Accessories
---BAE165 US 165° F electric thermal sensor, SPST, normally closed.
---S2A-F US
Auxiliary switch, 2x SPDT, 3A (0.5A inductive) @250 VAC
max.
Typical Specification
All smoke and combination fire and smoke dampers shall be provided
with Belimo FSTF, FSLF, FSNF, or FSAF actuators. All substitutions must be
approved before submission of bid. Damper and actuator shall have UL 555S
Listing for 250°F (350°F). Actuator shall have been tested to UL 2043 per
requirements of IMC 602.2 and NEC 300.22 (c). Where position indication is
required -S models with auxiliary switches or damper blade switches will be
provided per code requirements.
Wiring Diagrams
APPLICATION NOTES
Provide overload protection and disconnect as required.
45
Actuators may be powered in parallel. Power consumption must be
observed.
75
Ground present on some models.
N (Blue)
L1 (Brown)
1 N, L2
2 Hot
3 Ground
45
1
230 VAC
Detector or relay
F&S Damper
2 1
HOT
165°F
To alarm
system
Manual
reset
Actuator
N, L2,
or COM
Typical containment damper control wiring
Detector or relay
F&S Damper
2 1
HOT
To alarm
system
Actuator
N, L2,
or COM
Fusible link F&S
or smoke
damper
Typical smoke or fusible link damper wiring
Parallel Actuator Wiring
FSLF230 US
On/Off, Spring Return, 350°F [177°C] for a half hour, 15 Seconds Cycle Time
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA / CARIBBEAN
Date created, 03/08/2019 - Subject to change. © Belimo Air
controls (USA), Inc.