background image

Page

“ C o m p l e t e   A i r   C o n t r o l   a n d   D i s t r i b u t i o n   S o l u t i o n s . ”

w w w . n a i l o r . c o m

Calgary, Canada

Tel: 403-279-8619

Fax: 403-279-5035

Houston, Texas

Tel: 281-590-1172

Fax: 281-590-3086

Toronto, Canada

Tel: 416-744-3300

Fax: 416-744-3360

Las Vegas, Nevada

Tel: 702-648-5400

Fax: 702-638-0400

“ C o m p l e t e   A i r   C o n t r o l   a n d   D i s t r i b u t i o n   S o l u t i o n s . ”

Page 2.091

2/20  IOM-FSDIMP

Page 2 of 2

Dampers with Position Indicating Device

1. Use the signal from the damper’s position indication device to determine if the damper is in the fully open position.

2. Remove air pressure or electrical power from the actuator to cause the actuator’s spring return feature to close the 

damper.

3. Use the signal from the damper’s position indication device to determine if the damper is in the fully closed position.

4. Reapply air pressure or electrical power to reopen the damper.

5. Use the signal from the damper’s position indication device to determine if the damper is in the fully open position.

Dampers without Position Indicating Device

1. Visually confirm that the damper is in the fully open position.

2. Ensure that all obstructions are out of the path of the damper blades and then remove air pressure or electrical power 

from the actuator to cause the actuator to spring to the fully closed position.

3. Visually confirm that the damper is in the fully closed position.

4. Reapply air pressure or electrical power to reopen the damper.

Care should be exercised to ensure that all tests are performed safely by personnel wearing the appropriate personal 

protective equipment and such tests do not cause system damage. All inspections and testing shall be documented 

indicating the location of the damper, date of inspection, name of inspector, deficiencies detected, and how deficiencies 

were corrected.

Отзывы: