 x 203] minimum).
34" x 46"
(864 x 1168)
142" x 94"
(3607 x 2388)